Certificate holders

Subtype

Hi-Therma Monobloc 10 12

Certificate Holder
Qingdao Hisense Hitachi Air-conditioning Systems Co.,Ltd.
Qianwangang Road
266555 Qingdao, Shandong
China
Registration number
011-1W0661
Certification Body
DIN CERTCO Gesellschaft für Konformitätsbewertung mbH
Subtype title
Hi-Therma Monobloc 10 12
Driving energy
Electricity
Heat Pump Type
Outdoor Air/Water
Refrigerant
R32
Mass of Refrigerant

1,500 kg

Certification Date
10.08.2023
Testing basis
HP KEYMARK certification scheme rules V12
Generate PDF Export model CSV
  • Number of models 4

Models

AHZ-100HCDS1
Configure model
Model name
AHZ-100HCDS1
Application
Heating (medium temp)
Units
Outdoor
Climate Zone
Warmer Climate
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

10.00 kW

9.00 kW

El input

1.96 kW

2.90 kW

COP

5.10

3.10

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

62 dB(A)

62 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

265 %

170 %

Prated

9.70 kW

9.50 kW

SCOP

6.70

4.34

Tbiv

7 °C

7 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

9.38 kW

9.50 kW

COP Tj = +2°C

3.78

2.53

Cdh Tj = +2 °C

0.900

0.900

Pdh Tj = +7°C

6.21 kW

6.08 kW

COP Tj = +7°C

5.67

3.60

Cdh Tj = +7 °C

0.900

0.900

Pdh Tj = 12°C

2.95 kW

2.74 kW

COP Tj = 12°C

8.85

5.56

Cdh Tj = +12 °C

0.900

0.900

Pdh Tj = Tbiv

6.21 kW

6.08 kW

COP Tj = Tbiv

5.67

3.60

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

9.38 kW

9.50 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

3.78

2.53

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

65 °C

65 °C

Poff

10 W

10 W

PTO

13 W

13 W

PSB

10 W

10 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.32 kW

0.00 kW

Annual energy consumption Qhe

1926 kWh

2915 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

62 dB(A)

62 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

193 %

142 %

Prated

9.20 kW

9.20 kW

SCOP

4.90

3.62

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

8.16 kW

8.18 kW

COP Tj = -7°C

3.14

2.35

Cdh Tj = -7 °C

0.900

0.900

Pdh Tj = +2°C

5.19 kW

5.15 kW

COP Tj = +2°C

4.65

3.49

Cdh Tj = +2 °C

0.900

0.900

Pdh Tj = +7°C

3.28 kW

3.36 kW

COP Tj = +7°C

6.59

4.66

Cdh Tj = +7 °C

0.900

0.900

Pdh Tj = 12°C

2.75 kW

2.64 kW

COP Tj = 12°C

8.48

6.30

Cdh Tj = +12 °C

0.900

0.900

Pdh Tj = Tbiv

8.16 kW

8.18 kW

COP Tj = Tbiv

3.14

2.35

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

9.15 kW

9.05 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.64

1.96

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

60 °C

60 °C

Poff

10 W

10 W

PTO

13 W

13 W

PSB

10 W

10 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.05 kW

0.15 kW

Annual energy consumption Qhe

3890 kWh

5273 kWh

AHZ-100HEDS1
Configure model
Model name
AHZ-100HEDS1
Application
Heating (medium temp)
Units
Outdoor
Climate Zone
Warmer Climate
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

10.00 kW

9.00 kW

El input

1.96 kW

2.90 kW

COP

5.10

3.10

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

62 dB(A)

62 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

265 %

170 %

Prated

9.70 kW

9.50 kW

SCOP

6.70

4.34

Tbiv

7 °C

7 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

9.38 kW

9.50 kW

COP Tj = +2°C

3.78

2.53

Cdh Tj = +2 °C

0.900

0.900

Pdh Tj = +7°C

6.21 kW

6.08 kW

COP Tj = +7°C

5.67

3.60

Cdh Tj = +7 °C

0.900

0.900

Pdh Tj = 12°C

2.95 kW

2.74 kW

COP Tj = 12°C

8.85

5.56

Cdh Tj = +12 °C

0.900

0.900

Pdh Tj = Tbiv

6.21 kW

6.08 kW

COP Tj = Tbiv

5.67

3.60

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

9.38 kW

9.50 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

3.78

2.53

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

65 °C

65 °C

Poff

10 W

10 W

PTO

13 W

13 W

PSB

10 W

10 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.32 kW

0.00 kW

Annual energy consumption Qhe

1926 kWh

2915 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

62 dB(A)

62 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

193 %

142 %

Prated

9.20 kW

9.20 kW

SCOP

4.90

3.62

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

8.16 kW

8.18 kW

COP Tj = -7°C

3.14

2.35

Cdh Tj = -7 °C

0.900

0.900

Pdh Tj = +2°C

5.19 kW

5.15 kW

COP Tj = +2°C

4.65

3.49

Cdh Tj = +2 °C

0.900

0.900

Pdh Tj = +7°C

3.28 kW

3.36 kW

COP Tj = +7°C

6.59

4.66

Cdh Tj = +7 °C

0.900

0.900

Pdh Tj = 12°C

2.75 kW

2.64 kW

COP Tj = 12°C

8.48

6.30

Cdh Tj = +12 °C

0.900

0.900

Pdh Tj = Tbiv

8.16 kW

8.18 kW

COP Tj = Tbiv

3.14

2.35

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

9.15 kW

9.05 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.64

1.96

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

60 °C

60 °C

Poff

10 W

10 W

PTO

13 W

13 W

PSB

10 W

10 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.05 kW

0.15 kW

Annual energy consumption Qhe

3890 kWh

5273 kWh

AHZ-120HCDS1
Configure model
Model name
AHZ-120HCDS1
Application
Heating (medium temp)
Units
Outdoor
Climate Zone
Warmer Climate
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

