2,100 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
24.80 kW
23.20 kW
El input
5.37 kW
7.66 kW
COP
4.62
3.03
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Cooling
EN 14511-2
+7°C/+12°C
El input
6.19 kW
Cooling capacity
19.80
EER
3.20
EN 14825
+7°C/+12°C
Pdesignc
19.80 kW
SEER
4.92
Pdc Tj = 35°C
19.80 kW
EER Tj = 35°C
3.20
Cdc Tj = 35 °C
1.000
Pdc Tj = 30°C
14.60 kW
EER Tj = 30°C
4.35
Cdc Tj = 30 °C
1.000
Pdc Tj = 25°C
9.70 kW
EER Tj = 25°C
5.48
Cdc Tj = 25 °C
1.000
Pdc Tj = 20°C
9.76 kW
EER Tj = 20°C
6.06
Cdc Tj = 20 °C
0.986
Poff
22 W
PTO
0 W
PSB
28 W
PCK
0 W
Annual energy consumption Qce
2406 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
65 dB(A)
65 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
177 %
143 %
Prated
22.00 kW
22.00 kW
SCOP
4.49
3.66
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
19.60 kW
19.90 kW
COP Tj = -7°C
2.71
2.01
Cdh Tj = -7 °C
1.000
1.000
Pdh Tj = +2°C
11.90 kW
12.10 kW
COP Tj = +2°C
4.22
3.64
Cdh Tj = +2 °C
1.000
1.000
Pdh Tj = +7°C
10.50 kW
10.20 kW
COP Tj = +7°C
6.44
4.96
Cdh Tj = +7 °C
1.000
1.000
Pdh Tj = 12°C
12.30 kW
11.90 kW
COP Tj = 12°C
8.03
6.49
Cdh Tj = +12 °C
1.000
1.000
Pdh Tj = Tbiv
19.60 kW
19.90 kW
COP Tj = Tbiv
2.71
2.01
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
17.70 kW
17.70 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.43
1.78
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
69 °C
69 °C
Poff
22 W
22 W
PTO
22 W
22 W
PSB
22 W
22 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
4.30 kW
4.30 kW
Annual energy consumption Qhe
10195 kWh
12702 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
27.00 kW
26.30 kW
El input
6.21 kW
8.74 kW
COP
4.35
3.01
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Cooling
EN 14511-2
+7°C/+12°C
El input
7.19 kW
Cooling capacity
22.30
EER
3.10
EN 14825
+7°C/+12°C
Pdesignc
22.30 kW
SEER
4.84
Pdc Tj = 35°C
22.30 kW
EER Tj = 35°C
3.10
Cdc Tj = 35 °C
1.000
Pdc Tj = 30°C
16.40 kW
EER Tj = 30°C
4.17
Cdc Tj = 30 °C
1.000
Pdc Tj = 25°C
10.60 kW
EER Tj = 25°C
5.33
Cdc Tj = 25 °C
1.000
Pdc Tj = 20°C
9.94 kW
EER Tj = 20°C
6.14
Cdc Tj = 20 °C
0.986
Poff
22 W
PTO
0 W
PSB
28 W
PCK
0 W
Annual energy consumption Qce
2764 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
65 dB(A)
65 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
175 %
140 %
Prated
24.00 kW
23.00 kW
SCOP
4.46
3.56
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
21.00 kW
20.70 kW
COP Tj = -7°C
2.77
1.97
Cdh Tj = -7 °C
1.000
1.000
Pdh Tj = +2°C
12.80 kW
12.60 kW
COP Tj = +2°C
4.17
3.50
Cdh Tj = +2 °C
1.000
1.000
Pdh Tj = +7°C
10.40 kW
10.10 kW
COP Tj = +7°C
6.31
4.92
Cdh Tj = +7 °C
1.000
1.000
Pdh Tj = 12°C
12.30 kW
11.90 kW
COP Tj = 12°C
7.95
6.53
Cdh Tj = +12 °C
1.000
1.000
Pdh Tj = Tbiv
21.00 kW
20.70 kW
COP Tj = Tbiv
2.77
1.97
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
18.80 kW
18.50 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.46
1.70
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
69 °C
69 °C
Poff
22 W
22 W
PTO
22 W
22 W
PSB
22 W
22 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
5.20 kW
4.50 kW
Annual energy consumption Qhe
10997 kWh
136567 kWh