5,000 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
8.24 kW
9.03 kW
El input
1.79 kW
2.88 kW
COP
4.61
3.14
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
55 dB(A)
55 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
169 %
135 %
Prated
11.20 kW
11.60 kW
SCOP
4.31
3.44
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
9.89 kW
10.22 kW
COP Tj = -7°C
3.36
2.59
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
7.12 kW
7.06 kW
COP Tj = +2°C
4.17
3.28
Cdh Tj = +2 °C
0.980
0.990
Pdh Tj = +7°C
8.31 kW
8.01 kW
COP Tj = +7°C
5.24
4.25
Cdh Tj = +7 °C
0.980
0.990
Pdh Tj = 12°C
9.57 kW
9.28 kW
COP Tj = 12°C
6.41
5.25
Cdh Tj = +12 °C
0.980
0.980
Pdh Tj = Tbiv
9.89 kW
10.22 kW
COP Tj = Tbiv
3.36
2.59
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
9.25 kW
10.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.11
2.32
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
WTOL
65 °C
65 °C
Poff
10 W
10 W
PTO
10 W
10 W
PSB
10 W
10 W
PCK
38 W
38 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.95 kW
1.60 kW
Annual energy consumption Qhe
5368 kWh
6969 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
8.24 kW
9.03 kW
El input
1.79 kW
2.88 kW
COP
4.61
3.14
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
55 dB(A)
55 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
171 %
139 %
Prated
14.00 kW
14.80 kW
SCOP
4.35
3.54
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
12.34 kW
13.11 kW
COP Tj = -7°C
3.00
2.41
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
7.70 kW
8.08 kW
COP Tj = +2°C
4.31
3.48
Cdh Tj = +2 °C
0.980
0.990
Pdh Tj = +7°C
8.28 kW
8.00 kW
COP Tj = +7°C
5.31
4.37
Cdh Tj = +7 °C
0.980
0.990
Pdh Tj = 12°C
9.52 kW
9.23 kW
COP Tj = 12°C
6.43
5.28
Cdh Tj = +12 °C
0.980
0.980
Pdh Tj = Tbiv
12.34 kW
13.11 kW
COP Tj = Tbiv
3.00
2.41
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
12.63 kW
13.48 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.93
2.27
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
WTOL
65 °C
65 °C
Poff
10 W
10 W
PTO
10 W
10 W
PSB
10 W
10 W
PCK
38 W
38 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.37 kW
1.32 kW
Annual energy consumption Qhe
6657 kWh
8643 kWh