0,600 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
4 kW
4 kW
El input
0.78 kW
1.27 kW
COP
5.1
3.15
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Cooling
EN 14511-2
+7°C/+12°C
+18°C/+23°C
El input
1.03 kW
1.31 kW
Cooling capacity
3.2
4.2
EER
3.1
3.2
EN 14825
+7°C/+12°C
+18°C/+23°C
Pdesignc
3.2 kW
4.2 kW
SEER
3.99
4.89
Pdc Tj = 35°C
3.2 kW
4.2 kW
EER Tj = 35°C
3.1
3.2
Cdc Tj = 35 °C
0.985
0.989
Pdc Tj = 30°C
2.35 kW
3.07 kW
EER Tj = 30°C
3.69
4.3
Cdc Tj = 30 °C
0.976
0.979
Pdc Tj = 25°C
1.51 kW
1.97 kW
EER Tj = 25°C
4.48
5.59
Cdc Tj = 25 °C
0.955
0.957
Pdc Tj = 20°C
1.31 kW
1.8 kW
EER Tj = 20°C
5.39
7.24
Cdc Tj = 20 °C
0.938
0.94
Poff
15 W
15 W
PTO
15 W
15 W
PSB
15 W
15 W
PCK
0 W
0 W
Annual energy consumption Qce
481 kWh
515 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
56 dB(A)
56 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
177 %
135 %
Prated
5 kW
5 kW
SCOP
4.51
3.46
Tbiv
-7 °C
-7 °C
TOL
-25 °C
-25 °C
Pdh Tj = -7°C
4.42 kW
4.42 kW
COP Tj = -7°C
3.02
2.39
Cdh Tj = -7 °C
0.99
0.992
Pdh Tj = +2°C
2.69 kW
2.69 kW
COP Tj = +2°C
4.42
3.22
Cdh Tj = +2 °C
0.975
0.982
Pdh Tj = +7°C
1.73 kW
1.73 kW
COP Tj = +7°C
6.08
4.8
Cdh Tj = +7 °C
0.947
0.958
Pdh Tj = 12°C
1.68 kW
1.8 kW
COP Tj = 12°C
7.5
6.54
Cdh Tj = +12 °C
0.933
0.946
Pdh Tj = Tbiv
4.42 kW
4.42 kW
COP Tj = Tbiv
3.02
2.39
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
4.9 kW
4.9 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.76
2.07
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.992
0.994
WTOL
75 °C
75 °C
Poff
15 W
15 W
PTO
15 W
15 W
PSB
15 W
15 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.1 kW
0.1 kW
Annual energy consumption Qhe
2291 kWh
2984 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
134 %
COP
3.19
Heating up time
2:59 h:min
Standby power input
41 W
Reference hot water temperature
52.5 °C
Mixed water at 40°C
278 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
4 kW
4 kW
El input
0.78 kW
1.27 kW
COP
5.1
3.15
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Cooling
EN 14511-2
+7°C/+12°C
+18°C/+23°C
El input
1.03 kW
1.31 kW
Cooling capacity
3.2
4.2
EER
3.1
3.2
EN 14825
+7°C/+12°C
+18°C/+23°C
Pdesignc
3.2 kW
4.2 kW
SEER
3.99
4.89
Pdc Tj = 35°C
3.2 kW
4.2 kW
EER Tj = 35°C
3.1
3.2
Cdc Tj = 35 °C
0.985
0.989
Pdc Tj = 30°C
2.35 kW
3.07 kW
EER Tj = 30°C
3.69
4.3
Cdc Tj = 30 °C
0.976
0.979
Pdc Tj = 25°C
1.51 kW
1.97 kW
EER Tj = 25°C
4.48
5.59
Cdc Tj = 25 °C
0.955
0.957
Pdc Tj = 20°C
1.31 kW
1.8 kW
EER Tj = 20°C
5.39
7.24
Cdc Tj = 20 °C
0.938
0.94
Poff
15 W
15 W
PTO
15 W
15 W
PSB
15 W
15 W
PCK
0 W
0 W
Annual energy consumption Qce
481 kWh
515 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
56 dB(A)
56 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
182 %
138 %
Prated
5 kW
5 kW
SCOP
4.62
3.53
Tbiv
-7 °C
-7 °C
TOL
-25 °C
-25 °C
Pdh Tj = -7°C
4.42 kW
4.42 kW
COP Tj = -7°C
3.02
2.39
Cdh Tj = -7 °C
0.99
0.992
Pdh Tj = +2°C
2.69 kW
