2,700 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
20.72 kW
19.68 kW
El input
4.63 kW
7.41 kW
COP
4.55
2.66
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
69 dB(A)
73 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
175 %
137 %
Prated
16.45 kW
17.04 kW
SCOP
4.46
3.51
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
14.55 kW
15.08 kW
COP Tj = -7°C
3.55
2.33
Cdh Tj = -7 °C
0.990
0.990
Pdh Tj = +2°C
8.79 kW
9.22 kW
COP Tj = +2°C
4.29
3.49
Cdh Tj = +2 °C
0.990
0.990
Pdh Tj = +7°C
8.74 kW
6.54 kW
COP Tj = +7°C
5.18
4.15
Cdh Tj = +7 °C
0.990
0.990
Pdh Tj = 12°C
9.93 kW
7.95 kW
COP Tj = 12°C
6.79
5.96
Cdh Tj = +12 °C
0.990
0.990
Pdh Tj = Tbiv
14.55 kW
15.08 kW
COP Tj = Tbiv
0.55
2.33
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
16.54 kW
13.81 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.00
2.15
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.990
0.990
WTOL
50 °C
50 °C
Poff
5 W
5 W
PTO
5 W
5 W
PSB
5 W
5 W
PCK
50 W
50 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
3.23 kW
Annual energy consumption Qhe
7622 kWh
10032 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
20.49 kW
21.59 kW
El input
5.85 kW
7.46 kW
COP
3.50
2.89
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
72 dB(A)
75 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
175 %
132 %
Prated
17.73 kW
18.46 kW
SCOP
4.46
3.38
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
15.69 kW
16.33 kW
COP Tj = -7°C
3.52
2.21
Cdh Tj = -7 °C
0.990
0.990
Pdh Tj = +2°C
9.58 kW
9.86 kW
COP Tj = +2°C
4.29
3.41
Cdh Tj = +2 °C
0.990
0.990
Pdh Tj = +7°C
8.82 kW
6.79 kW
COP Tj = +7°C
5.14
4.01
Cdh Tj = +7 °C
0.990
0.990
Pdh Tj = 12°C
10.45 kW
8.10 kW
COP Tj = 12°C
6.81
5.72
Cdh Tj = +12 °C
0.990
0.990
Pdh Tj = Tbiv
15.69 kW
16.33 kW
COP Tj = Tbiv
3.52
2.21
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
16.22 kW
14.22 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.84
2.09
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.990
0.990
WTOL
50 °C
50 °C
Poff
5 W
5 W
PTO
5 W
5 W
PSB
5 W
5 W
PCK
50 W
50 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.51 kW
4.24 kW
Annual energy consumption Qhe
8214 kWh
11269 kWh