Certificate holders

Subtype

Samsung EHS R32 Mono 5kW (space heating/ 200L)

Certificate Holder
Samsung Electronics Air Conditioner Europe B.V.
Evert van de Beekstraat 310
1118 CX Schiphol
Netherlands
Registration number
011-1W0448
Certification Body
DIN CERTCO Gesellschaft für Konformitätsbewertung mbH
Subtype title
Samsung EHS R32 Mono 5kW (space heating/ 200L)
Driving energy
Electricity
Heat Pump Type
Outdoor Air/Water
Refrigerant
R32
Mass of Refrigerant

1,000 kg

Certification Date
26.01.2021
Testing basis
HP KEYMARK certification scheme rules V7
Generate PDF Export model CSV
  • Number of models 3

Models

AE050RXYDEG/EU & MIM-E03CN
Configure model
Model name
AE050RXYDEG/EU & MIM-E03CN
Application
Heating (medium temp)
Units
Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

5.00 kW

4.31 kW

El input

1.03 kW

1.52 kW

COP

4.85

2.83

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

40 dB(A)

40 dB(A)

Sound power level outdoor

61 dB(A)

61 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

175 %

125 %

Prated

6.00 kW

5.00 kW

SCOP

4.46

3.20

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

4.87 kW

4.42 kW

COP Tj = -7°C

2.99

2.16

Cdh Tj = -7 °C

0.90

0.90

Pdh Tj = +2°C

2.96 kW

2.69 kW

COP Tj = +2°C

4.18

3.17

Cdh Tj = +2 °C

0.90

0.90

Pdh Tj = +7°C

1.90 kW

1.73 kW

COP Tj = +7°C

6.11

4.03

Cdh Tj = +7 °C

0.90

0.90

Pdh Tj = 12°C

1.88 kW

1.70 kW

COP Tj = 12°C

7.70

4.73

Cdh Tj = +12 °C

0.90

0.90

Pdh Tj = Tbiv

4.87 kW

4.42 kW

COP Tj = Tbiv

2.99

2.16

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

4.60 kW

4.20 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.74

2.00

WTOL

65 °C

65 °C

Poff

22 W

22 W

PTO

22 W

22 W

PSB

22 W

22 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

1.40 kW

0.80 kW

Annual energy consumption Qhe

2548 kWh

3224 kWh

AE050RXYDEG/EU & AE200RNWMEG/EU
Configure model
Model name
AE050RXYDEG/EU & AE200RNWMEG/EU
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

5.00 kW

4.30 kW

El input

1.03 kW

1.52 kW

COP

4.85

2.83

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

40 dB(A)

40 dB(A)

Sound power level outdoor

61 dB(A)

61 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

175 %

125 %

Prated

6.00 kW

5.00 kW

SCOP

4.46

3.20

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

4.87 kW

4.42 kW

COP Tj = -7°C

2.99

2.16

Cdh Tj = -7 °C

0.90

0.90

Pdh Tj = +2°C

2.96 kW

2.69 kW

COP Tj = +2°C

4.18

3.17

Cdh Tj = +2 °C

0.90

0.90

Pdh Tj = +7°C

1.90 kW

1.73 kW

COP Tj = +7°C

6.11

4.03

Cdh Tj = +7 °C

0.90

0.90

Pdh Tj = 12°C

1.88 kW

1.70 kW

COP Tj = 12°C

7.70

4.73

Cdh Tj = +12 °C

0.90

0.90

Pdh Tj = Tbiv

4.87 kW

4.42 kW

COP Tj = Tbiv

2.99

2.16

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

4.59 kW

4.20 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.74

2.00

WTOL

65 °C

65 °C

Poff

22 W

22 W

PTO

22 W

22 W

PSB

22 W

22 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

1.41 kW

0.80 kW

Annual energy consumption Qhe

2548 kWh

3224 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

115 %

COP

2.86

Heating up time

2:20 h:min

Standby power input

58.0 W

Reference hot water temperature

52.1 °C

Mixed water at 40°C

206 l

AE050RXYDEG/EU + AE200CNWMEG/EU
Configure model
Model name
AE050RXYDEG/EU + AE200CNWMEG/EU
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

5.00 kW

4.30 kW

El input

1.03 kW

1.52 kW

COP

4.85

2.83

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

40 dB(A)

40 dB(A)

Sound power level outdoor

61 dB(A)

61 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

175 %

125 %

Prated

6.00 kW

5.00 kW

SCOP

4.46

3.20

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

4.87 kW

4.40 kW

COP Tj = -7°C

2.99

2.16

Cdh Tj = -7 °C

 

 

Pdh Tj = +2°C

2.96 kW

2.69 kW

COP Tj = +2°C

4.18

3.17

Cdh Tj = +2 °C

 

 

Pdh Tj = +7°C

1.90 kW

1.73 kW

COP Tj = +7°C

6.10

4.03

Cdh Tj = +7 °C

 

 

Pdh Tj = 12°C

1.80 kW

1.70 kW

COP Tj = 12°C

7.70

4.73

Cdh Tj = +12 °C

 

 

Pdh Tj = Tbiv

4.87 kW

4.40 kW

COP Tj = Tbiv

2.99

2.16

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

4.59 kW

4.20 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.74

2.00

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

65 °C

65 °C

Poff

22 W

22 W

PTO

22 W

22 W

PSB

22 W

22 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

1.41 kW

0.80 kW

Annual energy consumption Qhe

2 kWh

3 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

115 %

COP

2.86

Heating up time

2:20 h:min

Standby power input

58.0 W

Reference hot water temperature

52.1 °C

Mixed water at 40°C

206 l