2,300 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
15.92 kW
15.96 kW
El input
3.83 kW
5.95 kW
COP
4.16
2.68
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
67 dB(A)
68 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
178 %
129 %
Prated
11.33 kW
10.75 kW
SCOP
4.52
3.30
Tbiv
-7 °C
-7 °C
TOL
-25 °C
-25 °C
Pdh Tj = -7°C
10.02 kW
9.51 kW
COP Tj = -7°C
2.97
2.04
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
6.35 kW
5.80 kW
COP Tj = +2°C
4.58
3.32
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
7.24 kW
6.82 kW
COP Tj = +7°C
6.00
4.54
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
8.54 kW
8.08 kW
COP Tj = 12°C
8.15
6.23
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
10.02 kW
9.51 kW
COP Tj = Tbiv
2.97
2.04
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
10.86 kW
10.66 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.66
1.81
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
54 °C
54 °C
Poff
13 W
13 W
PTO
22 W
22 W
PSB
13 W
13 W
PCK
42 W
42 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.47 kW
0.09 kW
Annual energy consumption Qhe
5181 kWh
6736 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
15.87 kW
15.94 kW
El input
3.84 kW
5.89 kW
COP
4.14
2.71
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
67 dB(A)
68 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
178 %
129 %
Prated
11.19 kW
10.10 kW
SCOP
4.53
3.29
Tbiv
-7 °C
-7 °C
TOL
-25 °C
-25 °C
Pdh Tj = -7°C
9.89 kW
8.94 kW
COP Tj = -7°C
2.90
1.93
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
6.26 kW
5.56 kW
COP Tj = +2°C
4.52
3.35
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
7.18 kW
6.74 kW
COP Tj = +7°C
6.27
4.60
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
8.40 kW
7.99 kW
COP Tj = 12°C
8.31
6.41
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
9.89 kW
8.94 kW
COP Tj = Tbiv
2.90
1.93
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11.12 kW
10.14 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.64
1.88
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
54 °C
54 °C
Poff
13 W
13 W
PTO
21 W
21 W
PSB
13 W
13 W
PCK
43 W
43 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.07 kW
0.00 kW
Annual energy consumption Qhe
5103 kWh
6351 kWh