Certificate holders

Subtype

BAXI AURIGA HP 20

Certificate Holder
BAXI S.p.A.
Via Trozzetti, 20
Bassano del Grappa (VI)
Italy
Registration number
007-DO0152
Certification Body
Kiwa Nederland B.V.
Subtype title
BAXI AURIGA HP 20
Driving energy
Electricity
Heat Pump Type
Outdoor Air/Water
Refrigerant
R32
Mass of Refrigerant

4,800 kg

Certification Date
27.06.2023
Testing basis
European KEYMARK Scheme for Heat Pumps (v11)
Generate PDF Export model CSV Download certificate
  • Number of models 2

Models

AURIGA HP 20T
Configure model
Model name
AURIGA HP 20T
Application
Heating (medium temp)
Units
Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
+7°C/12°C and +18°C/+23°C
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

21.22 kW

15.78 kW

El input

4.84 kW

5.48 kW

COP

4.38

2.88

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Cooling

EN 14511-2

+7°C/+12°C

+18°C/+23°C

El input

6.11 kW

4.31 kW

Cooling capacity

20.04

21.31

EER

3.28

4.95

EN 14825

+7°C/+12°C

+18°C/+23°C

Pdesignc

20.04 kW

21.31 kW

SEER

5.03

7.56

Pdc Tj = 35°C

20.04 kW

21.31 kW

EER Tj = 35°C

3.28

4.95

Cdc Tj = 35 °C

1.000

1.000

Pdc Tj = 30°C

15.79 kW

16.61 kW

EER Tj = 30°C

4.38

6.41

Cdc Tj = 30 °C

1.000

1.000

Pdc Tj = 25°C

9.30 kW

10.22 kW

EER Tj = 25°C

5.64

9.04

Cdc Tj = 25 °C

1.000

1.000

Pdc Tj = 20°C

6.39 kW

7.75 kW

EER Tj = 20°C

7.22

11.09

Cdc Tj = 20 °C

0.900

0.900

Poff

0 W

0 W

PTO

26 W

26 W

PSB

26 W

26 W

PCK

26 W

26 W

Annual energy consumption Qce

12024 kWh

12786 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

69 dB(A)

65 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

174 %

130 %

Prated

16.80 kW

13.80 kW

SCOP

4.42

3.33

Tbiv

-5 °C

-5 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

14.44 kW

11.94 kW

COP Tj = -7°C

2.78

1.95

Cdh Tj = -7 °C

1.000

1.000

Pdh Tj = +2°C

8.53 kW

6.97 kW

COP Tj = +2°C

4.59

3.23

Cdh Tj = +2 °C

1.000

1.000

Pdh Tj = +7°C

6.37 kW

4.80 kW

COP Tj = +7°C

5.22

4.21

Cdh Tj = +7 °C

1.000

1.000

Pdh Tj = 12°C

6.28 kW

6.10 kW

COP Tj = 12°C

7.76

7.04

Cdh Tj = +12 °C

0.900

0.900

Pdh Tj = Tbiv

13.78 kW

11.63 kW

COP Tj = Tbiv

3.10

2.40

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

15.87 kW

13.20 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.67

1.74

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1.000

1.000

WTOL

58 °C

58 °C

Poff

0 W

0 W

PTO

58 W

58 W

PSB

58 W

58 W

PCK

60 W

60 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.93 kW

0.60 kW

Annual energy consumption Qhe

7847 kWh

8573 kWh

AURIGA HP/TX 20T
Configure model
Model name
AURIGA HP/TX 20T
Application
Heating (medium temp)
Units
Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
+7°C/12°C and +18°C/+23°C
General Data
Power supply
n/a

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

21.22 kW

15.78 kW

El input

4.84 kW

5.48 kW

COP

4.38

2.88

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Cooling

EN 14511-2

+7°C/+12°C

+18°C/+23°C

El input

6.11 kW

4.31 kW

Cooling capacity

20.04

21.31

EER

3.28

4.95

EN 14825

+7°C/+12°C

+18°C/+23°C

Pdesignc

20.04 kW

21.31 kW

SEER

5.03

7.56

Pdc Tj = 35°C

20.04 kW

21.31 kW

EER Tj = 35°C

3.28

4.95

Cdc Tj = 35 °C

1.000

1.000

Pdc Tj = 30°C

15.79 kW

16.61 kW

EER Tj = 30°C

4.38

6.41

Cdc Tj = 30 °C

1.000

1.000

Pdc Tj = 25°C

9.30 kW

10.22 kW

EER Tj = 25°C

5.64

9.04

Cdc Tj = 25 °C

1.000

1.000

Pdc Tj = 20°C

6.39 kW

7.75 kW

EER Tj = 20°C

7.22

11.09

Cdc Tj = 20 °C

0.900

0.900

Poff

0 W

0 W

PTO

26 W

26 W

PSB

26 W

26 W

PCK

26 W

26 W

Annual energy consumption Qce

12024 kWh

12786 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

69 dB(A)

65 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

174 %

130 %

Prated

16.80 kW

13.80 kW

SCOP

4.42

3.33

Tbiv

-5 °C

-5 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

14.44 kW

11.94 kW

COP Tj = -7°C

2.78

1.95

Cdh Tj = -7 °C

1.000

1.000

Pdh Tj = +2°C

8.53 kW

6.97 kW

COP Tj = +2°C

4.59

3.23

Cdh Tj = +2 °C

1.000

1.000

Pdh Tj = +7°C

6.37 kW

4.80 kW

COP Tj = +7°C

5.22

4.21

Cdh Tj = +7 °C

1.000

1.000

Pdh Tj = 12°C

6.28 kW

6.10 kW

COP Tj = 12°C

7.76

7.04

Cdh Tj = +12 °C

0.900

0.900

Pdh Tj = Tbiv

13.78 kW

11.63 kW

COP Tj = Tbiv

3.10

2.40

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

15.87 kW

13.20 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.67

1.74

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1.000

1.000

WTOL

58 °C

58 °C

Poff

0 W

0 W

PTO

58 W

58 W

PSB

58 W

58 W

PCK

60 W

60 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.93 kW

0.60 kW

Annual energy consumption Qhe

7847 kWh

8573 kWh