1,840 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
12.1 kW
12 kW
El input
2.42 kW
3.85 kW
COP
5
3.12
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
44 dB(A)
44 dB(A)
Sound power level outdoor
64 dB(A)
64 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
253 %
174 %
Prated
11.00 kW
12.00 kW
SCOP
6.41
4.44
Tbiv
7 °C
7 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
11.00 kW
12.00 kW
COP Tj = +2°C
3.61
2.27
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
7.10 kW
8.00 kW
COP Tj = +7°C
5.65
3.75
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
4.70 kW
4.30 kW
COP Tj = 12°C
8.34
5.95
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
7.10 kW
8.00 kW
COP Tj = Tbiv
5.65
3.75
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11.10 kW
12.10 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.61
2.27
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
65 °C
65 °C
Poff
14 W
14 W
PTO
24 W
24 W
PSB
14 W
14 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
2325 kWh
3762 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
44 dB(A)
44 dB(A)
Sound power level outdoor
64 dB(A)
64 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
163 %
119 %
Prated
11.00 kW
10.00 kW
SCOP
4.16
3.03
Tbiv
-15 °C
-15 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
7.20 kW
6.70 kW
COP Tj = -7°C
3.51
2.57
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
4.10 kW
3.90 kW
COP Tj = +2°C
5.05
3.69
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
3.20 kW
2.90 kW
COP Tj = +7°C
6.19
4.57
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
3.60 kW
3.20 kW
COP Tj = 12°C
8.19
6.59
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
9.20 kW
8.50 kW
COP Tj = Tbiv
2.59
1.85
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.10 kW
4.60 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.08
1.21
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
65 °C
65 °C
Poff
14 W
14 W
PTO
24 W
24 W
PSB
14 W
14 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
3.90 kW
5.40 kW
Annual energy consumption Qhe
6747 kWh
8500 kWh
Pdh Tj = -15°C (if TOL<-20°C)
9.20
8.50
COP Tj = -15°C (if TOL<-20°C)
2.59
1.85
Cdh Tj = -15 °C
0.900
0.900
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
44 dB(A)
44 dB(A)
Sound power level outdoor
64 dB(A)
64 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
185 %
136 %
Prated
12 kW
12 kW
SCOP
4.7
3.48
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
10.7 kW
10.7 kW
COP Tj = -7°C
2.92
2.11
Cdh Tj = -7 °C
0.9
0.9
Pdh Tj = +2°C
6.8 kW
6.8 kW
COP Tj = +2°C
4.51
3.43
Cdh Tj = +2 °C
0.9
0.9
Pdh Tj = +7°C
4.5 kW
4.4 kW
COP Tj = +7°C
6.36
4.57
Cdh Tj = +7 °C
0.9
0.9
Pdh Tj = 12°C
4 kW
3.7 kW
COP Tj = 12°C
8.45
6.19
Cdh Tj = +12 °C
0.9
0.9
Pdh Tj = Tbiv
10.7 kW
10.7 kW
COP Tj = Tbiv
2.92
2.11
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11.1 kW
10 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.7
1.82
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.9
0.9
WTOL
65 °C
65 °C
Poff
14 W
14 W
PTO
24 W
24 W
PSB
14 W
14 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.9 kW
2 kW
Annual energy consumption Qhe
5351 kWh
7213 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
14.5 kW
14 kW
El input
3.05 kW
4.65 kW
COP
4.75
3.01
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
44 dB(A)
44 dB(A)
Sound power level outdoor
66 dB(A)
66 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
249 %
170 %
Prated
12.00 kW
14.00 kW
SCOP
6.30
4.33
Tbiv
7 °C
7 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
12.00 kW
13.00 kW
COP Tj = +2°C
3.40
2.25
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
7.90 kW
9.00 kW
COP Tj = +7°C
5.60
3.61
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
4.10 kW
4.10 kW
COP Tj = 12°C
7.94
5.93
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
7.90 kW
9.00 kW
COP Tj = Tbiv
5.60
3.61
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
12.30 kW
13.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.40
2.25
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
65 °C
65 °C
Poff
14 W
14 W
PTO
24 W
24 W
PSB
14 W
14 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
1.00 kW
Annual energy consumption Qhe
2626 kWh
4324 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
44 dB(A)
44 dB(A)
Sound power level outdoor
66 dB(A)
66 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
156 %
117 %
Prated
