3,200 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
21.32 kW
18.30 kW
El input
4.94 kW
6.37 kW
COP
4.32
2.87
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
73 dB(A)
71 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
177 %
131 %
Prated
16.55 kW
16.19 kW
SCOP
4.50
3.36
Tbiv
-7 °C
-7 °C
TOL
-25 °C
-25 °C
Pdh Tj = -7°C
14.64 kW
14.33 kW
COP Tj = -7°C
2.90
2.11
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
9.07 kW
8.78 kW
COP Tj = +2°C
4.42
3.31
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
9.45 kW
8.92 kW
COP Tj = +7°C
6.22
4.53
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
9.60 kW
10.73 kW
COP Tj = 12°C
7.77
6.71
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
14.64 kW
14.32 kW
COP Tj = Tbiv
2.90
2.11
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
16.54 kW
15.97 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.67
1.89
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
55 °C
55 °C
Poff
12 W
12 W
PTO
27 W
27 W
PSB
12 W
12 W
PCK
42 W
42 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.01 kW
0.22 kW
Annual energy consumption Qhe
7600 kWh
9967 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
25.09 kW
26.31 kW
El input
6.03 kW
9.81 kW
COP
4.16
2.68
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
72 dB(A)
71 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
177 %
131 %
Prated
16.64 kW
16.18 kW
SCOP
4.51
3.35
Tbiv
-7 °C
-7 °C
TOL
-25 °C
-25 °C
Pdh Tj = -7°C
14.72 kW
14.31 kW
COP Tj = -7°C
2.91
2.09
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
9.00 kW
8.78 kW
COP Tj = +2°C
4.46
3.31
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
9.20 kW
8.58 kW
COP Tj = +7°C
5.97
4.53
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
10.88 kW
10.38 kW
COP Tj = 12°C
8.78
6.61
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
14.72 kW
14.31 kW
COP Tj = Tbiv
2.91
2.09
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
16.52 kW
16.08 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.65
1.89
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
55 °C
55 °C
Poff
11 W
11 W
PTO
23 W
23 W
PSB
11 W
11 W
PCK
44 W
44 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.12 kW
0.10 kW
Annual energy consumption Qhe
7623 kWh
9969 kWh