1,400 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
9.95 kW
9.67 kW
El input
2.11 kW
3.22 kW
COP
4.71
3.00
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
62 dB(A)
64 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
185 %
129 %
Prated
9.05 kW
7.50 kW
SCOP
4.70
3.30
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
8.01 kW
6.63 kW
COP Tj = -7°C
3.16
2.10
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
5.16 kW
4.26 kW
COP Tj = +2°C
4.54
3.21
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
3.24 kW
3.14 kW
COP Tj = +7°C
5.94
4.37
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
3.82 kW
3.90 kW
COP Tj = 12°C
9.30
6.75
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
8.01 kW
6.63 kW
COP Tj = Tbiv
3.16
2.10
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.71 kW
6.49 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.85
1.74
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
50 °C
50 °C
Poff
7 W
7 W
PTO
38 W
38 W
PSB
7 W
7 W
PCK
40 W
40 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.34 kW
1.01 kW
Annual energy consumption Qhe
3975 kWh
4694 kWh