13.00 kW
11.00 kW
SCOP
3.98
3.00
Tbiv
-15 °C
-15 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
8.20 kW
7.10 kW
COP Tj = -7°C
3.35
2.56
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
4.60 kW
4.20 kW
COP Tj = +2°C
4.71
3.62
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
3.30 kW
3.00 kW
COP Tj = +7°C
6.10
4.77
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
3.70 kW
3.60 kW
COP Tj = 12°C
8.00
6.40
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
10.60 kW
8.90 kW
COP Tj = Tbiv
2.61
1.82
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.80 kW
4.40 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.10
1.16
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
65 °C
65 °C
Poff
14 W
14 W
PTO
24 W
24 W
PSB
14 W
14 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
5.20 kW
6.60 kW
Annual energy consumption Qhe
8095 kWh
8982 kWh
Pdh Tj = -15°C (if TOL<-20°C)
10.60
8.90
COP Tj = -15°C (if TOL<-20°C)
2.61
1.82
Cdh Tj = -15 °C
0.900
0.900
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
44 dB(A)
44 dB(A)
Sound power level outdoor
66 dB(A)
66 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
180 %
131 %
Prated
14.00 kW
12.00 kW
SCOP
4.58
3.35
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
12.30 kW
10.90 kW
COP Tj = -7°C
2.70
2.02
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
7.50 kW
7.20 kW
COP Tj = +2°C
4.46
3.22
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
5.10 kW
4.60 kW
COP Tj = +7°C
6.38
4.53
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
4.50 kW
3.40 kW
COP Tj = 12°C
7.63
6.17
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
12.30 kW
10.90 kW
COP Tj = Tbiv
2.70
2.02
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
12.80 kW
10.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.64
1.78
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
65 °C
65 °C
Poff
14 W
14 W
PTO
24 W
24 W
PSB
14 W
14 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.20 kW
2.00 kW
Annual energy consumption Qhe
6270 kWh
7614 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
16 kW
16 kW
El input
3.54 kW
5.49 kW
COP
4.52
2.91
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
44 dB(A)
44 dB(A)
Sound power level outdoor
68 dB(A)
68 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
239 %
171 %
Prated
13.00 kW
14.00 kW
SCOP
6.05
4.35
Tbiv
7 °C
7 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
13.00 kW
13.20 kW
COP Tj = +2°C
3.34
2.31
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
8.50 kW
9.00 kW
COP Tj = +7°C
5.20
3.69
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
4.80 kW
4.10 kW
COP Tj = 12°C
7.95
5.80
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
8.50 kW
9.00 kW
COP Tj = Tbiv
5.20
3.69
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
13.20 kW
13.20 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.34
2.31
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
65 °C
65 °C
Poff
14 W
14 W
PTO
24 W
24 W
PSB
14 W
14 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.80 kW
Annual energy consumption Qhe
2936 kWh
4331 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
44 dB(A)
44 dB(A)
Sound power level outdoor
68 dB(A)
68 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
155 %
121 %
Prated
14 kW
12 kW
SCOP
3.95
3.1
Tbiv
-15 °C
-15 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
9.1 kW
7.7 kW
COP Tj = -7°C
3.3
2.61
Cdh Tj = -7 °C
0.9
0.9
Pdh Tj = +2°C
5 kW
4.5 kW
COP Tj = +2°C
4.88
3.79
Cdh Tj = +2 °C
0.9
0.9
Pdh Tj = +7°C
3.2 kW
3.1 kW
COP Tj = +7°C
5.75
4.87
Cdh Tj = +7 °C
0.9
0.9
Pdh Tj = 12°C
3.7 kW
3.6 kW
COP Tj = 12°C
7.59
6.38
Cdh Tj = +12 °C
0.9
0.9
Pdh Tj = Tbiv
11.3 kW
9.6 kW
COP Tj = Tbiv
2.28
1.84
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
9.8 kW
5.1 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
1.89
1.05
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.9
0.9
WTOL
65 °C
65 °C
Poff
14 W
14 W
PTO
24 W
24 W
PSB
14 W
14 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
4.2 kW
6.9 kW
Annual energy consumption Qhe
8667 kWh
9388 kWh
Pdh Tj = -15°C (if TOL<-20°C)
11.3
9.6
COP Tj = -15°C (if TOL<-20°C)
2.28
1.84
Cdh Tj = -15 °C
0.9
0.9
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
44 dB(A)
44 dB(A)
Sound power level outdoor
68 dB(A)
68 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
179 %
134 %
Prated
15 kW
13 kW
SCOP
4.55
3.43
