Subtype

Intelligent Inverter Heat Pump 40-R290

Certificate Holder
Ecoer Inc.
43671 Trade Center Place, Suite 100 Dulles
20166 Virginia
United States
Registration number
041-K063-02
Certification Body
BRE Global Limited
Subtype title
Intelligent Inverter Heat Pump 40-R290
Driving energy
Electricity
Heat Pump Type
Outdoor Air/Water
Refrigerant
R290
Mass of Refrigerant

0,850 kg

Certification Date
14.08.2023
Testing basis
Heat Pump Keymark Scheme Rules Rev 12
Generate PDF Export model CSV Download certificate
  • Number of models 1

Models

PASRW040-BP-PS-D
Configure model
Model name
PASRW040-BP-PS-D
Application
Heating (medium temp)
Units
Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

10.92 kW

10.36 kW

El input

2.08 kW

3.38 kW

COP

5.26

3.07

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

56 dB(A)

57 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

193 %

147 %

Prated

9.46 kW

9.02 kW

SCOP

4.90

3.76

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

8.37 kW

7.98 kW

COP Tj = -7°C

3.20

2.38

Cdh Tj = -7 °C

0.990

0.990

Pdh Tj = +2°C

5.23 kW

4.90 kW

COP Tj = +2°C

4.82

3.66

Cdh Tj = +2 °C

0.990

0.990

Pdh Tj = +7°C

5.76 kW

5.73 kW

COP Tj = +7°C

6.09

4.84

Cdh Tj = +7 °C

0.990

0.990

Pdh Tj = 12°C

6.25 kW

6.11 kW

COP Tj = 12°C

7.52

6.08

Cdh Tj = +12 °C

0.990

0.990

Pdh Tj = Tbiv

8.37 kW

7.98 kW

COP Tj = Tbiv

3.20

2.38

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

9.47 kW

9.00 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.82

1.99

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.990

0.990

WTOL

60 °C

60 °C

Poff

9 W

9 W

PTO

9 W

9 W

PSB

9 W

9 W

PCK

42 W

42 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.02 kW

Annual energy consumption Qhe

3988 kWh

4959 kWh