1,840 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
12.10 kW
11.90 kW
El input
2.44 kW
3.84 kW
COP
4.95
3.10
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
43 dB(A)
43 dB(A)
Sound power level outdoor
64 dB(A)
64 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
189 %
135 %
Prated
12.10 kW
11.60 kW
SCOP
4.80
3.44
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
10.72 kW
10.23 kW
COP Tj = -7°C
3.04
2.21
Cdh Tj = -7 °C
1.000
1.000
Pdh Tj = +2°C
7.63 kW
6.59 kW
COP Tj = +2°C
4.40
3.07
Cdh Tj = +2 °C
0.990
0.990
Pdh Tj = +7°C
4.22 kW
4.30 kW
COP Tj = +7°C
6.97
5.07
Cdh Tj = +7 °C
0.980
0.980
Pdh Tj = 12°C
4.74 kW
4.45 kW
COP Tj = 12°C
10.40
7.68
Cdh Tj = +12 °C
0.970
0.970
Pdh Tj = Tbiv
10.72 kW
10.23 kW
COP Tj = Tbiv
3.04
2.21
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
8.86 kW
8.27 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.54
1.81
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
60 °C
60 °C
Poff
16 W
16 W
PTO
17 W
17 W
PSB
16 W
16 W
PCK
43 W
43 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
3.15 kW
3.33 kW
Annual energy consumption Qhe
5210 kWh
6944 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
14.50 kW
13.80 kW
El input
2.99 kW
4.60 kW
COP
4.85
3.00
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
43 dB(A)
43 dB(A)
Sound power level outdoor
65 dB(A)
65 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
187 %
140 %
Prated
13.90 kW
12.10 kW
SCOP
4.75
3.56
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
12.29 kW
10.74 kW
COP Tj = -7°C
2.82
2.20
Cdh Tj = -7 °C
1.000
1.000
Pdh Tj = +2°C
8.32 kW
6.95 kW
COP Tj = +2°C
4.36
3.24
Cdh Tj = +2 °C
0.990
0.990
Pdh Tj = +7°C
5.57 kW
4.28 kW
COP Tj = +7°C
7.09
5.21
Cdh Tj = +7 °C
0.980
0.980
Pdh Tj = 12°C
4.63 kW
4.44 kW
COP Tj = 12°C
10.48
8.08
Cdh Tj = +12 °C
0.960
0.970
Pdh Tj = Tbiv
12.29 kW
10.74 kW
COP Tj = Tbiv
2.82
2.20
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
10.45 kW
8.23 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.85
1.81
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
60 °C
60 °C
Poff
16 W
16 W
PTO
17 W
17 W
PSB
16 W
16 W
PCK
43 W
43 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
3.54 kW
3.87 kW
Annual energy consumption Qhe
6040 kWh
7035 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
16.00 kW
16.00 kW
El input
3.44 kW
5.52 kW
COP
4.65
2.90
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
43 dB(A)
43 dB(A)
Sound power level outdoor
68 dB(A)
68 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
187 %
141 %
Prated
15.00 kW
13.00 kW
SCOP
4.75
3.60
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
13.31 kW
11.48 kW
COP Tj = -7°C
2.75
2.21
Cdh Tj = -7 °C
1.000
1.000
Pdh Tj = +2°C
8.41 kW
7.17 kW
COP Tj = +2°C
4.38
3.28
Cdh Tj = +2 °C
0.990
0.990
Pdh Tj = +7°C
5.55 kW
4.73 kW
COP Tj = +7°C
7.24
5.29
Cdh Tj = +7 °C
0.980
0.980
Pdh Tj = 12°C
4.43 kW
4.41 kW
COP Tj = 12°C
9.68
8.28
Cdh Tj = +12 °C
0.960
0.970
Pdh Tj = Tbiv
13.31 kW
11.48 kW
COP Tj = Tbiv
2.75
2.21
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11.52 kW
8.22 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.81
1.81
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
60 °C
60 °C
Poff
16 W
16 W
PTO
17 W
17 W
PSB
16 W
16 W
PCK
43 W
43 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
3.48 kW
4.78 kW
Annual energy consumption Qhe
6547 kWh