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
13.5 kW
11.4 kW
COP Tj = -7°C
2.7
2.05
Cdh Tj = -7 °C
0.9
0.9
Pdh Tj = +2°C
8 kW
7.1 kW
COP Tj = +2°C
4.39
3.33
Cdh Tj = +2 °C
0.9
0.9
Pdh Tj = +7°C
5.4 kW
4.5 kW
COP Tj = +7°C
6.33
4.62
Cdh Tj = +7 °C
0.9
0.9
Pdh Tj = 12°C
4.5 kW
3.4 kW
COP Tj = 12°C
8.57
6.12
Cdh Tj = +12 °C
0.9
0.9
Pdh Tj = Tbiv
13.5 kW
11.4 kW
COP Tj = Tbiv
2.7
2.05
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
13.2 kW
11.2 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.37
1.77
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.9
0.9
WTOL
65 °C
65 °C
Poff
14 W
14 W
PTO
24 W
24 W
PSB
14 W
14 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.8 kW
1.8 kW
Annual energy consumption Qhe
6915 kWh
7765 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
12.1 kW
12 kW
El input
2.42 kW
3.85 kW
COP
5
3.12
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
44 dB(A)
44 dB(A)
Sound power level outdoor
64 dB(A)
64 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
253 %
174 %
Prated
11 kW
12 kW
SCOP
6.41
4.44
Tbiv
7 °C
7 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
11 kW
12 kW
COP Tj = +2°C
3.61
2.27
Cdh Tj = +2 °C
0.9
0.9
Pdh Tj = +7°C
7.1 kW
8 kW
COP Tj = +7°C
5.65
3.75
Cdh Tj = +7 °C
0.9
0.9
Pdh Tj = 12°C
4.7 kW
4.3 kW
COP Tj = 12°C
8.34
5.95
Cdh Tj = +12 °C
0.9
0.9
Pdh Tj = Tbiv
7.1 kW
8 kW
COP Tj = Tbiv
5.65
3.75
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11.1 kW
12.1 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.61
2.27
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.9
0.9
WTOL
65 °C
65 °C
Poff
14 W
14 W
PTO
24 W
24 W
PSB
14 W
14 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0 kW
0 kW
Annual energy consumption Qhe
2325 kWh
3762 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
44 dB(A)
44 dB(A)
Sound power level outdoor
64 dB(A)
64 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
163 %
119 %
Prated
11.00 kW
10.00 kW
SCOP
4.16
3.03
Tbiv
-15 °C
-15 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
7.20 kW
6.70 kW
COP Tj = -7°C
3.51
2.57
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
4.10 kW
3.90 kW
COP Tj = +2°C
5.05
3.69
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
3.20 kW
2.90 kW
COP Tj = +7°C
6.19
4.57
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
3.60 kW
3.20 kW
COP Tj = 12°C
8.19
6.59
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
9.20 kW
8.50 kW
COP Tj = Tbiv
2.59
1.85
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.10 kW
4.60 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.08
1.21
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
65 °C
65 °C
Poff
14 W
14 W
PTO
24 W
24 W
PSB
14 W
14 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
3.90 kW
5.40 kW
Annual energy consumption Qhe
6747 kWh
8500 kWh
Pdh Tj = -15°C (if TOL<-20°C)
9.20
8.50
COP Tj = -15°C (if TOL<-20°C)
2.59
1.85
Cdh Tj = -15 °C
0.900
0.900
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
44 dB(A)
44 dB(A)
Sound power level outdoor
64 dB(A)
64 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
185 %
136 %
Prated
12 kW
12 kW
SCOP
4.7
3.48
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
10.7 kW
10.7 kW
COP Tj = -7°C
2.92
2.11
Cdh Tj = -7 °C
0.9
0.9
Pdh Tj = +2°C
6.8 kW
6.8 kW
COP Tj = +2°C
4.51
3.43
Cdh Tj = +2 °C
0.9
0.9
Pdh Tj = +7°C
4.5 kW
4.4 kW
COP Tj = +7°C
6.36
4.57
Cdh Tj = +7 °C
0.9
0.9
Pdh Tj = 12°C
4 kW
3.7 kW
COP Tj = 12°C
8.45
6.19
Cdh Tj = +12 °C
0.9
0.9
Pdh Tj = Tbiv
10.7 kW
10.7 kW
COP Tj = Tbiv
2.92
2.11
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11.1 kW
10 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.7
1.82
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.9
0.9
WTOL
65 °C
65 °C
Poff
14 W
14 W
PTO
24 W
24 W
PSB
14 W
14 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.9 kW
2 kW
Annual energy consumption Qhe
5351 kWh
7213 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
14.5 kW
14 kW
El input
3.05 kW
4.65 kW
COP
4.75
3.01
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
44 dB(A)
44 dB(A)
Sound power level outdoor
66 dB(A)
66 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
249 %
170 %
Prated
12.00 kW
14.00 kW
SCOP
6.30
4.33
Tbiv
7 °C
7 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
12.00 kW
13.00 kW
COP Tj = +2°C
3.40
2.25
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
7.90 kW
9.00 kW
COP Tj = +7°C
5.60
3.61
