Certificate holders

Subtype

Hi-Therma Monobloc 14 16

Certificate Holder
Qingdao Hisense Hitachi Air-conditioning Systems Co.,Ltd.
Qianwangang Road
266555 Qingdao, Shandong
China
Registration number
011-1W0662
Certification Body
DIN CERTCO Gesellschaft für Konformitätsbewertung mbH
Subtype title
Hi-Therma Monobloc 14 16
Driving energy
Electricity
Heat Pump Type
Outdoor Air/Water
Refrigerant
R32
Mass of Refrigerant

2,000 kg

Certification Date
10.08.2023
Testing basis
HP KEYMARK certification scheme rules V12
Generate PDF Export model CSV
  • Number of models 4

Models

AHZ-140HCDS1
Configure model
Model name
AHZ-140HCDS1
Application
Heating (medium temp)
Units
Outdoor
Climate Zone
Warmer Climate
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

14.00 kW

13.00 kW

El input

2.91 kW

4.26 kW

COP

4.80

3.05

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

66 dB(A)

66 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

250 %

170 %

Prated

13.70 kW

14.10 kW

SCOP

6.33

4.33

Tbiv

7 °C

7 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

13.56 kW

13.68 kW

COP Tj = +2°C

3.56

2.48

Cdh Tj = +2 °C

0.900

0.900

Pdh Tj = +7°C

8.81 kW

9.07 kW

COP Tj = +7°C

5.50

3.80

Cdh Tj = +7 °C

0.900

0.900

Pdh Tj = 12°C

4.11 kW

3.90 kW

COP Tj = 12°C

7.95

5.41

Cdh Tj = +12 °C

0.900

0.900

Pdh Tj = Tbiv

8.81 kW

9.07 kW

COP Tj = Tbiv

5.50

3.80

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

13.56 kW

13.68 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

3.56

2.48

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

65 °C

65 °C

Poff

10 W

10 W

PTO

13 W

13 W

PSB

10 W

10 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.14 kW

0.42 kW

Annual energy consumption Qhe

2896 kWh

4348 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

66 dB(A)

66 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

181 %

132 %

Prated

11.50 kW

11.50 kW

SCOP

4.59

3.37

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

10.20 kW

10.18 kW

COP Tj = -7°C

3.01

2.21

Cdh Tj = -7 °C

0.900

0.900

Pdh Tj = +2°C

6.22 kW

6.20 kW

COP Tj = +2°C

4.38

3.23

Cdh Tj = +2 °C

0.900

0.900

Pdh Tj = +7°C

4.15 kW

4.11 kW

COP Tj = +7°C

6.26

4.45

Cdh Tj = +7 °C

0.900

0.900

Pdh Tj = 12°C

3.72 kW

3.59 kW

COP Tj = 12°C

6.93

5.60

Cdh Tj = +12 °C

0.900

0.900

Pdh Tj = Tbiv

10.20 kW

10.18 kW

COP Tj = Tbiv

3.01

2.21

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

11.01 kW

11.05 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.66

1.82

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

60 °C

60 °C

Poff

10 W

10 W

PTO

13 W

13 W

PSB

10 W

10 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.49 kW

0.45 kW

Annual energy consumption Qhe

5191 kWh

7047 kWh

AHZ-140HEDS1
Configure model
Model name
AHZ-140HEDS1
Application
Heating (medium temp)
Units
Outdoor
Climate Zone
Warmer Climate
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

14.00 kW

13.00 kW

El input

2.91 kW

4.26 kW

COP

4.80

3.05

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

66 dB(A)

66 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

250 %

170 %

Prated

13.70 kW

14.10 kW

SCOP

6.33

4.33

Tbiv

7 °C

7 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

13.56 kW

13.68 kW

COP Tj = +2°C

3.56

2.48

Cdh Tj = +2 °C

0.900

0.900

Pdh Tj = +7°C

8.81 kW

9.07 kW

COP Tj = +7°C

5.50

3.80

Cdh Tj = +7 °C

0.900

0.900

Pdh Tj = 12°C

4.11 kW

3.90 kW

COP Tj = 12°C

7.95

5.41

Cdh Tj = +12 °C

0.900

0.900

Pdh Tj = Tbiv

8.81 kW

9.07 kW

COP Tj = Tbiv

5.50

3.80

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

13.56 kW

13.68 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

3.56

2.48

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

65 °C

65 °C

Poff

10 W

10 W

PTO

13 W

13 W

PSB

10 W

10 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.14 kW

0.42 kW

Annual energy consumption Qhe

2896 kWh

4348 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

66 dB(A)

66 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

181 %

132 %

Prated

11.50 kW

11.50 kW

SCOP

4.59

3.37

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

10.20 kW

10.18 kW

COP Tj = -7°C

3.01

2.21

Cdh Tj = -7 °C

0.900

0.900

Pdh Tj = +2°C

6.22 kW

6.20 kW

COP Tj = +2°C

4.38

3.23

Cdh Tj = +2 °C

0.900

0.900

Pdh Tj = +7°C

4.15 kW

4.11 kW

COP Tj = +7°C

6.26

4.45

Cdh Tj = +7 °C

0.900

0.900

Pdh Tj = 12°C

3.72 kW

3.59 kW

COP Tj = 12°C

6.93

5.60

Cdh Tj = +12 °C

0.900

0.900

Pdh Tj = Tbiv

10.20 kW

10.18 kW

COP Tj = Tbiv

3.01

2.21

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

11.01 kW

11.05 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.66

1.82

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

60 °C

60 °C

Poff

10 W

10 W

PTO

13 W

13 W

PSB

10 W

10 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.49 kW

0.45 kW

Annual energy consumption Qhe

5191 kWh

7047 kWh

AHZ-160HCDS1
Configure model
Model name
AHZ-160HCDS1
Application
Heating (medium temp)
Units
Outdoor
Climate Zone
Warmer Climate
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