7440 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
12.10 kW
11.90 kW
El input
2.44 kW
3.84 kW
COP
4.95
3.10
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
43 dB(A)
43 dB(A)
Sound power level outdoor
64 dB(A)
64 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
189 %
139 %
Prated
12.00 kW
11.60 kW
SCOP
4.81
3.55
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
10.62 kW
10.22 kW
COP Tj = -7°C
3.18
2.21
Cdh Tj = -7 °C
0.990
1.000
Pdh Tj = +2°C
7.47 kW
6.75 kW
COP Tj = +2°C
4.37
3.28
Cdh Tj = +2 °C
0.990
0.990
Pdh Tj = +7°C
4.19 kW
4.25 kW
COP Tj = +7°C
6.94
4.97
Cdh Tj = +7 °C
0.970
0.980
Pdh Tj = 12°C
4.70 kW
4.43 kW
COP Tj = 12°C
10.17
7.74
Cdh Tj = +12 °C
0.960
0.970
Pdh Tj = Tbiv
10.62 kW
10.22 kW
COP Tj = Tbiv
3.18
2.21
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
8.35 kW
8.13 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.44
1.81
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
60 °C
60 °C
Poff
17 W
17 W
PTO
17 W
17 W
PSB
17 W
17 W
PCK
38 W
38 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
3.65 kW
3.47 kW
Annual energy consumption Qhe
5158 kWh
6732 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
14.50 kW
13.80 kW
El input
2.99 kW
4.60 kW
COP
4.85
3.00
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
43 dB(A)
43 dB(A)
Sound power level outdoor
65 dB(A)
65 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
187 %
140 %
Prated
13.90 kW
12.10 kW
SCOP
4.75
3.59
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
12.25 kW
10.68 kW
COP Tj = -7°C
2.77
2.23
Cdh Tj = -7 °C
1.000
1.000
Pdh Tj = +2°C
8.44 kW
7.08 kW
COP Tj = +2°C
4.41
3.29
Cdh Tj = +2 °C
0.990
0.990
Pdh Tj = +7°C
5.51 kW
4.24 kW
COP Tj = +7°C
7.08
5.11
Cdh Tj = +7 °C
0.980
0.980
Pdh Tj = 12°C
4.65 kW
4.41 kW
COP Tj = 12°C
10.50
8.07
Cdh Tj = +12 °C
0.960
0.970
Pdh Tj = Tbiv
12.25 kW
10.68 kW
COP Tj = Tbiv
2.77
2.23
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
9.57 kW
8.13 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.69
1.82
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
60 °C
60 °C
Poff
17 W
17 W
PTO
17 W
17 W
PSB
17 W
17 W
PCK
38 W
38 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
4.33 kW
3.97 kW
Annual energy consumption Qhe
6029 kWh
6956 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
16.00 kW
16.00 kW
El input
3.44 kW
5.52 kW
COP
4.65
2.90
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
43 dB(A)
43 dB(A)
Sound power level outdoor
68 dB(A)
68 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
187 %
142 %
Prated
15.00 kW
13.00 kW
SCOP
4.74
3.62
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
13.23 kW
11.46 kW
COP Tj = -7°C
2.83
2.21
Cdh Tj = -7 °C
1.000
1.000
Pdh Tj = +2°C
8.19 kW
7.30 kW
COP Tj = +2°C
4.34
3.33
Cdh Tj = +2 °C
0.990
0.990
Pdh Tj = +7°C
5.48 kW
4.70 kW
COP Tj = +7°C
7.22
5.20
Cdh Tj = +7 °C
0.980
0.980
Pdh Tj = 12°C
4.38 kW
4.41 kW
COP Tj = 12°C
9.59
8.35
Cdh Tj = +12 °C
0.960
0.970
Pdh Tj = Tbiv
13.23 kW
11.46 kW
COP Tj = Tbiv
2.83
2.21
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
10.49 kW
8.12 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.65
1.83
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
60 °C
60 °C
Poff
17 W
17 W
PTO
17 W
17 W
PSB
17 W
17 W
PCK
38 W
38 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
4.51 kW
4.88 kW
Annual energy consumption Qhe
6514 kWh
7384 kWh