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
4.10 kW
4.10 kW
COP Tj = 12°C
7.94
5.93
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
7.90 kW
9.00 kW
COP Tj = Tbiv
5.60
3.61
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
12.30 kW
13.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.40
2.25
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
65 °C
65 °C
Poff
14 W
14 W
PTO
24 W
24 W
PSB
14 W
14 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
1.00 kW
Annual energy consumption Qhe
2626 kWh
4324 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
44 dB(A)
44 dB(A)
Sound power level outdoor
66 dB(A)
66 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
156 %
117 %
Prated
13.00 kW
11.00 kW
SCOP
3.98
3.00
Tbiv
-15 °C
-15 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
8.20 kW
7.10 kW
COP Tj = -7°C
3.35
2.56
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
4.60 kW
4.20 kW
COP Tj = +2°C
4.71
3.62
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
3.30 kW
3.00 kW
COP Tj = +7°C
6.10
4.77
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
3.70 kW
3.60 kW
COP Tj = 12°C
8.00
6.40
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
10.60 kW
8.90 kW
COP Tj = Tbiv
2.61
1.82
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.80 kW
4.40 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.10
1.16
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
65 °C
65 °C
Poff
14 W
14 W
PTO
24 W
24 W
PSB
14 W
14 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
5.20 kW
6.60 kW
Annual energy consumption Qhe
8095 kWh
8982 kWh
Pdh Tj = -15°C (if TOL<-20°C)
10.60
8.90
COP Tj = -15°C (if TOL<-20°C)
2.61
1.82
Cdh Tj = -15 °C
0.900
0.900
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
44 dB(A)
44 dB(A)
Sound power level outdoor
66 dB(A)
66 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
180 %
131 %
Prated
14.00 kW
12.00 kW
SCOP
4.58
3.35
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
12.30 kW
10.90 kW
COP Tj = -7°C
2.70
2.02
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
7.50 kW
7.20 kW
COP Tj = +2°C
4.46
3.22
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
5.10 kW
4.60 kW
COP Tj = +7°C
6.38
4.53
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
4.50 kW
3.40 kW
COP Tj = 12°C
7.63
6.17
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
12.30 kW
10.90 kW
COP Tj = Tbiv
2.70
2.02
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
12.80 kW
10.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.64
1.78
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
65 °C
65 °C
Poff
14 W
14 W
PTO
24 W
24 W
PSB
14 W
14 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.20 kW
2.00 kW
Annual energy consumption Qhe
6270 kWh
7614 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
16 kW
16 kW
El input
3.54 kW
5.49 kW
COP
4.52
2.91
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
44 dB(A)
44 dB(A)
Sound power level outdoor
68 dB(A)
68 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
239 %
171 %
Prated
13 kW
14 kW
SCOP
6.05
4.35
Tbiv
7 °C
7 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
13 kW
13.2 kW
COP Tj = +2°C
3.34
2.31
Cdh Tj = +2 °C
0.9
0.9
Pdh Tj = +7°C
8.5 kW
9 kW
COP Tj = +7°C
5.2
3.69
Cdh Tj = +7 °C
0.9
0.9
Pdh Tj = 12°C
4.8 kW
4.1 kW
COP Tj = 12°C
7.95
5.8
Cdh Tj = +12 °C
0.9
0.9
Pdh Tj = Tbiv
8.5 kW
9 kW
COP Tj = Tbiv
5.2
3.69
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
13 kW
13.2 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.34
2.31
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.9
0.9
WTOL
65 °C
65 °C
Poff
14 W
14 W
PTO
24 W
24 W
PSB
14 W
14 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0 kW
0.8 kW
Annual energy consumption Qhe
2936 kWh
4331 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
44 dB(A)
44 dB(A)
Sound power level outdoor
68 dB(A)
68 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
155 %
121 %
Prated
14 kW
12 kW
SCOP
3.95
3.1
Tbiv
-15 °C
-15 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
9.1 kW
7.7 kW
COP Tj = -7°C
3.3
2.61
Cdh Tj = -7 °C
0.9
0.9
Pdh Tj = +2°C
5 kW
4.5 kW
COP Tj = +2°C
4.88
3.79
Cdh Tj = +2 °C
0.9
0.9
Pdh Tj = +7°C
3.2 kW
3.1 kW
COP Tj = +7°C
5.75
4.87
Cdh Tj = +7 °C
0.9
0.9
Pdh Tj = 12°C
3.7 kW
3.6 kW
COP Tj = 12°C
7.59
6.38
Cdh Tj = +12 °C
0.9
0.9
Pdh Tj = Tbiv
11.3 kW
9.6 kW
COP Tj = Tbiv
2.28
1.84
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
9.8 kW
