0,780 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
8.71 kW
7.95 kW
El input
1.86 kW
2.49 kW
COP
4.69
3.20
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
63 dB(A)
64 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
191 %
144 %
Prated
6.16 kW
5.85 kW
SCOP
4.84
3.67
Tbiv
-7 °C
-7 °C
TOL
-25 °C
-25 °C
Pdh Tj = -7°C
5.45 kW
5.18 kW
COP Tj = -7°C
2.99
2.33
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
3.39 kW
3.17 kW
COP Tj = +2°C
4.69
3.54
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
2.53 kW
2.35 kW
COP Tj = +7°C
6.95
4.91
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
2.87 kW
2.80 kW
COP Tj = 12°C
9.99
7.38
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
5.45 kW
5.18 kW
COP Tj = Tbiv
2.99
2.33
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
4.02 kW
5.16 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.23
2.09
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
74 °C
74 °C
Poff
10 W
10 W
PTO
14 W
14 W
PSB
10 W
10 W
PCK
45 W
45 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
2.14 kW
0.70 kW
Annual energy consumption Qhe
2627 kWh
3296 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
8.50 kW
7.91 kW
El input
1.94 kW
2.59 kW
COP
4.39
3.05
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
63 dB(A)
64 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
188 %
138 %
Prated
6.30 kW
5.78 kW
SCOP
4.78
3.51
Tbiv
-7 °C
-7 °C
TOL
-25 °C
-25 °C
Pdh Tj = -7°C
5.57 kW
5.11 kW
COP Tj = -7°C
3.02
2.18
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
3.40 kW
3.15 kW
COP Tj = +2°C
4.58
3.44
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
2.44 kW
2.23 kW
COP Tj = +7°C
6.67
4.62
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
2.72 kW
2.64 kW
COP Tj = 12°C
8.56
6.79
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
5.57 kW
5.11 kW
COP Tj = Tbiv
3.02
2.18
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.54 kW
5.07 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.77
2.01
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
75 °C
75 °C
Poff
10 W
10 W
PTO
13 W
12 W
PSB
10 W
10 W
PCK
45 W
45 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.76 kW
0.71 kW
Annual energy consumption Qhe
2726 kWh
3400 kWh