0,750 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
9.69 kW
9.10 kW
El input
2.05 kW
2.85 kW
COP
4.72
3.20
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Cooling
EN 14511-2
+7°C/+12°C
El input
2.77 kW
Cooling capacity
8.57
EER
3.09
EN 14825
+7°C/+12°C
Pdesignc
8.57 kW
SEER
5.41
Pdc Tj = 35°C
8.57 kW
EER Tj = 35°C
3.09
Cdc Tj = 35 °C
1.000
Pdc Tj = 30°C
6.15 kW
EER Tj = 30°C
4.41
Cdc Tj = 30 °C
1.000
Pdc Tj = 25°C
3.72 kW
EER Tj = 25°C
6.06
Cdc Tj = 25 °C
1.000
Pdc Tj = 20°C
2.95 kW
EER Tj = 20°C
8.87
Cdc Tj = 20 °C
0.934
Poff
22 W
PTO
0 W
PSB
28 W
PCK
0 W
Annual energy consumption Qce
950 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
58 dB(A)
58 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
205 %
154 %
Prated
9.00 kW
8.90 kW
SCOP
5.19
3.93
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
8.00 kW
7.90 kW
COP Tj = -7°C
3.01
2.33
Cdh Tj = -7 °C
1.000
1.000
Pdh Tj = +2°C
4.60 kW
4.80 kW
COP Tj = +2°C
5.14
3.85
Cdh Tj = +2 °C
1.000
1.000
Pdh Tj = +7°C
3.10 kW
3.30 kW
COP Tj = +7°C
7.12
5.22
Cdh Tj = +7 °C
0.949
0.966
Pdh Tj = 12°C
3.20 kW
4.00 kW
COP Tj = 12°C
9.27
7.52
Cdh Tj = +12 °C
0.935
0.958
Pdh Tj = Tbiv
8.00 kW
7.90 kW
COP Tj = Tbiv
3.01
2.33
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.30 kW
7.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.64
2.04
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
68 °C
68 °C
Poff
22 W
22 W
PTO
22 W
22 W
PSB
22 W
22 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.70 kW
1.90 kW
Annual energy consumption Qhe
3581 kWh
4664 kWh