5.1 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
1.89
1.05
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.9
0.9
WTOL
65 °C
65 °C
Poff
14 W
14 W
PTO
24 W
24 W
PSB
14 W
14 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
4.2 kW
6.9 kW
Annual energy consumption Qhe
8667 kWh
9388 kWh
Pdh Tj = -15°C (if TOL<-20°C)
11.3
9.6
COP Tj = -15°C (if TOL<-20°C)
2.28
1.84
Cdh Tj = -15 °C
0.9
0.9
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
44 dB(A)
44 dB(A)
Sound power level outdoor
68 dB(A)
68 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
179 %
134 %
Prated
15 kW
13 kW
SCOP
4.55
3.43
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
13.5 kW
11.4 kW
COP Tj = -7°C
2.7
2.05
Cdh Tj = -7 °C
0.9
0.9
Pdh Tj = +2°C
8 kW
7.1 kW
COP Tj = +2°C
4.39
3.33
Cdh Tj = +2 °C
0.9
0.9
Pdh Tj = +7°C
5.4 kW
4.5 kW
COP Tj = +7°C
6.33
4.62
Cdh Tj = +7 °C
0.9
0.9
Pdh Tj = 12°C
4.5 kW
3.4 kW
COP Tj = 12°C
8.57
6.12
Cdh Tj = +12 °C
0.9
0.9
Pdh Tj = Tbiv
13.5 kW
11.4 kW
COP Tj = Tbiv
2.7
2.05
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
13.2 kW
11.2 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.37
1.77
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.9
0.9
WTOL
65 °C
65 °C
Poff
14 W
14 W
PTO
24 W
24 W
PSB
14 W
14 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.8 kW
1.8 kW
Annual energy consumption Qhe
6915 kWh
7765 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
12.1 kW
12 kW
El input
2.42 kW
3.85 kW
COP
5
3.12
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
44 dB(A)
44 dB(A)
Sound power level outdoor
64 dB(A)
64 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
253 %
174 %
Prated
11 kW
12 kW
SCOP
6.41
4.44
Tbiv
7 °C
7 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
11 kW
12 kW
COP Tj = +2°C
3.61
2.27
Cdh Tj = +2 °C
0.9
0.9
Pdh Tj = +7°C
7.1 kW
8 kW
COP Tj = +7°C
5.65
3.75
Cdh Tj = +7 °C
0.9
0.9
Pdh Tj = 12°C
4.7 kW
4.3 kW
COP Tj = 12°C
8.34
5.95
Cdh Tj = +12 °C
0.9
0.9
Pdh Tj = Tbiv
7.1 kW
8 kW
COP Tj = Tbiv
5.65
3.75
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11.1 kW
12.1 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.61
2.27
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.9
0.9
WTOL
65 °C
65 °C
Poff
14 W
14 W
PTO
24 W
24 W
PSB
14 W
14 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0 kW
0 kW
Annual energy consumption Qhe
2325 kWh
3762 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
44 dB(A)
44 dB(A)
Sound power level outdoor
64 dB(A)
64 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
163 %
119 %
Prated
11.00 kW
10.00 kW
SCOP
4.16
3.03
Tbiv
-15 °C
-15 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
7.20 kW
6.70 kW
COP Tj = -7°C
3.51
2.57
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
4.10 kW
3.90 kW
COP Tj = +2°C
5.05
3.69
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
3.20 kW
2.90 kW
COP Tj = +7°C
6.19
4.57
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
3.60 kW
3.20 kW
COP Tj = 12°C
8.19
6.59
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
9.20 kW
8.50 kW
COP Tj = Tbiv
2.59
1.85
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.10 kW
4.60 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.08
1.21
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
65 °C
65 °C
Poff
14 W
14 W
PTO
24 W
24 W
PSB
14 W
14 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
3.90 kW
5.40 kW
Annual energy consumption Qhe
6747 kWh
8500 kWh
Pdh Tj = -15°C (if TOL<-20°C)
9.20
8.50
COP Tj = -15°C (if TOL<-20°C)
2.59
1.85
Cdh Tj = -15 °C
0.900
0.900
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
44 dB(A)
44 dB(A)
Sound power level outdoor
64 dB(A)
64 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
185 %
136 %
Prated
12 kW
12 kW
SCOP
4.7
3.48
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
10.7 kW
10.7 kW
COP Tj = -7°C
2.92
2.11
Cdh Tj = -7 °C
0.9
0.9
Pdh Tj = +2°C
6.8 kW
6.8 kW
COP Tj = +2°C
4.51
3.43
Cdh Tj = +2 °C
0.9
0.9
Pdh Tj = +7°C
4.5 kW
4.4 kW
COP Tj = +7°C
6.36
4.57
Cdh Tj = +7 °C
0.9
0.9
Pdh Tj = 12°C
4 kW
3.7 kW
COP Tj = 12°C
8.45
6.19
Cdh Tj = +12 °C
0.9
0.9
Pdh Tj = Tbiv
10.7 kW
10.7 kW
COP Tj = Tbiv
2.92
2.11
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11.1 kW
10 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.7
1.82
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.9
0.9
WTOL
65 °C
65 °C
Poff
14 W
14 W
PTO
24 W
24 W
PSB
14 W