2.69 kW
COP Tj = +2°C
4.42
3.22
Cdh Tj = +2 °C
0.975
0.982
Pdh Tj = +7°C
1.73 kW
1.73 kW
COP Tj = +7°C
6.08
4.8
Cdh Tj = +7 °C
0.947
0.958
Pdh Tj = 12°C
1.68 kW
1.8 kW
COP Tj = 12°C
7.5
6.54
Cdh Tj = +12 °C
0.933
0.946
Pdh Tj = Tbiv
4.42 kW
4.42 kW
COP Tj = Tbiv
3.02
2.39
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
4.9 kW
4.9 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.76
2.07
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.992
0.994
WTOL
75 °C
75 °C
Poff
15 W
15 W
PTO
15 W
15 W
PSB
15 W
15 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.1 kW
0.1 kW
Annual energy consumption Qhe
2236 kWh
2929 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
134 %
COP
3.19
Heating up time
2:59 h:min
Standby power input
41 W
Reference hot water temperature
52.5 °C
Mixed water at 40°C
278 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
4 kW
4 kW
El input
0.78 kW
1.27 kW
COP
5.1
3.15
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Cooling
EN 14511-2
+7°C/+12°C
+18°C/+23°C
El input
1.03 kW
1.31 kW
Cooling capacity
3.2
4.2
EER
3.1
3.2
EN 14825
+7°C/+12°C
+18°C/+23°C
Pdesignc
3.2 kW
4.2 kW
SEER
3.99
4.89
Pdc Tj = 35°C
3.2 kW
4.2 kW
EER Tj = 35°C
3.1
3.2
Cdc Tj = 35 °C
0.985
0.989
Pdc Tj = 30°C
2.35 kW
3.07 kW
EER Tj = 30°C
3.69
4.3
Cdc Tj = 30 °C
0.976
0.979
Pdc Tj = 25°C
1.51 kW
1.97 kW
EER Tj = 25°C
4.48
5.59
Cdc Tj = 25 °C
0.955
0.957
Pdc Tj = 20°C
1.31 kW
1.8 kW
EER Tj = 20°C
5.39
7.24
Cdc Tj = 20 °C
0.938
0.94
Poff
15 W
15 W
PTO
15 W
15 W
PSB
15 W
15 W
PCK
0 W
0 W
Annual energy consumption Qce
481 kWh
515 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
56 dB(A)
56 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
182 %
138 %
Prated
5 kW
5 kW
SCOP
4.62
3.53
Tbiv
-7 °C
-7 °C
TOL
-25 °C
-25 °C
Pdh Tj = -7°C
4.42 kW
4.42 kW
COP Tj = -7°C
3.02
2.39
Cdh Tj = -7 °C
0.99
0.992
Pdh Tj = +2°C
2.69 kW
2.69 kW
COP Tj = +2°C
4.42
3.22
Cdh Tj = +2 °C
0.975
0.982
Pdh Tj = +7°C
1.73 kW
1.73 kW
COP Tj = +7°C
6.08
4.8
Cdh Tj = +7 °C
0.947
0.958
Pdh Tj = 12°C
1.68 kW
1.8 kW
COP Tj = 12°C
7.5
6.54
Cdh Tj = +12 °C
0.933
0.946
Pdh Tj = Tbiv
4.42 kW
4.42 kW
COP Tj = Tbiv
3.02
2.39
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
4.9 kW
4.9 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.76
2.07
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.992
0.994
WTOL
75 °C
75 °C
Poff
15 W
15 W
PTO
15 W
15 W
PSB
15 W
15 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.1 kW
0.1 kW
Annual energy consumption Qhe
2236 kWh
2929 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
4 kW
4 kW
El input
0.78 kW
1.27 kW
COP
5.1
3.15
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Cooling
EN 14511-2
+7°C/+12°C
+18°C/+23°C
El input
1.03 kW
1.31 kW
Cooling capacity
3.2
4.2
EER
3.1
3.2
EN 14825
+7°C/+12°C
+18°C/+23°C
Pdesignc
3.2 kW
4.2 kW
SEER
3.99
4.89
Pdc Tj = 35°C
3.2 kW
4.2 kW
EER Tj = 35°C
3.1
3.2
Cdc Tj = 35 °C
0.985
0.989
