0,420 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
4.11 kW
4.24 kW
El input
0.85 kW
1.41 kW
COP
4.84
3.01
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
52 dB(A)
52 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
186 %
136 %
Prated
5.70 kW
5.70 kW
SCOP
4.72
3.48
Tbiv
-10 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
5.56 kW
5.74 kW
COP Tj = -7°C
2.88
2.27
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
3.22 kW
3.21 kW
COP Tj = +2°C
4.69
3.44
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
1.93 kW
1.79 kW
COP Tj = +7°C
6.57
4.58
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
1.76 kW
1.65 kW
COP Tj = 12°C
7.92
5.78
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
5.70 kW
5.70 kW
COP Tj = Tbiv
2.83
2.05
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.70 kW
5.70 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.83
2.05
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
70 °C
70 °C
Poff
5 W
5 W
PTO
8 W
8 W
PSB
5 W
5 W
PCK
8 W
8 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
2494 kWh
3380 kWh