16.00 kW

15.00 kW

El input

3.48 kW

5.08 kW

COP

4.60

2.95

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

67 dB(A)

67 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

250 %

172 %

Prated

14.10 kW

14.10 kW

SCOP

6.34

4.37

Tbiv

7 °C

7 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

13.88 kW

13.80 kW

COP Tj = +2°C

3.48

2.45

Cdh Tj = +2 °C

0.900

0.900

Pdh Tj = +7°C

9.09 kW

9.08 kW

COP Tj = +7°C

5.56

3.72

Cdh Tj = +7 °C

0.900

0.900

Pdh Tj = 12°C

4.14 kW

4.14 kW

COP Tj = 12°C

7.98

5.60

Cdh Tj = +12 °C

0.900

0.900

Pdh Tj = Tbiv

9.09 kW

9.08 kW

COP Tj = Tbiv

5.56

3.72

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

13.88 kW

13.80 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

3.48

2.45

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

65 °C

65 °C

Poff

10 W

10 W

PTO

13 W

13 W

PSB

10 W

10 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.22 kW

0.30 kW

Annual energy consumption Qhe

2980 kWh

4320 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

67 dB(A)

67 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

176 %

131 %

Prated

13.00 kW

12.50 kW

SCOP

4.47

3.35

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

11.50 kW

11.07 kW

COP Tj = -7°C

2.95

2.28

Cdh Tj = -7 °C

0.900

0.900

Pdh Tj = +2°C

6.84 kW

6.69 kW

COP Tj = +2°C

4.19

3.12

Cdh Tj = +2 °C

0.900

0.900

Pdh Tj = +7°C

4.37 kW

4.38 kW

COP Tj = +7°C

6.25

4.48

Cdh Tj = +7 °C

0.900

0.900

Pdh Tj = 12°C

3.80 kW

3.88 kW

COP Tj = 12°C

6.80

5.98

Cdh Tj = +12 °C

0.900

0.900

Pdh Tj = Tbiv

11.50 kW

11.07 kW

COP Tj = Tbiv

2.95

2.28

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

12.80 kW

11.99 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.62

1.76

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

60 °C

60 °C

Poff

10 W

10 W

PTO

13 W

13 W

PSB

10 W

10 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.20 kW

0.51 kW

Annual energy consumption Qhe

6003 kWh

7712 kWh

AHZ-160HEDS1
Configure model
Model name
AHZ-160HEDS1
Application
Heating (medium temp)
Units
Outdoor
Climate Zone
Warmer Climate
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

16.00 kW

15.00 kW

El input

3.48 kW

5.08 kW

COP

4.60

2.95

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

67 dB(A)

67 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

250 %

172 %

Prated

14.10 kW

14.10 kW

SCOP

6.34

4.37

Tbiv

7 °C

7 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

13.88 kW

13.80 kW

COP Tj = +2°C

3.48

2.45

Cdh Tj = +2 °C

0.900

0.900

Pdh Tj = +7°C

9.09 kW

9.08 kW

COP Tj = +7°C

5.56

3.72

Cdh Tj = +7 °C

0.900

0.900

Pdh Tj = 12°C

4.14 kW

4.14 kW

COP Tj = 12°C

7.98

5.60

Cdh Tj = +12 °C

0.900

0.900

Pdh Tj = Tbiv

9.09 kW

9.08 kW

COP Tj = Tbiv

5.56

3.72

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

13.88 kW

13.80 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

3.48

2.45

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

65 °C

65 °C

Poff

10 W

10 W

PTO

13 W

13 W

PSB

10 W

10 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.22 kW

0.30 kW

Annual energy consumption Qhe

2980 kWh

4320 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

67 dB(A)

67 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

176 %

131 %

Prated

13.00 kW

12.50 kW

SCOP

4.47

3.35

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

11.50 kW

11.07 kW

COP Tj = -7°C

2.95

2.28

Cdh Tj = -7 °C

0.900

0.900

Pdh Tj = +2°C

6.84 kW

6.69 kW

COP Tj = +2°C

4.19

3.12

Cdh Tj = +2 °C

0.900

0.900

Pdh Tj = +7°C

4.37 kW

4.38 kW

COP Tj = +7°C

6.25

4.48

Cdh Tj = +7 °C

0.900

0.900

Pdh Tj = 12°C

3.80 kW

3.88 kW

COP Tj = 12°C

6.80

5.98

Cdh Tj = +12 °C

0.900

0.900

Pdh Tj = Tbiv

11.50 kW

11.07 kW

COP Tj = Tbiv

2.95

2.28

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

12.80 kW

11.99 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.62

1.76

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

60 °C

60 °C

Poff

10 W

10 W

PTO

13 W

13 W

PSB

10 W

10 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.20 kW

0.51 kW

Annual energy consumption Qhe

6003 kWh

7712 kWh