Pdc Tj = 30°C
2.35 kW
3.07 kW
EER Tj = 30°C
3.69
4.3
Cdc Tj = 30 °C
0.976
0.979
Pdc Tj = 25°C
1.51 kW
1.97 kW
EER Tj = 25°C
4.48
5.59
Cdc Tj = 25 °C
0.955
0.957
Pdc Tj = 20°C
1.31 kW
1.8 kW
EER Tj = 20°C
5.39
7.24
Cdc Tj = 20 °C
0.938
0.94
Poff
15 W
15 W
PTO
15 W
15 W
PSB
15 W
15 W
PCK
0 W
0 W
Annual energy consumption Qce
481 kWh
515 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
56 dB(A)
56 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
182 %
138 %
Prated
5 kW
5 kW
SCOP
4.62
3.53
Tbiv
-7 °C
-7 °C
TOL
-25 °C
-25 °C
Pdh Tj = -7°C
4.42 kW
4.42 kW
COP Tj = -7°C
3.02
2.39
Cdh Tj = -7 °C
0.99
0.992
Pdh Tj = +2°C
2.69 kW
2.69 kW
COP Tj = +2°C
4.42
3.22
Cdh Tj = +2 °C
0.975
0.982
Pdh Tj = +7°C
1.73 kW
1.73 kW
COP Tj = +7°C
6.08
4.8
Cdh Tj = +7 °C
0.947
0.958
Pdh Tj = 12°C
1.68 kW
1.8 kW
COP Tj = 12°C
7.5
6.54
Cdh Tj = +12 °C
0.933
0.946
Pdh Tj = Tbiv
4.42 kW
4.42 kW
COP Tj = Tbiv
3.02
2.39
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
4.9 kW
4.9 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.76
2.07
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.992
0.994
WTOL
75 °C
75 °C
Poff
15 W
15 W
PTO
15 W
15 W
PSB
15 W
15 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.1 kW
0.1 kW
Annual energy consumption Qhe
2236 kWh
2929 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
4 kW
4 kW
El input
0.78 kW
1.27 kW
COP
5.1
3.15
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Cooling
EN 14511-2
+7°C/+12°C
+18°C/+23°C
El input
1.03 kW
1.31 kW
Cooling capacity
3.2
4.2
EER
3.1
3.2
EN 14825
+7°C/+12°C
+18°C/+23°C
Pdesignc
3.2 kW
4.2 kW
SEER
3.99
4.89
Pdc Tj = 35°C
3.2 kW
4.2 kW
EER Tj = 35°C
3.1
3.2
Cdc Tj = 35 °C
0.985
0.989
Pdc Tj = 30°C
2.35 kW
3.07 kW
EER Tj = 30°C
3.69
4.3
Cdc Tj = 30 °C
0.976
0.979
Pdc Tj = 25°C
1.51 kW
1.97 kW
EER Tj = 25°C
4.48
5.59
Cdc Tj = 25 °C
0.955
0.957
Pdc Tj = 20°C
1.31 kW
1.8 kW
EER Tj = 20°C
5.39
7.24
Cdc Tj = 20 °C
0.938
0.94
Poff
15 W
15 W
PTO
15 W
15 W
PSB
15 W
15 W
PCK
0 W
0 W
Annual energy consumption Qce
481 kWh
515 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
56 dB(A)
56 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
182 %
138 %
Prated
5 kW
5 kW
SCOP
4.62
3.53
Tbiv
-7 °C
-7 °C
TOL
-25 °C
-25 °C
Pdh Tj = -7°C
4.42 kW
4.42 kW
COP Tj = -7°C
3.02
2.39
Cdh Tj = -7 °C
0.99
0.992
Pdh Tj = +2°C
2.69 kW
2.69 kW
COP Tj = +2°C
4.42
3.22
Cdh Tj = +2 °C
0.975
0.982
Pdh Tj = +7°C
1.73 kW
1.73 kW
COP Tj = +7°C
6.08
4.8
Cdh Tj = +7 °C
0.947
0.958
Pdh Tj = 12°C
1.68 kW
1.8 kW
COP Tj = 12°C
7.5
6.54
Cdh Tj = +12 °C
0.933
0.946
Pdh Tj = Tbiv
4.42 kW
4.42 kW
COP Tj = Tbiv
3.02
2.39
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
4.9 kW
4.9 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.76
2.07
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.992
0.994
WTOL
75 °C
75 °C
Poff
15 W
15 W
PTO
15 W
15 W
PSB
15 W
15 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.1 kW
0.1 kW
