Certificate holders

Subtype

Tri-Thermal Split series 12 14 16 kW(Single Phase)

Certificate Holder
GD TCL Intelligent Heating & Ventilating Equipment Co., Ltd.
No. 7 Yuanlin Road,
Guangdong
China
Registration number
041-K051-05
Certification Body
BRE Global Limited
Subtype title
Tri-Thermal Split series 12 14 16 kW(Single Phase)
Driving energy
Electricity
Heat Pump Type
Outdoor Air/Water
Refrigerant
R32
Mass of Refrigerant

1,840 kg

Certification Date
29.08.2023
Testing basis
Heat Pump Keymark Scheme Rules Rev 12
Generate PDF Export model CSV Download certificate
  • Number of models 6

Models

Indoor unit: SMKL-16D/HBp-A, Outdoor unit: THF-12D/HBpO-A
Configure model
Model name
Indoor unit: SMKL-16D/HBp-A, Outdoor unit: THF-12D/HBpO-A
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

12.10 kW

12.00 kW

El input

2.42 kW

3.85 kW

COP

5.00

3.12

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

44 dB(A)

44 dB(A)

Sound power level outdoor

64 dB(A)

64 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

252 %

173 %

Prated

11.00 kW

12.00 kW

SCOP

6.39

4.41

Tbiv

7 °C

7 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

11.00 kW

12.00 kW

COP Tj = +2°C

3.61

2.27

Cdh Tj = +2 °C

0.900

0.900

Pdh Tj = +7°C

7.20 kW

8.00 kW

COP Tj = +7°C

5.65

3.75

Cdh Tj = +7 °C

0.900

0.900

Pdh Tj = 12°C

4.70 kW

4.30 kW

COP Tj = 12°C

8.33

5.95

Cdh Tj = +12 °C

0.900

0.900

Pdh Tj = Tbiv

7.20 kW

8.00 kW

COP Tj = Tbiv

5.65

3.75

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

11.00 kW

12.00 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

3.61

2.27

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

65 °C

65 °C

Poff

14 W

14 W

PTO

24 W

24 W

PSB

14 W

14 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

2330 kWh

3752 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

44 dB(A)

44 dB(A)

Sound power level outdoor

64 dB(A)

64 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

163 %

119 %

Prated

11.00 kW

10.00 kW

SCOP

4.15

3.05

Tbiv

-15 °C

-15 °C

TOL

-22 °C

-22 °C

Pdh Tj = -7°C

7.20 kW

6.70 kW

COP Tj = -7°C

3.51

2.58

Cdh Tj = -7 °C

0.900

0.900

Pdh Tj = +2°C

4.20 kW

4.00 kW

COP Tj = +2°C

5.05

3.68

Cdh Tj = +2 °C

0.900

0.900

Pdh Tj = +7°C

3.20 kW

2.90 kW

COP Tj = +7°C

6.17

4.57

Cdh Tj = +7 °C

0.900

0.900

Pdh Tj = 12°C

3.60 kW

3.30 kW

COP Tj = 12°C

8.19

6.59

Cdh Tj = +12 °C

0.900

0.900

Pdh Tj = Tbiv

9.30 kW

8.60 kW

COP Tj = Tbiv

2.59

1.89

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

7.20 kW

4.70 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.09

1.21

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

65 °C

65 °C

Poff

14 W

14 W

PTO

24 W

24 W

PSB

14 W

14 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

3.80 kW

5.30 kW

Annual energy consumption Qhe

6751 kWh

8474 kWh

Pdh Tj = -15°C (if TOL<-20°C)

9.30

8.60

COP Tj = -15°C (if TOL<-20°C)

2.59

1.89

Cdh Tj = -15 °C

0.900

0.900

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

44 dB(A)

44 dB(A)

Sound power level outdoor

64 dB(A)

