1,650 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
15.87 kW
14.86 kW
El input
3.45 kW
4.98 kW
COP
4.60
2.98
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
69 dB(A)
69 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
182 %
135 %
Prated
12.74 kW
12.10 kW
SCOP
4.64
3.46
Tbiv
-7 °C
-7 °C
TOL
-25 °C
-25 °C
Pdh Tj = -7°C
11.27 kW
10.70 kW
COP Tj = -7°C
3.03
2.23
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
6.89 kW
6.54 kW
COP Tj = +2°C
4.57
3.32
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
5.57 kW
5.13 kW
COP Tj = +7°C
5.92
4.60
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
5.26 kW
5.37 kW
COP Tj = 12°C
8.53
6.86
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
11.27 kW
10.70 kW
COP Tj = Tbiv
3.03
2.23
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11.64 kW
11.19 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.58
1.88
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
75 °C
75 °C
Poff
14 W
14 W
PTO
17 W
17 W
PSB
14 W
14 W
PCK
41 W
41 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.10 kW
0.91 kW
Annual energy consumption Qhe
5677 kWh
7226 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
19.12 kW
18.31 kW
El input
4.50 kW
6.39 kW
COP
4.25
2.87
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
70 dB(A)
72 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
182 %
137 %
Prated
14.68 kW
13.94 kW
SCOP
4.63
3.49
Tbiv
-7 °C
-7 °C
TOL
-25 °C
-25 °C
Pdh Tj = -7°C
12.99 kW
12.33 kW
COP Tj = -7°C
2.96
2.17
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
8.10 kW
7.74 kW
COP Tj = +2°C
4.39
3.35
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
5.90 kW
5.59 kW
COP Tj = +7°C
6.35
4.65
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
5.77 kW
5.62 kW
COP Tj = 12°C
8.97
7.10
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
12.99 kW
12.33 kW
COP Tj = Tbiv
2.96
2.17
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
13.51 kW
13.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.63
1.91
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
75 °C
75 °C
Poff
14 W
14 W
PTO
17 W
17 W
PSB
14 W
14 W
PCK
39 W
39 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.18 kW
0.94 kW
Annual energy consumption Qhe
6548 kWh
8254 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
17.75 kW
16.81 kW
El input
4.03 kW
5.70 kW
COP
4.40
2.95
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
70 dB(A)
70 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
185 %
137 %
Prated
13.86 kW
12.94 kW
SCOP
4.70
3.51
Tbiv
-7 °C
-7 °C
TOL
-25 °C
-25 °C
Pdh Tj = -7°C
12.26 kW
11.44 kW
COP Tj = -7°C
2.99
2.16
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
7.62 kW
6.97 kW
COP Tj = +2°C
4.68
3.52
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
5.52 kW
4.89 kW
COP Tj = +7°C
6.18
4.39
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
5.82 kW
5.45 kW
COP Tj = 12°C
7.69
6.38
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
12.26 kW
11.44 kW
COP Tj = Tbiv
2.99
2.16
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
12.34 kW
11.93 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.54
1.85
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
75 °C
75 °C
Poff
14 W
14 W
PTO
18 W
18 W
PSB
14 W
14 W
PCK
39 W
39 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.52 kW
1.01 kW
Annual energy consumption Qhe
6088 kWh
7612 kWh