12.00 kW

11.20 kW

El input

2.42 kW

3.67 kW

COP

4.95

3.05

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

64 dB(A)

64 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

259 %

170 %

Prated

10.50 kW

10.50 kW

SCOP

6.56

4.33

Tbiv

7 °C

7 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

10.22 kW

10.10 kW

COP Tj = +2°C

3.74

2.47

Cdh Tj = +2 °C

0.900

0.900

Pdh Tj = +7°C

6.77 kW

6.75 kW

COP Tj = +7°C

5.90

3.62

Cdh Tj = +7 °C

0.900

0.900

Pdh Tj = 12°C

2.94 kW

2.95 kW

COP Tj = 12°C

8.13

5.69

Cdh Tj = +12 °C

0.900

0.900

Pdh Tj = Tbiv

6.77 kW

6.75 kW

COP Tj = Tbiv

5.90

3.62

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

10.22 kW

10.10 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

3.74

2.47

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

65 °C

65 °C

Poff

10 W

10 W

PTO

13 W

13 W

PSB

10 W

10 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.28 kW

0.40 kW

Annual energy consumption Qhe

2145 kWh

3243 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

64 dB(A)

64 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

192 %

136 %

Prated

10.20 kW

10.00 kW

SCOP

4.87

3.47

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

8.98 kW

8.87 kW

COP Tj = -7°C

3.15

2.32

Cdh Tj = -7 °C

0.900

0.900

Pdh Tj = +2°C

5.61 kW

5.34 kW

COP Tj = +2°C

4.64

3.22

Cdh Tj = +2 °C

0.900

0.900

Pdh Tj = +7°C

3.57 kW

3.47 kW

COP Tj = +7°C

6.48

4.65

Cdh Tj = +7 °C

0.900

0.900

Pdh Tj = 12°C

2.77 kW

2.66 kW

COP Tj = 12°C

8.11

6.34

Cdh Tj = +12 °C

0.900

0.900

Pdh Tj = Tbiv

8.98 kW

8.87 kW

COP Tj = Tbiv

3.15

2.32

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

9.92 kW

10.15 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.71

1.89

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

60 °C

60 °C

Poff

10 W

10 W

PTO

13 W

13 W

PSB

10 W

10 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.28 kW

0.00 kW

Annual energy consumption Qhe

4309 kWh

5964 kWh

AHZ-120HEDS1
Configure model
Model name
AHZ-120HEDS1
Application
Heating (medium temp)
Units
Outdoor
Climate Zone
Warmer Climate
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

12.00 kW

11.20 kW

El input

2.42 kW

3.67 kW

COP

4.95

3.05

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

64 dB(A)

64 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

259 %

170 %

Prated

10.50 kW

10.50 kW

SCOP

6.56

4.33

Tbiv

7 °C

7 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

10.22 kW

10.10 kW

COP Tj = +2°C

3.74

2.47

Cdh Tj = +2 °C

0.900

0.900

Pdh Tj = +7°C

6.77 kW

6.75 kW

COP Tj = +7°C

5.90

3.62

Cdh Tj = +7 °C

0.900

0.900

Pdh Tj = 12°C

2.94 kW

2.95 kW

COP Tj = 12°C

8.13

5.69

Cdh Tj = +12 °C

0.900

0.900

Pdh Tj = Tbiv

6.77 kW

6.75 kW

COP Tj = Tbiv

5.90

3.62

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

10.22 kW

10.10 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

3.74

2.47

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

65 °C

65 °C

Poff

10 W

10 W

PTO

13 W

13 W

PSB

10 W

10 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.28 kW

0.40 kW

Annual energy consumption Qhe

2145 kWh

3243 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

64 dB(A)

64 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

192 %

136 %

Prated

10.20 kW

10.00 kW

SCOP

4.87

3.47

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

8.98 kW

8.87 kW

COP Tj = -7°C

3.15

2.32

Cdh Tj = -7 °C

0.900

0.900

Pdh Tj = +2°C

5.61 kW

5.34 kW

COP Tj = +2°C

4.64

3.22

Cdh Tj = +2 °C

0.900

0.900

Pdh Tj = +7°C

3.57 kW

3.47 kW

COP Tj = +7°C

6.48

4.65

Cdh Tj = +7 °C

0.900

0.900

Pdh Tj = 12°C

2.77 kW

2.66 kW

COP Tj = 12°C

8.11

6.34

Cdh Tj = +12 °C

0.900

0.900

Pdh Tj = Tbiv

8.98 kW

8.87 kW

COP Tj = Tbiv

3.15

2.32

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

9.92 kW

10.15 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.71

1.89

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

60 °C

60 °C

Poff

10 W

10 W

PTO

13 W

13 W

PSB

10 W

10 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.28 kW

0.00 kW

Annual energy consumption Qhe

4309 kWh

5964 kWh