Annual energy consumption Qhe
2236 kWh
2929 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
5 kW
5 kW
El input
1 kW
1.61 kW
COP
5
3.1
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Cooling
EN 14511-2
+7°C/+12°C
+18°C/+23°C
El input
1.24 kW
1.53 kW
Cooling capacity
3.6
4.6
EER
2.9
3
EN 14825
+7°C/+12°C
+18°C/+23°C
Pdesignc
3.6 kW
4.6 kW
SEER
3.98
4.79
Pdc Tj = 35°C
3.6 kW
4.6 kW
EER Tj = 35°C
2.9
3
Cdc Tj = 35 °C
0.988
0.99
Pdc Tj = 30°C
2.64 kW
3.37 kW
EER Tj = 30°C
3.64
4.19
Cdc Tj = 30 °C
0.979
0.981
Pdc Tj = 25°C
1.7 kW
2.16 kW
EER Tj = 25°C
4.47
5.49
Cdc Tj = 25 °C
0.961
0.962
Pdc Tj = 20°C
1.65 kW
2.22 kW
EER Tj = 20°C
5.4
7.05
Cdc Tj = 20 °C
0.951
0.952
Poff
15 W
15 W
PTO
15 W
15 W
PSB
15 W
15 W
PCK
0 W
0 W
Annual energy consumption Qce
543 kWh
576 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
56 dB(A)
56 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
175 %
137 %
Prated
6 kW
6 kW
SCOP
4.46
3.5
Tbiv
-7 °C
-7 °C
TOL
-25 °C
-25 °C
Pdh Tj = -7°C
5.31 kW
5.31 kW
COP Tj = -7°C
2.97
2.35
Cdh Tj = -7 °C
0.992
0.993
Pdh Tj = +2°C
3.23 kW
3.23 kW
COP Tj = +2°C
4.4
3.42
Cdh Tj = +2 °C
0.98
0.984
Pdh Tj = +7°C
2.08 kW
2.08 kW
COP Tj = +7°C
5.78
4.42
Cdh Tj = +7 °C
0.958
0.968
Pdh Tj = 12°C
1.8 kW
1.7 kW
COP Tj = 12°C
7.69
6.39
Cdh Tj = +12 °C
0.936
0.944
Pdh Tj = Tbiv
5.31 kW
5.31 kW
COP Tj = Tbiv
2.97
2.35
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.9 kW
5.9 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.63
2.03
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.993
0.995
WTOL
75 °C
75 °C
Poff
15 W
15 W
PTO
15 W
15 W
PSB
15 W
15 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.1 kW
0.1 kW
Annual energy consumption Qhe
2778 kWh
3541 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
134 %
COP
3.19
Heating up time
2:59 h:min
Standby power input
41 W
Reference hot water temperature
52.5 °C
Mixed water at 40°C
278 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
5 kW
5 kW
El input
1 kW
1.61 kW
COP
5
3.1
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Cooling
EN 14511-2
+7°C/+12°C
+18°C/+23°C
El input
1.24 kW
1.53 kW
Cooling capacity
3.6
4.6
EER
2.9
3
EN 14825
+7°C/+12°C
+18°C/+23°C
Pdesignc
3.6 kW
4.6 kW
SEER
3.98
4.79
Pdc Tj = 35°C
3.6 kW
4.6 kW
EER Tj = 35°C
2.9
3
Cdc Tj = 35 °C
0.988
0.99
Pdc Tj = 30°C
2.64 kW
3.37 kW
EER Tj = 30°C
3.64
4.19
Cdc Tj = 30 °C
0.979
0.981
Pdc Tj = 25°C
1.7 kW
2.16 kW
EER Tj = 25°C
4.47
5.49
Cdc Tj = 25 °C
0.961
0.962
Pdc Tj = 20°C
1.65 kW
2.22 kW
EER Tj = 20°C
5.4
7.05
Cdc Tj = 20 °C
0.951
0.952
Poff
15 W
15 W
PTO
15 W
15 W
PSB
15 W
15 W
PCK
0 W
0 W
Annual energy consumption Qce
543 kWh
576 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
56 dB(A)
56 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
179 %
139 %
Prated
6 kW
6 kW
SCOP
4.55
3.56
Tbiv
-7 °C
-7 °C
TOL
-25 °C
-25 °C
Pdh Tj = -7°C
5.31 kW
5.31 kW
COP Tj = -7°C
2.97
2.35
Cdh Tj = -7 °C
0.992
0.993
Pdh Tj = +2°C