64 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

188 %

136 %

Prated

12.00 kW

12.00 kW

SCOP

4.78

3.48

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

10.80 kW

10.80 kW

COP Tj = -7°C

2.92

2.12

Cdh Tj = -7 °C

0.900

0.900

Pdh Tj = +2°C

7.00 kW

6.60 kW

COP Tj = +2°C

4.53

3.29

Cdh Tj = +2 °C

0.900

0.900

Pdh Tj = +7°C

4.60 kW

4.40 kW

COP Tj = +7°C

6.66

4.74

Cdh Tj = +7 °C

0.900

0.900

Pdh Tj = 12°C

4.20 kW

4.00 kW

COP Tj = 12°C

8.92

7.28

Cdh Tj = +12 °C

0.900

0.900

Pdh Tj = Tbiv

10.80 kW

10.80 kW

COP Tj = Tbiv

2.92

2.12

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

11.40 kW

10.00 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.63

1.83

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

65 °C

65 °C

Poff

14 W

14 W

PTO

24 W

24 W

PSB

14 W

14 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.60 kW

2.00 kW

Annual energy consumption Qhe

5291 kWh

7221 kWh

Indoor unit: SMKLd-16D/3HBp-A, Outdoor unit: THF-12D/HBpO-A
Configure model
Model name
Indoor unit: SMKLd-16D/3HBp-A, Outdoor unit: THF-12D/HBpO-A
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

12.10 kW

12.00 kW

El input

2.42 kW

3.85 kW

COP

5.00

3.12

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

44 dB(A)

44 dB(A)

Sound power level outdoor

64 dB(A)

64 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

252 %

173 %

Prated

11.00 kW

12.00 kW

SCOP

6.39

4.41

Tbiv

7 °C

7 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

11.00 kW

12.00 kW

COP Tj = +2°C

3.61

2.27

Cdh Tj = +2 °C

0.900

0.900

Pdh Tj = +7°C

7.20 kW

8.00 kW

COP Tj = +7°C

5.65

3.75

Cdh Tj = +7 °C

0.900

0.900

Pdh Tj = 12°C

4.70 kW

4.30 kW

COP Tj = 12°C

8.33

5.95

Cdh Tj = +12 °C

0.900

0.900

Pdh Tj = Tbiv

7.20 kW

8.00 kW

COP Tj = Tbiv

5.65

3.75

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

11.00 kW

12.00 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

3.61

2.27

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

65 °C

65 °C

Poff

14 W

14 W

PTO

24 W

24 W

PSB

14 W

14 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

2330 kWh

3752 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

44 dB(A)

44 dB(A)

Sound power level outdoor

64 dB(A)

64 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

163 %

119 %

Prated

11.00 kW

10.00 kW

SCOP

4.15

3.05

Tbiv

-15 °C

-15 °C

TOL

-22 °C

-22 °C

Pdh Tj = -7°C

7.20 kW

6.70 kW

COP Tj = -7°C

3.51

2.58

Cdh Tj = -7 °C

0.900

0.900

Pdh Tj = +2°C

4.20 kW

4.00 kW

COP Tj = +2°C

5.05

3.68

Cdh Tj = +2 °C

0.900

0.900

Pdh Tj = +7°C

3.20 kW

2.90 kW

COP Tj = +7°C

6.17

4.57

Cdh Tj = +7 °C

0.900

0.900

Pdh Tj = 12°C

3.60 kW

3.30 kW

COP Tj = 12°C

8.19

6.59

Cdh Tj = +12 °C

0.900

0.900

Pdh Tj = Tbiv

9.30 kW

8.60 kW

COP Tj = Tbiv

2.59

1.89

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

7.20 kW

4.70 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.09

1.21

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

65 °C

65 °C

Poff

14 W

14 W

PTO

24 W

24 W

PSB

14 W

14 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

3.80 kW

5.30 kW

Annual energy consumption Qhe

6751 kWh

8474 kWh

Pdh Tj = -15°C (if TOL<-20°C)

9.30

8.60

COP Tj = -15°C (if TOL<-20°C)

2.59

1.89

Cdh Tj = -15 °C

0.900

0.900

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

44 dB(A)

44 dB(A)

Sound power level outdoor

64 dB(A)

