Certificate holders

Subtype

Split Type EVI DC Inverter Air to Water Heat Pump- R32- 65

Certificate Holder
AOKOL Environment Technology Co., Ltd.
No 1, building 1, No.550, Kangzhuang South Road, Zhuangqiao Street, Jiangbei District, Ningbo City, Zhejiang Province,

China
Registration number
041-K081-02
Certification Body
BRE Global Limited
Subtype title
Split Type EVI DC Inverter Air to Water Heat Pump- R32- 65
Driving energy
Electricity
Heat Pump Type
Outdoor Air/Water
Refrigerant
R32
Mass of Refrigerant

2,300 kg

Certification Date
12.01.2024
Testing basis
Heat Pump KEYMARK certification Scheme rules v13
Generate PDF Export model CSV Download certificate
  • Number of models 1

Models

ASH-65CHW/FR
Configure model
Model name
ASH-65CHW/FR
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

14.46 kW

18.29 kW

El input

3.63 kW

7.27 kW

COP

3.98

2.52

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

42 dB(A)

46 dB(A)

Sound power level outdoor

69 dB(A)

71 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

180 %

133 %

Prated

14.73 kW

14.58 kW

SCOP

4.56

3.39

Tbiv

-7 °C

-7 °C

TOL

-25 °C

-25 °C

Pdh Tj = -7°C

13.03 kW

12.90 kW

COP Tj = -7°C

3.11

2.09

Cdh Tj = -7 °C

0.900

0.900

Pdh Tj = +2°C

8.15 kW

7.90 kW

COP Tj = +2°C

4.60

3.38

Cdh Tj = +2 °C

0.900

0.900

Pdh Tj = +7°C

5.29 kW

5.40 kW

COP Tj = +7°C

5.33

4.23

Cdh Tj = +7 °C

0.900

0.900

Pdh Tj = 12°C

6.28 kW

5.99 kW

COP Tj = 12°C

7.52

6.29

Cdh Tj = +12 °C

0.900

0.900

Pdh Tj = Tbiv

13.03 kW

12.90 kW

COP Tj = Tbiv

3.11

2.09

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

14.63 kW

14.50 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.77

2.04

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

60 °C

60 °C

Poff

10 W

10 W

PTO

36 W

36 W

PSB

10 W

10 W

PCK

50 W

50 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.10 kW

0.08 kW

Annual energy consumption Qhe

6670 kWh

8875 kWh