3.23 kW
3.23 kW
COP Tj = +2°C
4.4
3.42
Cdh Tj = +2 °C
0.98
0.984
Pdh Tj = +7°C
2.08 kW
2.08 kW
COP Tj = +7°C
5.78
4.42
Cdh Tj = +7 °C
0.958
0.968
Pdh Tj = 12°C
1.8 kW
1.7 kW
COP Tj = 12°C
7.69
6.39
Cdh Tj = +12 °C
0.936
0.944
Pdh Tj = Tbiv
5.31 kW
5.31 kW
COP Tj = Tbiv
2.97
2.35
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.9 kW
5.9 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.63
2.03
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.993
0.995
WTOL
75 °C
75 °C
Poff
15 W
15 W
PTO
15 W
15 W
PSB
15 W
15 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.1 kW
0.1 kW
Annual energy consumption Qhe
2723 kWh
3486 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
134 %
COP
3.19
Heating up time
2:59 h:min
Standby power input
41 W
Reference hot water temperature
52.5 °C
Mixed water at 40°C
278 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
5 kW
5 kW
El input
1 kW
1.61 kW
COP
5
3.1
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Cooling
EN 14511-2
+7°C/+12°C
+18°C/+23°C
El input
1.24 kW
1.53 kW
Cooling capacity
3.6
4.6
EER
2.9
3
EN 14825
+7°C/+12°C
+18°C/+23°C
Pdesignc
3.6 kW
4.6 kW
SEER
3.98
4.79
Pdc Tj = 35°C
3.6 kW
4.6 kW
EER Tj = 35°C
2.9
3
Cdc Tj = 35 °C
0.988
0.99
Pdc Tj = 30°C
2.64 kW
3.37 kW
EER Tj = 30°C
3.64
4.19
Cdc Tj = 30 °C
0.979
0.981
Pdc Tj = 25°C
1.7 kW
2.16 kW
EER Tj = 25°C
4.47
5.49
Cdc Tj = 25 °C
0.961
0.962
Pdc Tj = 20°C
1.65 kW
2.22 kW
EER Tj = 20°C
5.4
7.05
Cdc Tj = 20 °C
0.951
0.952
Poff
15 W
15 W
PTO
15 W
15 W
PSB
15 W
15 W
PCK
0 W
0 W
Annual energy consumption Qce
543 kWh
576 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
56 dB(A)
56 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
179 %
139 %
Prated
6 kW
6 kW
SCOP
4.55
3.56
Tbiv
-7 °C
-7 °C
TOL
-25 °C
-25 °C
Pdh Tj = -7°C
5.31 kW
5.31 kW
COP Tj = -7°C
2.97
2.35
Cdh Tj = -7 °C
0.992
0.993
Pdh Tj = +2°C
3.23 kW
3.23 kW
COP Tj = +2°C
4.4
3.42
Cdh Tj = +2 °C
0.98
0.984
Pdh Tj = +7°C
2.08 kW
2.08 kW
COP Tj = +7°C
5.78
4.42
Cdh Tj = +7 °C
0.958
0.968
Pdh Tj = 12°C
1.8 kW
1.7 kW
COP Tj = 12°C
7.69
6.39
Cdh Tj = +12 °C
0.936
0.944
Pdh Tj = Tbiv
5.31 kW
5.31 kW
COP Tj = Tbiv
2.97
2.35
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.9 kW
5.9 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.63
2.03
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.993
0.995
WTOL
75 °C
75 °C
Poff
15 W
15 W
PTO
15 W
15 W
PSB
15 W
15 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.1 kW
0.1 kW
Annual energy consumption Qhe
2723 kWh
3486 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
5 kW
5 kW
El input
1 kW
1.61 kW
COP
5
3.1
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Cooling
EN 14511-2
+7°C/+12°C
+18°C/+23°C
El input
1.24 kW
1.53 kW
Cooling capacity
3.6
4.6
EER
2.9
3
EN 14825
+7°C/+12°C
+18°C/+23°C
Pdesignc
3.6 kW
4.6 kW
SEER
3.98
4.79
Pdc Tj = 35°C
3.6 kW
4.6 kW
EER Tj = 35°C
2.9
3
Cdc Tj = 35 °C
0.988
0.99
Pdc Tj = 30°C
2.64 kW
3.37 kW
