Certificate holders

Subtype

Samsung EHS R32 Mono 8kW (space heating/ 260L)

Certificate Holder
Samsung Electronics Air Conditioner Europe B.V.
Evert van de Beekstraat 310
1118 CX Schiphol
Netherlands
Registration number
011-1W0450
Certification Body
DIN CERTCO Gesellschaft für Konformitätsbewertung mbH
Subtype title
Samsung EHS R32 Mono 8kW (space heating/ 260L)
Driving energy
Electricity
Heat Pump Type
Outdoor Air/Water
Refrigerant
R32
Mass of Refrigerant

1,150 kg

Certification Date
26.01.2021
Testing basis
HP KEYMARK certification scheme rules V7
Generate PDF Export model CSV
  • Number of models 5

Models

AE080RXYDEG/EU & AE260RNWMEG/EU
Configure model
Model name
AE080RXYDEG/EU & AE260RNWMEG/EU
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

8.00 kW

7.10 kW

El input

1.77 kW

2.53 kW

COP

4.52

2.81

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

40 dB(A)

40 dB(A)

Sound power level outdoor

63 dB(A)

63 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

175 %

126 %

Prated

8.00 kW

8.00 kW

SCOP

4.44

3.23

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

7.08 kW

7.08 kW

COP Tj = -7°C

2.63

1.90

Cdh Tj = -7 °C

0.90

0.90

Pdh Tj = +2°C

4.31 kW

4.31 kW

COP Tj = +2°C

4.24

3.11

Cdh Tj = +2 °C

0.90

0.90

Pdh Tj = +7°C

3.10 kW

2.80 kW

COP Tj = +7°C

6.39

4.55

Cdh Tj = +7 °C

0.90

0.90

Pdh Tj = 12°C

2.60 kW

2.40 kW

COP Tj = 12°C

8.22

5.77

Cdh Tj = +12 °C

0.90

0.90

Pdh Tj = Tbiv

7.10 kW

7.10 kW

COP Tj = Tbiv

2.63

1.90

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

7.00 kW

6.80 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.48

1.66

WTOL

65 °C

65 °C

Poff

22 W

22 W

PTO

22 W

22 W

PSB

22 W

22 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

1.00 kW

1.20 kW

Annual energy consumption Qhe

3719 kWh

5113 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

XL

Efficiency ηDHW

123 %

COP

2.85

Heating up time

2:25 h:min

Standby power input

65.0 W

Reference hot water temperature

52.0 °C

Mixed water at 40°C

290 l

AE080RXYDGG/EU & MIM-E03CN
Configure model
Model name
AE080RXYDGG/EU & MIM-E03CN
Application
Heating (medium temp)
Units
Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

8.00 kW

7.10 kW

El input

1.77 kW

2.53 kW

COP

4.52

2.81

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

40 dB(A)

40 dB(A)

Sound power level outdoor

63 dB(A)

63 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

175 %

126 %

Prated

8.00 kW

8.00 kW

SCOP

4.44

3.23

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

7.08 kW

7.08 kW

COP Tj = -7°C

2.63

1.90

Cdh Tj = -7 °C

0.90

0.90

Pdh Tj = +2°C

4.31 kW

4.31 kW

COP Tj = +2°C

4.24

3.11

Cdh Tj = +2 °C

0.90

0.90

Pdh Tj = +7°C

3.10 kW

2.80 kW

COP Tj = +7°C

6.39

4.55

Cdh Tj = +7 °C

0.90

0.90

Pdh Tj = 12°C

2.60 kW

2.40 kW

COP Tj = 12°C

8.22

5.77

Cdh Tj = +12 °C

0.90

0.90

Pdh Tj = Tbiv

7.10 kW

7.10 kW

COP Tj = Tbiv

2.63

1.90

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

7.00 kW

6.80 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.48

1.66

WTOL

65 °C

65 °C

Poff

22 W

22 W

PTO

22 W

22 W

PSB

22 W

22 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

1.00 kW

1.20 kW

Annual energy consumption Qhe

3719 kWh

5113 kWh

AE080RXYDGG/EU & AE260RNWMGG/EU
Configure model
Model name
AE080RXYDGG/EU & AE260RNWMGG/EU
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

8.00 kW

7.10 kW

El input

1.77 kW

2.53 kW

COP

4.52

2.81

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

40 dB(A)

40 dB(A)

Sound power level outdoor

63 dB(A)

