BAXI AURIGA HP 26

Certificate Holder
BAXI S.p.A.
Via Trozzetti, 20
Bassano del Grappa (VI)
Italy
Registration number
007-DO0156
Certification Body
Kiwa Nederland B.V.
Subtype title
BAXI AURIGA HP 26
Driving energy
Electricity
Heat Pump Type
Outdoor Air/Water
Refrigerant
R32
Mass of Refrigerant

4,800 kg

Certification Date
27.06.2023
Testing basis
European KEYMARK Scheme for Heat Pumps (v11)
Generate PDF Export model CSV Download certificate
  • Number of models 2

Models

AURIGA HP 26T
Configure model
Model name
AURIGA HP 26T
Application
Heating (medium temp)
Units
Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
+7°C/12°C and +18°C/+23°C
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

27.19 kW

18.83 kW

El input

6.32 kW

6.45 kW

COP

4.30

2.92

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Cooling

EN 14511-2

+7°C/+12°C

+18°C/+23°C

El input

7.74 kW

5.60 kW

Cooling capacity

24.75

26.00

EER

3.20

4.64

EN 14825

+7°C/+12°C

+18°C/+23°C

Pdesignc

24.75 kW

26.00 kW

SEER

4.76

7.29

Pdc Tj = 35°C

24.75 kW

26.00 kW

EER Tj = 35°C

3.20

4.64

Cdc Tj = 35 °C

1.000

1.000

Pdc Tj = 30°C

18.10 kW

19.70 kW

EER Tj = 30°C

4.22

6.20

Cdc Tj = 30 °C

1.000

1.000

Pdc Tj = 25°C

11.83 kW

12.40 kW

EER Tj = 25°C

5.35

8.35

Cdc Tj = 25 °C

1.000

1.000

Pdc Tj = 20°C

8.26 kW

8.68 kW

EER Tj = 20°C

6.26

10.80

Cdc Tj = 20 °C

0.900

0.900

Poff

0 W

0 W

PTO

26 W

26 W

PSB

26 W

26 W

PCK

26 W

26 W

Annual energy consumption Qce

14850 kWh

15600 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

69 dB(A)

65 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

170 %

136 %

Prated

23.00 kW

17.90 kW

SCOP

4.31

3.47

Tbiv

-5 °C

-5 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

18.92 kW

14.77 kW

COP Tj = -7°C

2.74

2.22

Cdh Tj = -7 °C

1.000

1.000

Pdh Tj = +2°C

12.96 kW

9.40 kW

COP Tj = +2°C

4.51

3.50

Cdh Tj = +2 °C

1.000

1.000

Pdh Tj = +7°C

7.88 kW

6.47 kW

COP Tj = +7°C

5.40

4.35

Cdh Tj = +7 °C

1.000

1.000

Pdh Tj = 12°C

7.90 kW

7.84 kW

COP Tj = 12°C

6.86

6.40

Cdh Tj = +12 °C

0.900

0.900

Pdh Tj = Tbiv

17.97 kW

13.89 kW

COP Tj = Tbiv

2.91

2.46

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

19.36 kW

14.01 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.70

1.67

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1.000

1.000

WTOL

58 °C

58 °C

Poff

0 W

0 W

PTO

58 W

58 W

PSB

58 W

58 W

PCK

60 W

60 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

3.64 kW

3.89 kW

Annual energy consumption Qhe

11013 kWh

10662 kWh

AURIGA HP/TX 26T
Configure model
Model name
AURIGA HP/TX 26T
Application
Heating (medium temp)
Units
Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
+7°C/12°C and +18°C/+23°C
General Data
Power supply
n/a

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

27.19 kW

18.83 kW

El input

6.32 kW

6.45 kW

COP

4.30

2.92

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Cooling

EN 14511-2

+7°C/+12°C

+18°C/+23°C

El input

7.74 kW

5.60 kW

Cooling capacity

24.75

26.00

EER

3.20

4.64

EN 14825

+7°C/+12°C

+18°C/+23°C

Pdesignc

24.75 kW

26.00 kW

SEER

4.76

7.29

Pdc Tj = 35°C

24.75 kW

26.00 kW

EER Tj = 35°C

3.20

4.64

Cdc Tj = 35 °C

1.000

1.000

Pdc Tj = 30°C

18.10 kW

19.70 kW

EER Tj = 30°C

4.22

6.20

Cdc Tj = 30 °C

1.000

1.000

Pdc Tj = 25°C

11.83 kW

12.40 kW

EER Tj = 25°C

5.35

8.35

Cdc Tj = 25 °C

1.000

1.000

Pdc Tj = 20°C

8.26 kW

8.68 kW

EER Tj = 20°C

6.26

10.80

Cdc Tj = 20 °C

0.900

0.900

Poff

0 W

0 W

PTO

26 W

26 W

PSB

26 W

26 W

PCK

26 W

26 W

Annual energy consumption Qce

14850 kWh

15600 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

69 dB(A)

65 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

170 %

136 %

Prated

23.00 kW

17.90 kW

SCOP

4.31

3.47

Tbiv

-5 °C

-5 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

18.92 kW

14.77 kW

COP Tj = -7°C

2.74

2.22

Cdh Tj = -7 °C

1.000

1.000

Pdh Tj = +2°C

12.96 kW

9.40 kW

COP Tj = +2°C

4.51

3.50

Cdh Tj = +2 °C

1.000

1.000

Pdh Tj = +7°C

7.88 kW

6.47 kW

COP Tj = +7°C

5.40

4.35

Cdh Tj = +7 °C

1.000

1.000

Pdh Tj = 12°C

7.90 kW

7.84 kW

COP Tj = 12°C

6.86

6.40

Cdh Tj = +12 °C

0.900

0.900

Pdh Tj = Tbiv

17.97 kW

13.89 kW

COP Tj = Tbiv

2.91

2.46

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

19.36 kW

14.01 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.70

1.67

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1.000

1.000

WTOL

58 °C

58 °C

Poff

0 W

0 W

PTO

58 W

58 W

PSB

58 W

58 W

PCK

60 W

60 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

3.64 kW

3.89 kW

Annual energy consumption Qhe

11013 kWh

10662 kWh