EER Tj = 30°C
3.64
4.19
Cdc Tj = 30 °C
0.979
0.981
Pdc Tj = 25°C
1.7 kW
2.16 kW
EER Tj = 25°C
4.47
5.49
Cdc Tj = 25 °C
0.961
0.962
Pdc Tj = 20°C
1.65 kW
2.22 kW
EER Tj = 20°C
5.4
7.05
Cdc Tj = 20 °C
0.951
0.952
Poff
15 W
15 W
PTO
15 W
15 W
PSB
15 W
15 W
PCK
0 W
0 W
Annual energy consumption Qce
543 kWh
576 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
56 dB(A)
56 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
179 %
139 %
Prated
6 kW
6 kW
SCOP
4.55
3.56
Tbiv
-7 °C
-7 °C
TOL
-25 °C
-25 °C
Pdh Tj = -7°C
5.31 kW
5.31 kW
COP Tj = -7°C
2.97
2.35
Cdh Tj = -7 °C
0.992
0.993
Pdh Tj = +2°C
3.23 kW
3.23 kW
COP Tj = +2°C
4.4
3.42
Cdh Tj = +2 °C
0.98
0.984
Pdh Tj = +7°C
2.08 kW
2.08 kW
COP Tj = +7°C
5.78
4.42
Cdh Tj = +7 °C
0.958
0.968
Pdh Tj = 12°C
1.8 kW
1.7 kW
COP Tj = 12°C
7.69
6.39
Cdh Tj = +12 °C
0.936
0.944
Pdh Tj = Tbiv
5.31 kW
5.31 kW
COP Tj = Tbiv
2.97
2.35
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.9 kW
5.9 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.63
2.03
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.993
0.995
WTOL
75 °C
75 °C
Poff
15 W
15 W
PTO
15 W
15 W
PSB
15 W
15 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.1 kW
0.1 kW
Annual energy consumption Qhe
2723 kWh
3486 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
5 kW
5 kW
El input
1 kW
1.61 kW
COP
5
3.1
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Cooling
EN 14511-2
+7°C/+12°C
+18°C/+23°C
El input
1.24 kW
1.53 kW
Cooling capacity
3.6
4.6
EER
2.9
3
EN 14825
+7°C/+12°C
+18°C/+23°C
Pdesignc
3.6 kW
4.6 kW
SEER
3.98
4.79
Pdc Tj = 35°C
3.6 kW
4.6 kW
EER Tj = 35°C
2.9
3
Cdc Tj = 35 °C
0.988
0.99
Pdc Tj = 30°C
2.64 kW
3.37 kW
EER Tj = 30°C
3.64
4.19
Cdc Tj = 30 °C
0.979
0.981
Pdc Tj = 25°C
1.7 kW
2.16 kW
EER Tj = 25°C
4.47
5.49
Cdc Tj = 25 °C
0.961
0.962
Pdc Tj = 20°C
1.65 kW
2.22 kW
EER Tj = 20°C
5.4
7.05
Cdc Tj = 20 °C
0.951
0.952
Poff
15 W
15 W
PTO
15 W
15 W
PSB
15 W
15 W
PCK
0 W
0 W
Annual energy consumption Qce
543 kWh
576 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
56 dB(A)
56 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
179 %
139 %
Prated
6 kW
6 kW
SCOP
4.55
3.56
Tbiv
-7 °C
-7 °C
TOL
-25 °C
-25 °C
Pdh Tj = -7°C
5.31 kW
5.31 kW
COP Tj = -7°C
2.97
2.35
Cdh Tj = -7 °C
0.992
0.993
Pdh Tj = +2°C
3.23 kW
3.23 kW
COP Tj = +2°C
4.4
3.42
Cdh Tj = +2 °C
0.98
0.984
Pdh Tj = +7°C
2.08 kW
2.08 kW
COP Tj = +7°C
5.78
4.42
Cdh Tj = +7 °C
0.958
0.968
Pdh Tj = 12°C
1.8 kW
1.7 kW
COP Tj = 12°C
7.69
6.39
Cdh Tj = +12 °C
0.936
0.944
Pdh Tj = Tbiv
5.31 kW
5.31 kW
COP Tj = Tbiv
2.97
2.35
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.9 kW
5.9 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.63
2.03
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.993
0.995
WTOL
75 °C
75 °C
Poff
15 W
15 W
PTO
15 W
15 W
PSB
15 W
15 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.1 kW
0.1 kW
Annual energy consumption Qhe
2723 kWh
3486 kWh