1,550 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
4.52 kW
7.04 kW
El input
0.89 kW
2.24 kW
COP
5.08
3.14
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
200 %
148 %
Prated
9.00 kW
9.00 kW
SCOP
5.07
3.77
Tbiv
-8 °C
-8 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
7.52 kW
7.83 kW
COP Tj = -7°C
3.11
2.38
Cdh Tj = -7 °C
0.990
1.000
Pdh Tj = +2°C
4.69 kW
4.72 kW
COP Tj = +2°C
5.10
3.68
Cdh Tj = +2 °C
0.990
0.990
Pdh Tj = +7°C
3.20 kW
3.20 kW
COP Tj = +7°C
6.44
4.89
Cdh Tj = +7 °C
0.970
0.980
Pdh Tj = 12°C
3.45 kW
3.24 kW
COP Tj = 12°C
7.80
5.97
Cdh Tj = +12 °C
0.970
0.980
Pdh Tj = Tbiv
8.57 kW
8.11 kW
COP Tj = Tbiv
2.89
2.25
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.87 kW
7.26 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.66
2.02
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
°C
°C
Poff
12 W
12 W
PTO
13 W
13 W
PSB
13 W
13 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.13 kW
1.74 kW
Annual energy consumption Qhe
3668 kWh
4937 kWh