64 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

188 %

136 %

Prated

12.00 kW

12.00 kW

SCOP

4.78

3.48

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

10.80 kW

10.80 kW

COP Tj = -7°C

2.92

2.12

Cdh Tj = -7 °C

0.900

0.900

Pdh Tj = +2°C

7.00 kW

6.60 kW

COP Tj = +2°C

4.53

3.29

Cdh Tj = +2 °C

0.900

0.900

Pdh Tj = +7°C

4.60 kW

4.40 kW

COP Tj = +7°C

6.66

4.74

Cdh Tj = +7 °C

0.900

0.900

Pdh Tj = 12°C

4.20 kW

4.00 kW

COP Tj = 12°C

8.92

7.28

Cdh Tj = +12 °C

0.900

0.900

Pdh Tj = Tbiv

10.80 kW

10.80 kW

COP Tj = Tbiv

2.92

2.12

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

11.40 kW

10.00 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.63

1.83

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

65 °C

65 °C

Poff

14 W

14 W

PTO

24 W

24 W

PSB

14 W

14 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.60 kW

2.00 kW

Annual energy consumption Qhe

5291 kWh

7221 kWh

Indoor unit: SMKL-16D/HBp-A, Outdoor unit: THF-14D/HBpO-A
Configure model
Model name
Indoor unit: SMKL-16D/HBp-A, Outdoor unit: THF-14D/HBpO-A
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

14.50 kW

14.00 kW

El input

3.05 kW

4.65 kW

COP

4.75

3.01

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

44 dB(A)

44 dB(A)

Sound power level outdoor

66 dB(A)

66 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

248 %

170 %

Prated

12.00 kW

14.00 kW

SCOP

6.28

4.33

Tbiv

7 °C

7 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

12.00 kW

13.10 kW

COP Tj = +2°C

3.40

2.24

Cdh Tj = +2 °C

0.900

0.900

Pdh Tj = +7°C

8.00 kW

9.00 kW

COP Tj = +7°C

5.61

3.61

Cdh Tj = +7 °C

0.900

0.900

Pdh Tj = 12°C

4.20 kW

4.10 kW

COP Tj = 12°C

7.94

5.93

Cdh Tj = +12 °C

0.900

0.900

Pdh Tj = Tbiv

8.00 kW

9.00 kW

COP Tj = Tbiv

5.61

3.61

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

12.00 kW

13.10 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

3.40

2.24

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

65 °C

65 °C

Poff

14 W

14 W

PTO

24 W

24 W

PSB

14 W

14 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.90 kW

Annual energy consumption Qhe

2638 kWh

4325 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

44 dB(A)

44 dB(A)

Sound power level outdoor

66 dB(A)

66 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

156 %

117 %

Prated

13.00 kW

11.00 kW

SCOP

3.99

3.01

Tbiv

-15 °C

-15 °C

TOL

-22 °C

-22 °C

Pdh Tj = -7°C

8.30 kW

7.20 kW

COP Tj = -7°C

3.35

2.56

Cdh Tj = -7 °C

0.900

0.900

Pdh Tj = +2°C

4.70 kW

4.30 kW

COP Tj = +2°C

4.72

3.62

Cdh Tj = +2 °C

0.900

0.900

Pdh Tj = +7°C

3.40 kW

3.10 kW

COP Tj = +7°C

6.11

4.77

Cdh Tj = +7 °C

0.900

0.900

Pdh Tj = 12°C

3.80 kW

3.60 kW

COP Tj = 12°C

8.00

6.40

Cdh Tj = +12 °C

0.900

0.900

Pdh Tj = Tbiv

10.70 kW

8.90 kW

COP Tj = Tbiv

2.61

1.83

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

7.90 kW

4.40 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.10

1.16

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

65 °C

65 °C

Poff

14 W

14 W

PTO

24 W

24 W

PSB

14 W

14 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

5.10 kW

6.60 kW

Annual energy consumption Qhe

8088 kWh

8975 kWh

Pdh Tj = -15°C (if TOL<-20°C)

10.70

8.90

COP Tj = -15°C (if TOL<-20°C)

2.61

1.83

Cdh Tj = -15 °C

0.900

0.900

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

44 dB(A)

44 dB(A)

Sound power level outdoor

66 dB(A)

66 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

182 %

135 %

Prated

14.00 kW

12.00 kW

SCOP

4.63

3.46

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

12.40 kW

11.00 kW

COP Tj = -7°C

2.80

2.10

Cdh Tj = -7 °C

0.900

0.900

Pdh Tj = +2°C

7.50 kW

7.00 kW

COP Tj = +2°C

4.39

3.27

Cdh Tj = +2 °C

0.900

0.900

Pdh Tj = +7°C

5.20 kW

4.50 kW

COP Tj = +7°C

6.54

4.79

Cdh Tj = +7 °C

0.900

0.900

Pdh Tj = 12°C

4.60 kW

4.10 kW

COP Tj = 12°C

8.59

7.25

Cdh Tj = +12 °C

0.900

0.900

Pdh Tj = Tbiv

12.40 kW

11.00 kW

COP Tj = Tbiv

2.80

2.10

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

12.90 kW

10.30 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.51

1.81

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

65 °C

65 °C

Poff

14 W

14 W

PTO

24 W

24 W

PSB

14 W

14 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

1.10 kW

1.70 kW

Annual energy consumption Qhe

6237 kWh

7410 kWh

Indoor unit: SMKLd-16D/3HBp-A, Outdoor unit: THF-14D/HBpO-A
Configure model
Model name
Indoor unit: SMKLd-16D/3HBp-A, Outdoor unit: THF-14D/HBpO-A
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

