2,670 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
19.36 kW
18.53 kW
El input
4.27 kW
6.01 kW
COP
4.54
3.08
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
69 dB(A)
71 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
180 %
133 %
Prated
13.96 kW
13.43 kW
SCOP
4.56
3.40
Tbiv
-7 °C
-7 °C
TOL
-25 °C
-25 °C
Pdh Tj = -7°C
12.35 kW
11.88 kW
COP Tj = -7°C
3.13
2.30
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
7.59 kW
7.34 kW
COP Tj = +2°C
4.45
3.26
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
7.42 kW
7.03 kW
COP Tj = +7°C
5.98
4.59
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
8.77 kW
8.39 kW
COP Tj = 12°C
8.45
6.56
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
12.35 kW
11.88 kW
COP Tj = Tbiv
3.13
2.30
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
13.57 kW
13.42 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.79
2.03
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
55 °C
55 °C
Poff
12 W
12 W
PTO
19 W
19 W
PSB
12 W
12 W
PCK
42 W
42 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.38 kW
0.01 kW
Annual energy consumption Qhe
6319 kWh
8162 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
21.18 kW
21.35 kW
El input
4.82 kW
7.11 kW
COP
4.40
3.00
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
71 dB(A)
71 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
178 %
132 %
Prated
12.40 kW
13.42 kW
SCOP
4.53
3.37
Tbiv
-7 °C
-7 °C
TOL
-25 °C
-25 °C
Pdh Tj = -7°C
10.97 kW
11.87 kW
COP Tj = -7°C
2.82
2.29
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
6.80 kW
7.24 kW
COP Tj = +2°C
4.55
3.22
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
7.40 kW
6.99 kW
COP Tj = +7°C
6.13
4.54
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
8.79 kW
8.42 kW
COP Tj = 12°C
8.53
6.63
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
10.97 kW
11.87 kW
COP Tj = Tbiv
2.82
2.29
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
12.25 kW
13.37 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.78
2.01
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
55 °C
55 °C
Poff
12 W
12 W
PTO
20 W
20 W
PSB
12 W
12 W
PCK
42 W
42 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.15 kW
0.05 kW
Annual energy consumption Qhe
5652 kWh
8219 kWh