63 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

175 %

126 %

Prated

8.00 kW

8.00 kW

SCOP

4.44

3.23

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

7.08 kW

7.08 kW

COP Tj = -7°C

2.63

1.90

Cdh Tj = -7 °C

0.90

0.90

Pdh Tj = +2°C

4.31 kW

4.31 kW

COP Tj = +2°C

4.24

3.11

Cdh Tj = +2 °C

0.90

0.90

Pdh Tj = +7°C

3.10 kW

2.80 kW

COP Tj = +7°C

6.39

4.55

Cdh Tj = +7 °C

0.90

0.90

Pdh Tj = 12°C

2.60 kW

2.40 kW

COP Tj = 12°C

8.22

5.77

Cdh Tj = +12 °C

0.90

0.90

Pdh Tj = Tbiv

7.10 kW

7.10 kW

COP Tj = Tbiv

2.63

1.90

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

7.00 kW

6.80 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.48

1.66

WTOL

65 °C

65 °C

Poff

22 W

22 W

PTO

22 W

22 W

PSB

22 W

22 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

1.00 kW

1.20 kW

Annual energy consumption Qhe

3719 kWh

5113 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

XL

Efficiency ηDHW

123 %

COP

2.85

Heating up time

2:25 h:min

Standby power input

65.0 W

Reference hot water temperature

52.0 °C

Mixed water at 40°C

290 l

AE080RXYDEG/EU + AE260CNWMEG/EU
Configure model
Model name
AE080RXYDEG/EU + AE260CNWMEG/EU
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

8.00 kW

7.10 kW

El input

1.77 kW

2.53 kW

COP

4.52

2.81

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

40 dB(A)

40 dB(A)

Sound power level outdoor

63 dB(A)

63 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

175 %

126 %

Prated

8.00 kW

8.00 kW

SCOP

4.44

3.23

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

7.08 kW

7.08 kW

COP Tj = -7°C

2.63

1.90

Cdh Tj = -7 °C

 

 

Pdh Tj = +2°C

4.31 kW

4.31 kW

COP Tj = +2°C

4.24

3.11

Cdh Tj = +2 °C

 

 

Pdh Tj = +7°C

3.10 kW

2.80 kW

COP Tj = +7°C

6.39

4.55

Cdh Tj = +7 °C

 

 

Pdh Tj = 12°C

2.60 kW

2.40 kW

COP Tj = 12°C

8.22

5.77

Cdh Tj = +12 °C

 

 

Pdh Tj = Tbiv

7.10 kW

7.10 kW

COP Tj = Tbiv

2.63

1.90

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

7.00 kW

6.80 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.48

1.66

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

65 °C

65 °C

Poff

22 W

22 W

PTO

22 W

22 W

PSB

22 W

22 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

1.00 kW

1.20 kW

Annual energy consumption Qhe

3 kWh

5 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

XL

Efficiency ηDHW

123 %

COP

2.85

Heating up time

2:25 h:min

Standby power input

65.0 W

Reference hot water temperature

52.0 °C

Mixed water at 40°C

290 l

AE080RXYDGG/EU + AE260CNWMGG/EU
Configure model
Model name
AE080RXYDGG/EU + AE260CNWMGG/EU
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

8.00 kW

7.10 kW

El input

1.77 kW

2.53 kW

COP

4.52

2.81

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

40 dB(A)

40 dB(A)

Sound power level outdoor

63 dB(A)

63 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

175 %

126 %

Prated

8.00 kW

8.00 kW

SCOP

4.44

3.23

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

7.08 kW

7.08 kW

COP Tj = -7°C

2.63

1.90

Cdh Tj = -7 °C

 

 

Pdh Tj = +2°C

4.31 kW

4.31 kW

COP Tj = +2°C

4.24

3.11

Cdh Tj = +2 °C

 

 

Pdh Tj = +7°C

3.10 kW

2.80 kW

COP Tj = +7°C

6.38

4.55

Cdh Tj = +7 °C

 

 

Pdh Tj = 12°C

2.60 kW

2.40 kW

COP Tj = 12°C

8.22

5.77

Cdh Tj = +12 °C

 

 

Pdh Tj = Tbiv

7.10 kW

7.10 kW

COP Tj = Tbiv

2.63

1.90

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

7.00 kW

6.80 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.48

1.66

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

65 °C

65 °C

Poff

22 W

22 W

PTO

22 W

22 W

PSB

22 W

22 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

1.00 kW

1.20 kW

Annual energy consumption Qhe

3 kWh

5 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

XL

Efficiency ηDHW

123 %

COP

2.85

Heating up time

2:25 h:min

Standby power input

65.0 W

Reference hot water temperature

52.0 °C

Mixed water at 40°C

290 l