14.50 kW

14.00 kW

El input

3.05 kW

4.65 kW

COP

4.75

3.01

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

44 dB(A)

44 dB(A)

Sound power level outdoor

66 dB(A)

66 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

248 %

170 %

Prated

12.00 kW

14.00 kW

SCOP

6.28

4.33

Tbiv

7 °C

7 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

12.00 kW

13.10 kW

COP Tj = +2°C

3.40

2.24

Cdh Tj = +2 °C

0.900

0.900

Pdh Tj = +7°C

8.00 kW

9.00 kW

COP Tj = +7°C

5.61

3.61

Cdh Tj = +7 °C

0.900

0.900

Pdh Tj = 12°C

4.20 kW

4.10 kW

COP Tj = 12°C

7.94

5.93

Cdh Tj = +12 °C

0.900

0.900

Pdh Tj = Tbiv

8.00 kW

9.00 kW

COP Tj = Tbiv

5.61

3.61

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

12.00 kW

13.10 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

3.40

2.24

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

65 °C

65 °C

Poff

14 W

14 W

PTO

24 W

24 W

PSB

14 W

14 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.90 kW

Annual energy consumption Qhe

2638 kWh

4325 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

44 dB(A)

44 dB(A)

Sound power level outdoor

66 dB(A)

66 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

156 %

117 %

Prated

13.00 kW

11.00 kW

SCOP

3.99

3.01

Tbiv

-15 °C

-15 °C

TOL

-22 °C

-22 °C

Pdh Tj = -7°C

8.30 kW

7.20 kW

COP Tj = -7°C

3.35

2.56

Cdh Tj = -7 °C

0.900

0.900

Pdh Tj = +2°C

4.70 kW

4.30 kW

COP Tj = +2°C

4.72

3.62

Cdh Tj = +2 °C

0.900

0.900

Pdh Tj = +7°C

3.40 kW

3.10 kW

COP Tj = +7°C

6.11

4.77

Cdh Tj = +7 °C

0.900

0.900

Pdh Tj = 12°C

3.80 kW

3.60 kW

COP Tj = 12°C

8.00

6.40

Cdh Tj = +12 °C

0.900

0.900

Pdh Tj = Tbiv

10.70 kW

8.90 kW

COP Tj = Tbiv

2.61

1.83

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

7.90 kW

4.40 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.10

1.16

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

65 °C

65 °C

Poff

14 W

14 W

PTO

24 W

24 W

PSB

14 W

14 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

5.10 kW

6.60 kW

Annual energy consumption Qhe

8088 kWh

8975 kWh

Pdh Tj = -15°C (if TOL<-20°C)

10.70

8.90

COP Tj = -15°C (if TOL<-20°C)

2.61

1.83

Cdh Tj = -15 °C

0.900

0.900

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

44 dB(A)

44 dB(A)

Sound power level outdoor

66 dB(A)

66 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

182 %

135 %

Prated

14.00 kW

12.00 kW

SCOP

4.63

3.46

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

12.40 kW

11.00 kW

COP Tj = -7°C

2.80

2.10

Cdh Tj = -7 °C

0.900

0.900

Pdh Tj = +2°C

7.50 kW

7.00 kW

COP Tj = +2°C

4.39

3.27

Cdh Tj = +2 °C

0.900

0.900

Pdh Tj = +7°C

5.20 kW

4.50 kW

COP Tj = +7°C

6.54

4.79

Cdh Tj = +7 °C

0.900

0.900

Pdh Tj = 12°C

4.60 kW

4.10 kW

COP Tj = 12°C

8.59

7.25

Cdh Tj = +12 °C

0.900

0.900

Pdh Tj = Tbiv

12.40 kW

11.00 kW

COP Tj = Tbiv

2.80

2.10

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

12.90 kW

10.30 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.51

1.81

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

65 °C

65 °C

Poff

14 W

14 W

PTO

24 W

24 W

PSB

14 W

14 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

1.10 kW

1.70 kW

Annual energy consumption Qhe

6237 kWh

7410 kWh

Indoor unit: SMKLd-16D/3HBp-A, Outdoor unit: THF-16D/HBpO-A
Configure model
Model name
Indoor unit: SMKLd-16D/3HBp-A, Outdoor unit: THF-16D/HBpO-A
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

