3,300 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
12.00 kW
12.00 kW
El input
2.35 kW
3.53 kW
COP
5.11
3.40
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
44 dB(A)
44 dB(A)
Sound power level outdoor
59 dB(A)
59 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
193 %
148 %
Prated
12.60 kW
12.60 kW
SCOP
4.90
3.78
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
11.15 kW
11.15 kW
COP Tj = -7°C
3.10
2.30
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
6.80 kW
6.80 kW
COP Tj = +2°C
4.70
3.70
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
4.70 kW
4.70 kW
COP Tj = +7°C
6.60
5.00
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
4.70 kW
4.70 kW
COP Tj = 12°C
8.60
6.30
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
11.15 kW
11.15 kW
COP Tj = Tbiv
3.10
2.30
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
12.30 kW
12.30 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.70
2.05
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
70 °C
70 °C
Poff
22 W
22 W
PTO
22 W
22 W
PSB
22 W
22 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.30 kW
0.30 kW
Annual energy consumption Qhe
5277 kWh
6862 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
115 %
COP
2.60
Heating up time
0:54 h:min
Standby power input
65.0 W
Reference hot water temperature
52.1 °C
Mixed water at 40°C
206 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
14.00 kW
14.00 kW
El input
2.77 kW
4.18 kW
COP
5.05
3.35
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
44 dB(A)
44 dB(A)
Sound power level outdoor
60 dB(A)
60 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
190 %
147 %
Prated
13.60 kW
13.60 kW
SCOP
4.83
3.75
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
12.03 kW
12.03 kW
COP Tj = -7°C
2.90
2.28
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
7.32 kW
7.30 kW
COP Tj = +2°C
4.65
3.65
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
4.80 kW
4.80 kW
COP Tj = +7°C
6.60
5.00
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
4.80 kW
4.80 kW
COP Tj = 12°C
8.60
6.28
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
12.03 kW
12.00 kW
COP Tj = Tbiv
2.90
2.28
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
13.30 kW
13.30 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.65
2.00
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
70 °C
70 °C
Poff
22 W
22 W
PTO
22 W
22 W
PSB
22 W
22 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.30 kW
0.30 kW
Annual energy consumption Qhe
5796 kWh
7472 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
115 %
COP
2.60
Heating up time
0:54 h:min
Standby power input
65.0 W
Reference hot water temperature
52.1 °C
Mixed water at 40°C
206 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
12.00 kW
12.00 kW
El input
2.35 kW
3.53 kW
COP
5.11
3.40
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
44 dB(A)
44 dB(A)
Sound power level outdoor
59 dB(A)
59 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
193 %
148 %
Prated
12.60 kW
12.60 kW
SCOP
4.90
3.78
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
11.15 kW
11.15 kW
COP Tj = -7°C
3.10
2.30
Cdh Tj = -7 °C
Pdh Tj = +2°C
6.80 kW
6.80 kW
COP Tj = +2°C
4.70
3.70
Cdh Tj = +2 °C
Pdh Tj = +7°C
4.70 kW
4.70 kW
COP Tj = +7°C
6.60
5.00
Cdh Tj = +7 °C
Pdh Tj = 12°C
4.70 kW
4.70 kW
COP Tj = 12°C
8.60
6.30
Cdh Tj = +12 °C
Pdh Tj = Tbiv
11.15 kW
11.15 kW
COP Tj = Tbiv
3.10
2.30
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
12.30 kW
12.30 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.70
2.05
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
°C
°C
Poff
22 W
22 W
PTO
22 W
22 W
PSB
22 W
22 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.30 kW
0.30 kW
Annual energy consumption Qhe
5 kWh
6 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
115 %
COP
2.60
Heating up time
0:9 h:min
Standby power input
65.0 W
Reference hot water temperature
52.1 °C
Mixed water at 40°C
206 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
14.00 kW
14.00 kW
El input
2.77 kW
4.18 kW
COP
5.05
3.35
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
44 dB(A)
44 dB(A)
Sound power level outdoor
60 dB(A)
60 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
190 %
147 %
Prated
13.60 kW
13.60 kW
SCOP
4.83
3.75
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
12.03 kW
12.00 kW
COP Tj = -7°C
2.90
2.28
Cdh Tj = -7 °C
Pdh Tj = +2°C
7.32 kW
7.30 kW
COP Tj = +2°C
4.65
3.65
Cdh Tj = +2 °C
Pdh Tj = +7°C
4.80 kW
4.80 kW
COP Tj = +7°C
6.60
5.00
Cdh Tj = +7 °C
Pdh Tj = 12°C
4.80 kW
4.80 kW
COP Tj = 12°C
8.60
6.28
Cdh Tj = +12 °C
Pdh Tj = Tbiv
12.03 kW
12.00 kW
COP Tj = Tbiv
2.90
2.28
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
13.30 kW
13.30 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.65
2.00
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
°C
°C
Poff
22 W
22 W
PTO
22 W
22 W
PSB
22 W
22 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.30 kW
0.30 kW
Annual energy consumption Qhe
5 kWh
7 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
115 %
COP
2.60
Heating up time
0:9 h:min
Standby power input
65.0 W
Reference hot water temperature
52.1 °C
Mixed water at 40°C
206 l