14 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.9 kW
2 kW
Annual energy consumption Qhe
5351 kWh
7213 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
14.5 kW
14 kW
El input
3.05 kW
4.65 kW
COP
4.75
3.01
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
44 dB(A)
44 dB(A)
Sound power level outdoor
66 dB(A)
66 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
249 %
170 %
Prated
12.00 kW
14.00 kW
SCOP
6.30
4.33
Tbiv
7 °C
7 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
12.00 kW
13.00 kW
COP Tj = +2°C
3.40
2.25
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
7.90 kW
9.00 kW
COP Tj = +7°C
5.60
3.61
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
4.10 kW
4.10 kW
COP Tj = 12°C
7.94
5.93
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
7.90 kW
9.00 kW
COP Tj = Tbiv
5.60
3.61
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
12.30 kW
13.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.40
2.25
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
65 °C
65 °C
Poff
14 W
14 W
PTO
24 W
24 W
PSB
14 W
14 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
1.00 kW
Annual energy consumption Qhe
2626 kWh
4324 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
44 dB(A)
44 dB(A)
Sound power level outdoor
66 dB(A)
66 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
156 %
117 %
Prated
13.00 kW
11.00 kW
SCOP
3.98
3.00
Tbiv
-15 °C
-15 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
8.20 kW
7.10 kW
COP Tj = -7°C
3.35
2.56
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
4.60 kW
4.20 kW
COP Tj = +2°C
4.71
3.62
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
3.30 kW
3.00 kW
COP Tj = +7°C
6.10
4.77
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
3.70 kW
3.60 kW
COP Tj = 12°C
8.00
6.40
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
10.60 kW
8.90 kW
COP Tj = Tbiv
2.61
1.82
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.80 kW
4.40 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.10
1.16
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
65 °C
65 °C
Poff
14 W
14 W
PTO
24 W
24 W
PSB
14 W
14 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
5.20 kW
6.60 kW
Annual energy consumption Qhe
8095 kWh
8982 kWh
Pdh Tj = -15°C (if TOL<-20°C)
10.60
8.90
COP Tj = -15°C (if TOL<-20°C)
2.61
1.82
Cdh Tj = -15 °C
0.900
0.900
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
44 dB(A)
44 dB(A)
Sound power level outdoor
66 dB(A)
66 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
180 %
131 %
Prated
14.00 kW
12.00 kW
SCOP
4.58
3.35
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
12.30 kW
10.90 kW
COP Tj = -7°C
2.70
2.02
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
7.50 kW
7.20 kW
COP Tj = +2°C
4.46
3.22
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
5.10 kW
4.60 kW
COP Tj = +7°C
6.38
4.53
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
4.50 kW
3.40 kW
COP Tj = 12°C
7.63
6.17
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
12.30 kW
10.90 kW
COP Tj = Tbiv
2.70
2.02
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
12.80 kW
10.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.64
1.78
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
65 °C
65 °C
Poff
14 W
14 W
PTO
24 W
24 W
PSB
14 W
14 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.20 kW
2.00 kW
Annual energy consumption Qhe
6270 kWh
7614 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
16 kW
16 kW
El input
3.54 kW
5.49 kW
COP
4.52
2.91
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
44 dB(A)
44 dB(A)
Sound power level outdoor
68 dB(A)
68 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
239 %
171 %
Prated
13 kW
14 kW
SCOP
6.05
4.35
Tbiv
7 °C
7 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
13 kW
13.2 kW
COP Tj = +2°C
3.34
2.31
Cdh Tj = +2 °C
0.9
0.9
Pdh Tj = +7°C
8.5 kW
9 kW
COP Tj = +7°C
5.2
3.69
Cdh Tj = +7 °C
0.9
0.9
Pdh Tj = 12°C
4.8 kW
4.1 kW
COP Tj = 12°C
7.95
5.8
Cdh Tj = +12 °C
0.9
0.9
Pdh Tj = Tbiv
8.5 kW
9 kW
COP Tj = Tbiv
5.2
3.69
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
13 kW
13.2 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.34
2.31
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.9
0.9
WTOL
65 °C
65 °C
Poff
14 W
14 W
PTO
24 W
24 W
PSB
14 W
14 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0 kW
0.8 kW
Annual energy consumption Qhe
2936 kWh
4331 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
