1,400 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
13.54 kW
11.98 kW
El input
2.96 kW
4.02 kW
COP
4.57
2.98
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
63 dB(A)
63 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
152 %
121 %
Prated
23.00 kW
22.00 kW
SCOP
3.88
3.09
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
18.78 kW
17.76 kW
COP Tj = -7°C
2.92
2.13
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
13.90 kW
13.72 kW
COP Tj = +2°C
3.79
2.97
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
13.50 kW
13.45 kW
COP Tj = +7°C
5.34
4.54
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
15.90 kW
15.85 kW
COP Tj = 12°C
6.31
5.78
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
18.78 kW
17.76 kW
COP Tj = Tbiv
2.92
2.13
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
18.57 kW
17.36 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.67
1.86
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
70 °C
70 °C
Poff
7 W
7 W
PTO
10 W
10 W
PSB
7 W
7 W
PCK
10 W
10 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
4.43 kW
4.64 kW
Annual energy consumption Qhe
12194 kWh
14720 kWh