16.00 kW

16.00 kW

El input

3.54 kW

5.49 kW

COP

4.52

2.91

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

44 dB(A)

44 dB(A)

Sound power level outdoor

68 dB(A)

68 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

239 %

170 %

Prated

13.00 kW

14.00 kW

SCOP

6.06

4.34

Tbiv

7 °C

7 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

13.00 kW

13.30 kW

COP Tj = +2°C

3.33

2.31

Cdh Tj = +2 °C

0.900

0.900

Pdh Tj = +7°C

8.60 kW

9.00 kW

COP Tj = +7°C

5.20

3.68

Cdh Tj = +7 °C

0.900

0.900

Pdh Tj = 12°C

4.80 kW

4.10 kW

COP Tj = 12°C

7.95

5.80

Cdh Tj = +12 °C

0.900

0.900

Pdh Tj = Tbiv

8.60 kW

9.00 kW

COP Tj = Tbiv

5.20

3.68

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

13.30 kW

13.30 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

3.33

2.31

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

65 °C

65 °C

Poff

14 W

14 W

PTO

24 W

24 W

PSB

14 W

14 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.70 kW

Annual energy consumption Qhe

2934 kWh

4327 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

44 dB(A)

44 dB(A)

Sound power level outdoor

68 dB(A)

68 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

155 %

120 %

Prated

14.00 kW

12.00 kW

SCOP

3.96

3.09

Tbiv

-15 °C

-15 °C

TOL

-22 °C

-22 °C

Pdh Tj = -7°C

9.10 kW

7.70 kW

COP Tj = -7°C

3.29

2.61

Cdh Tj = -7 °C

0.900

0.900

Pdh Tj = +2°C

5.00 kW

4.50 kW

COP Tj = +2°C

4.86

3.79

Cdh Tj = +2 °C

0.900

0.900

Pdh Tj = +7°C

4.20 kW

3.20 kW

COP Tj = +7°C

6.51

4.87

Cdh Tj = +7 °C

0.900

0.900

Pdh Tj = 12°C

3.70 kW

3.70 kW

COP Tj = 12°C

7.59

6.39

Cdh Tj = +12 °C

0.900

0.900

Pdh Tj = Tbiv

11.30 kW

9.60 kW

COP Tj = Tbiv

2.28

1.84

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

9.80 kW

5.10 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

1.89

1.04

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

65 °C

65 °C

Poff

14 W

14 W

PTO

24 W

24 W

PSB

14 W

14 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

4.20 kW

6.90 kW

Annual energy consumption Qhe

8631 kWh

9390 kWh

Pdh Tj = -15°C (if TOL<-20°C)

11.30

9.60

COP Tj = -15°C (if TOL<-20°C)

2.28

1.84

Cdh Tj = -15 °C

0.900

0.900

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

44 dB(A)

44 dB(A)

Sound power level outdoor

68 dB(A)

68 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

179 %

136 %

Prated

15.00 kW

13.00 kW

SCOP

4.56

3.48

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

13.40 kW

11.60 kW

COP Tj = -7°C

2.67

2.05

Cdh Tj = -7 °C

0.900

0.900

Pdh Tj = +2°C

8.00 kW

7.30 kW

COP Tj = +2°C

4.33

3.31

Cdh Tj = +2 °C

0.900

0.900

Pdh Tj = +7°C

5.40 kW

4.80 kW

COP Tj = +7°C

6.48

4.82

Cdh Tj = +7 °C

0.900

0.900

Pdh Tj = 12°C

4.60 kW

4.00 kW

COP Tj = 12°C

8.96

7.35

Cdh Tj = +12 °C

0.900

0.900

Pdh Tj = Tbiv

13.40 kW

11.60 kW

COP Tj = Tbiv

2.67

2.05

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

13.40 kW

11.20 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.46

1.72

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

65 °C

65 °C

Poff

14 W

14 W

PTO

24 W

24 W

PSB

14 W

14 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

1.60 kW

1.80 kW

Annual energy consumption Qhe

6874 kWh

7752 kWh

Indoor unit: SMKL-16D/HBp-A, Outdoor unit: THF-16D/HBpO-A
Configure model
Model name
Indoor unit: SMKL-16D/HBp-A, Outdoor unit: THF-16D/HBpO-A
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