44 dB(A)
44 dB(A)
Sound power level outdoor
68 dB(A)
68 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
155 %
121 %
Prated
14 kW
12 kW
SCOP
3.95
3.1
Tbiv
-15 °C
-15 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
9.1 kW
7.7 kW
COP Tj = -7°C
3.3
2.61
Cdh Tj = -7 °C
0.9
0.9
Pdh Tj = +2°C
5 kW
4.5 kW
COP Tj = +2°C
4.88
3.79
Cdh Tj = +2 °C
0.9
0.9
Pdh Tj = +7°C
3.2 kW
3.1 kW
COP Tj = +7°C
5.75
4.87
Cdh Tj = +7 °C
0.9
0.9
Pdh Tj = 12°C
3.7 kW
3.6 kW
COP Tj = 12°C
7.59
6.38
Cdh Tj = +12 °C
0.9
0.9
Pdh Tj = Tbiv
11.3 kW
9.6 kW
COP Tj = Tbiv
2.28
1.84
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
9.8 kW
5.1 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
1.89
1.05
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.9
0.9
WTOL
65 °C
65 °C
Poff
14 W
14 W
PTO
24 W
24 W
PSB
14 W
14 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
4.2 kW
6.9 kW
Annual energy consumption Qhe
8667 kWh
9388 kWh
Pdh Tj = -15°C (if TOL<-20°C)
11.3
9.6
COP Tj = -15°C (if TOL<-20°C)
2.28
1.84
Cdh Tj = -15 °C
0.9
0.9
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
44 dB(A)
44 dB(A)
Sound power level outdoor
68 dB(A)
68 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
179 %
134 %
Prated
15 kW
13 kW
SCOP
4.55
3.43
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
13.5 kW
11.4 kW
COP Tj = -7°C
2.7
2.05
Cdh Tj = -7 °C
0.9
0.9
Pdh Tj = +2°C
8 kW
7.1 kW
COP Tj = +2°C
4.39
3.33
Cdh Tj = +2 °C
0.9
0.9
Pdh Tj = +7°C
5.4 kW
4.5 kW
COP Tj = +7°C
6.33
4.62
Cdh Tj = +7 °C
0.9
0.9
Pdh Tj = 12°C
4.5 kW
3.4 kW
COP Tj = 12°C
8.57
6.12
Cdh Tj = +12 °C
0.9
0.9
Pdh Tj = Tbiv
13.5 kW
11.4 kW
COP Tj = Tbiv
2.7
2.05
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
13.2 kW
11.2 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.37
1.77
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.9
0.9
WTOL
65 °C
65 °C
Poff
14 W
14 W
PTO
24 W
24 W
PSB
14 W
14 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.8 kW
1.8 kW
Annual energy consumption Qhe
6915 kWh
7765 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
12.1 kW
12 kW
El input
2.42 kW
3.85 kW
COP
5
3.12
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
44 dB(A)
44 dB(A)
Sound power level outdoor
64 dB(A)
64 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
253 %
174 %
Prated
11 kW
12 kW
SCOP
6.41
4.44
Tbiv
7 °C
7 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
11 kW
12 kW
COP Tj = +2°C
3.61
2.27
Cdh Tj = +2 °C
0.9
0.9
Pdh Tj = +7°C
7.1 kW
8 kW
COP Tj = +7°C
5.65
3.75
Cdh Tj = +7 °C
0.9
0.9
Pdh Tj = 12°C
4.7 kW
4.3 kW
COP Tj = 12°C
8.34
5.95
Cdh Tj = +12 °C
0.9
0.9
Pdh Tj = Tbiv
7.1 kW
8 kW
COP Tj = Tbiv
5.65
3.75
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11.1 kW
12.1 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.61
2.27
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.9
0.9
WTOL
65 °C
65 °C
Poff
14 W
14 W
PTO
24 W
24 W
PSB
14 W
14 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0 kW
0 kW
Annual energy consumption Qhe
2325 kWh
3762 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
44 dB(A)
44 dB(A)
Sound power level outdoor
64 dB(A)
64 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
163 %
119 %
Prated
11.00 kW
10.00 kW
SCOP
4.16
3.03
Tbiv
-15 °C
-15 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
7.20 kW
6.70 kW
COP Tj = -7°C
3.51
2.57
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
4.10 kW
3.90 kW
COP Tj = +2°C
5.05
3.69
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
3.20 kW
2.90 kW
COP Tj = +7°C
6.19
4.57
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
3.60 kW
3.20 kW
COP Tj = 12°C
8.19
6.59
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
9.20 kW
8.50 kW
COP Tj = Tbiv
2.59
1.85
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.10 kW
4.60 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.08
1.21
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
65 °C
65 °C
Poff
14 W
14 W
PTO
24 W
24 W
PSB
14 W
14 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
3.90 kW
5.40 kW
Annual energy consumption Qhe
6747 kWh
8500 kWh
Pdh Tj = -15°C (if TOL<-20°C)
9.20
8.50
COP Tj = -15°C (if TOL<-20°C)
2.59
1.85
Cdh Tj = -15 °C
0.900
0.900
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
44 dB(A)
44 dB(A)
Sound power level outdoor
64 dB(A)
64 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
185 %
136 %
Prated
12 kW
12 kW
SCOP
4.7
3.48
