0,880 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
5.00 kW
5.00 kW
El input
0.97 kW
1.64 kW
COP
5.15
3.04
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
52 dB(A)
52 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
200 %
143 %
Prated
5.80 kW
5.50 kW
SCOP
5.07
3.65
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
5.10 kW
4.90 kW
COP Tj = -7°C
3.20
2.26
Cdh Tj = -7 °C
0.990
0.990
Pdh Tj = +2°C
3.10 kW
3.00 kW
COP Tj = +2°C
4.98
3.59
Cdh Tj = +2 °C
0.980
0.980
Pdh Tj = +7°C
2.00 kW
1.90 kW
COP Tj = +7°C
6.76
4.76
Cdh Tj = +7 °C
0.960
0.970
Pdh Tj = 12°C
2.50 kW
2.40 kW
COP Tj = 12°C
8.78
6.72
Cdh Tj = +12 °C
0.950
0.960
Pdh Tj = Tbiv
5.10 kW
4.90 kW
COP Tj = Tbiv
3.20
2.26
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.00 kW
4.70 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.84
2.00
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.990
0.990
WTOL
60 °C
60 °C
Poff
5 W
5 W
PTO
13 W
13 W
PSB
9 W
9 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.80 kW
0.80 kW
Annual energy consumption Qhe
2364 kWh
3110 kWh