16.00 kW

16.00 kW

El input

3.54 kW

5.49 kW

COP

4.52

2.91

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

44 dB(A)

44 dB(A)

Sound power level outdoor

68 dB(A)

68 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

239 %

170 %

Prated

13.00 kW

14.00 kW

SCOP

6.06

4.34

Tbiv

7 °C

7 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

13.00 kW

13.30 kW

COP Tj = +2°C

3.33

2.31

Cdh Tj = +2 °C

0.900

0.900

Pdh Tj = +7°C

8.60 kW

9.00 kW

COP Tj = +7°C

5.20

3.68

Cdh Tj = +7 °C

0.900

0.900

Pdh Tj = 12°C

4.80 kW

4.10 kW

COP Tj = 12°C

7.95

5.80

Cdh Tj = +12 °C

0.900

0.900

Pdh Tj = Tbiv

8.60 kW

9.00 kW

COP Tj = Tbiv

5.20

3.68

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

13.30 kW

13.30 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

3.33

2.31

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

65 °C

65 °C

Poff

14 W

14 W

PTO

24 W

24 W

PSB

14 W

14 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.70 kW

Annual energy consumption Qhe

2934 kWh

4327 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

44 dB(A)

44 dB(A)

Sound power level outdoor

68 dB(A)

68 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

155 %

120 %

Prated

14.00 kW

12.00 kW

SCOP

3.96

3.09

Tbiv

-15 °C

-15 °C

TOL

-22 °C

-22 °C

Pdh Tj = -7°C

9.10 kW

7.70 kW

COP Tj = -7°C

3.29

2.61

Cdh Tj = -7 °C

0.900

0.900

Pdh Tj = +2°C

5.00 kW

4.50 kW

COP Tj = +2°C

4.86

3.79

Cdh Tj = +2 °C

0.900

0.900

Pdh Tj = +7°C

4.20 kW

3.20 kW

COP Tj = +7°C

6.51

4.87

Cdh Tj = +7 °C

0.900

0.900

Pdh Tj = 12°C

3.70 kW

3.70 kW

COP Tj = 12°C

7.59

6.39

Cdh Tj = +12 °C

0.900

0.900

Pdh Tj = Tbiv

11.30 kW

9.60 kW

COP Tj = Tbiv

2.28

1.84

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

9.80 kW

5.10 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

1.89

1.04

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

65 °C

65 °C

Poff

14 W

14 W

PTO

24 W

24 W

PSB

14 W

14 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

4.20 kW

6.90 kW

Annual energy consumption Qhe

8631 kWh

9390 kWh

Pdh Tj = -15°C (if TOL<-20°C)

11.30

9.60

COP Tj = -15°C (if TOL<-20°C)

2.28

1.84

Cdh Tj = -15 °C

0.900

0.900

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

44 dB(A)

44 dB(A)

Sound power level outdoor

68 dB(A)

68 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

179 %

136 %

Prated

15.00 kW

13.00 kW

SCOP

4.56

3.48

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

13.40 kW

11.60 kW

COP Tj = -7°C

2.67

2.05

Cdh Tj = -7 °C

0.900

0.900

Pdh Tj = +2°C

8.00 kW

7.30 kW

COP Tj = +2°C

4.33

3.31

Cdh Tj = +2 °C

0.900

0.900

Pdh Tj = +7°C

5.40 kW

4.80 kW

COP Tj = +7°C

6.48

4.82

Cdh Tj = +7 °C

0.900

0.900

Pdh Tj = 12°C

4.60 kW

4.00 kW

COP Tj = 12°C

8.96

7.35

Cdh Tj = +12 °C

0.900

0.900

Pdh Tj = Tbiv

13.40 kW

11.60 kW

COP Tj = Tbiv

2.67

2.05

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

13.40 kW

11.20 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.46

1.72

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

65 °C

65 °C

Poff

14 W

14 W

PTO

24 W

24 W

PSB

14 W

14 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

1.60 kW

1.80 kW

Annual energy consumption Qhe

6874 kWh

7752 kWh