Certificate holders

Subtype

Monoblock Heat Pump 4 6 kW

Certificate Holder
Zhejiang Zhongguang Electrical Co., Ltd.
No. 96 Yunjing Road Shuige Industry Area, Lishui
323000 Zhejiang
China
Registration number
011-1W0670
Certification Body
DIN CERTCO Gesellschaft für Konformitätsbewertung mbH
Subtype title
Monoblock Heat Pump 4 6 kW
Driving energy
Electricity
Heat Pump Type
Outdoor Air/Water
Refrigerant
R32
Mass of Refrigerant

1,200 kg

Certification Date
23.08.2023
Testing basis
HP KEYMARK certification scheme rules V12
Generate PDF Export model CSV
  • Number of models 2

Models

AHb04VR3HP
Configure model
Model name
AHb04VR3HP
Application
Heating (medium temp)
Units
Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

4.20 kW

4.40 kW

El input

0.82 kW

1.47 kW

COP

5.15

3.00

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

57 dB(A)

57 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

195 %

139 %

Prated

4.10 kW

4.00 kW

SCOP

4.95

3.56

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

3.65 kW

3.55 kW

COP Tj = -7°C

3.29

2.10

Cdh Tj = -7 °C

0.980

0.990

Pdh Tj = +2°C

2.33 kW

2.39 kW

COP Tj = +2°C

4.60

3.36

Cdh Tj = +2 °C

0.960

0.970

Pdh Tj = +7°C

2.28 kW

2.68 kW

COP Tj = +7°C

7.23

5.56

Cdh Tj = +7 °C

0.930

0.960

Pdh Tj = 12°C

1.94 kW

2.64 kW

COP Tj = 12°C

10.04

6.82

Cdh Tj = +12 °C

0.920

0.950

Pdh Tj = Tbiv

3.65 kW

3.55 kW

COP Tj = Tbiv

3.29

2.10

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

3.49 kW

3.50 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.78

1.84

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.980

0.990

WTOL

60 °C

60 °C

Poff

15 W

15 W

PTO

21 W

21 W

PSB

15 W

15 W

PCK

43 W

43 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.61 kW

0.50 kW

Annual energy consumption Qhe

1711 kWh

2320 kWh

AHb06VR3HP
Configure model
Model name
AHb06VR3HP
Application
Heating (medium temp)
Units
Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

6.20 kW

6.00 kW

El input

1.24 kW

2.00 kW

COP

5.00

3.00

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

59 dB(A)

59 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

185 %

131 %

Prated

6.10 kW

5.20 kW

SCOP

4.71

3.35

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

5.41 kW

4.62 kW

COP Tj = -7°C

3.15

2.04

Cdh Tj = -7 °C

0.990

0.990

Pdh Tj = +2°C

3.53 kW

3.60 kW

COP Tj = +2°C

4.08

3.07

Cdh Tj = +2 °C

0.980

0.980

Pdh Tj = +7°C

2.28 kW

2.68 kW

COP Tj = +7°C

7.27

5.26

Cdh Tj = +7 °C

0.930

0.960

Pdh Tj = 12°C

1.94 kW

2.64 kW

COP Tj = 12°C

10.14

6.84

Cdh Tj = +12 °C

0.920

0.950

Pdh Tj = Tbiv

5.41 kW

4.62 kW

COP Tj = Tbiv

3.15

2.04

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

5.25 kW

4.07 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.84

1.56

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.990

0.990

WTOL

60 °C

60 °C

Poff

15 W

15 W

PTO

21 W

21 W

PSB

15 W

15 W

PCK

43 W

43 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.85 kW

1.13 kW

Annual energy consumption Qhe

2677 kWh

3208 kWh