1,300 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
6.66 kW
7.18 kW
El input
1.42 kW
2.42 kW
COP
4.68
2.96
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
59 dB(A)
59 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
187 %
136 %
Prated
6.76 kW
6.84 kW
SCOP
4.76
3.46
Tbiv
-7 °C
-7 °C
TOL
-25 °C
-25 °C
Pdh Tj = -7°C
5.98 kW
6.05 kW
COP Tj = -7°C
2.76
2.04
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
3.65 kW
3.85 kW
COP Tj = +2°C
4.72
3.46
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
2.60 kW
2.39 kW
COP Tj = +7°C
6.23
4.32
Cdh Tj = +7 °C
0.990
0.900
Pdh Tj = 12°C
3.01 kW
2.94 kW
COP Tj = 12°C
8.33
6.24
Cdh Tj = +12 °C
0.990
0.990
Pdh Tj = Tbiv
5.98 kW
6.05 kW
COP Tj = Tbiv
2.76
2.04
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
6.04 kW
6.12 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.67
1.89
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
55 °C
55 °C
Poff
14 W
14 W
PTO
15 W
15 W
PSB
14 W
14 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.72 kW
0.72 kW
Annual energy consumption Qhe
2934 kWh
4082 kWh