1,800 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
9.10 kW
9.95 kW
El input
2.04 kW
3.31 kW
COP
4.46
3.01
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
64 dB(A)
64 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
179 %
134 %
Prated
9.61 kW
10.06 kW
SCOP
4.54
3.44
Tbiv
-7 °C
-7 °C
TOL
-25 °C
-25 °C
Pdh Tj = -7°C
8.50 kW
8.90 kW
COP Tj = -7°C
3.01
2.31
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
5.18 kW
5.49 kW
COP Tj = +2°C
4.42
3.35
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
4.20 kW
4.00 kW
COP Tj = +7°C
5.68
4.17
Cdh Tj = +7 °C
0.990
0.990
Pdh Tj = 12°C
4.78 kW
4.61 kW
COP Tj = 12°C
7.64
5.69
Cdh Tj = +12 °C
0.990
0.990
Pdh Tj = Tbiv
8.50 kW
8.90 kW
COP Tj = Tbiv
3.01
2.31
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
8.17 kW
8.60 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.82
2.18
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.990
WTOL
55 °C
55 °C
Poff
16 W
14 W
PTO
16 W
15 W
PSB
16 W
14 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.44 kW
1.46 kW
Annual energy consumption Qhe
4367 kWh
6053 kWh