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
10.7 kW
10.7 kW
COP Tj = -7°C
2.92
2.11
Cdh Tj = -7 °C
0.9
0.9
Pdh Tj = +2°C
6.8 kW
6.8 kW
COP Tj = +2°C
4.51
3.43
Cdh Tj = +2 °C
0.9
0.9
Pdh Tj = +7°C
4.5 kW
4.4 kW
COP Tj = +7°C
6.36
4.57
Cdh Tj = +7 °C
0.9
0.9
Pdh Tj = 12°C
4 kW
3.7 kW
COP Tj = 12°C
8.45
6.19
Cdh Tj = +12 °C
0.9
0.9
Pdh Tj = Tbiv
10.7 kW
10.7 kW
COP Tj = Tbiv
2.92
2.11
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11.1 kW
10 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.7
1.82
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.9
0.9
WTOL
65 °C
65 °C
Poff
14 W
14 W
PTO
24 W
24 W
PSB
14 W
14 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.9 kW
2 kW
Annual energy consumption Qhe
5351 kWh
7213 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
14.5 kW
14 kW
El input
3.05 kW
4.65 kW
COP
4.75
3.01
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
44 dB(A)
44 dB(A)
Sound power level outdoor
66 dB(A)
66 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
249 %
170 %
Prated
12.00 kW
14.00 kW
SCOP
6.30
4.33
Tbiv
7 °C
7 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
12.00 kW
13.00 kW
COP Tj = +2°C
3.40
2.25
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
7.90 kW
9.00 kW
COP Tj = +7°C
5.60
3.61
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
4.10 kW
4.10 kW
COP Tj = 12°C
7.94
5.93
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
7.90 kW
9.00 kW
COP Tj = Tbiv
5.60
3.61
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
12.30 kW
13.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.40
2.25
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
65 °C
65 °C
Poff
14 W
14 W
PTO
24 W
24 W
PSB
14 W
14 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
1.00 kW
Annual energy consumption Qhe
2626 kWh
4324 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
44 dB(A)
44 dB(A)
Sound power level outdoor
66 dB(A)
66 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
156 %
117 %
Prated
13.00 kW
11.00 kW
SCOP
3.98
3.00
Tbiv
-15 °C
-15 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
8.20 kW
7.10 kW
COP Tj = -7°C
3.35
2.56
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
4.60 kW
4.20 kW
COP Tj = +2°C
4.71
3.62
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
3.30 kW
3.00 kW
COP Tj = +7°C
6.10
4.77
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
3.70 kW
3.60 kW
COP Tj = 12°C
8.00
6.40
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
10.60 kW
8.90 kW
COP Tj = Tbiv
2.61
1.82
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.80 kW
4.40 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.10
1.16
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
65 °C
65 °C
Poff
14 W
14 W
PTO
24 W
24 W
PSB
14 W
14 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
5.20 kW
6.60 kW
Annual energy consumption Qhe
8095 kWh
8982 kWh
Pdh Tj = -15°C (if TOL<-20°C)
10.60
8.90
COP Tj = -15°C (if TOL<-20°C)
2.61
1.82
Cdh Tj = -15 °C
0.900
0.900
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
44 dB(A)
44 dB(A)
Sound power level outdoor
66 dB(A)
66 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
180 %
131 %
Prated
14.00 kW
12.00 kW
SCOP
4.65
3.35
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
12.30 kW
10.90 kW
COP Tj = -7°C
2.70
2.02
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
7.50 kW
7.20 kW
COP Tj = +2°C
4.46
3.22
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
5.10 kW
4.60 kW
COP Tj = +7°C
6.38
4.53
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
4.50 kW
3.40 kW
COP Tj = 12°C
7.63
6.17
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
12.30 kW
10.90 kW
COP Tj = Tbiv
2.70
2.02
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
12.80 kW
10.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.64
1.78
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
65 °C
65 °C
Poff
14 W
14 W
PTO
24 W
24 W
PSB
14 W
14 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.20 kW
2.00 kW
Annual energy consumption Qhe
6270 kWh
7614 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
16 kW
16 kW
El input
3.54 kW
5.49 kW
COP
4.52
2.91
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
44 dB(A)
44 dB(A)
Sound power level outdoor
68 dB(A)
68 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
239 %
171 %
Prated
13 kW
14 kW
SCOP
6.05
4.35
Tbiv
7 °C
7 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
13 kW
13.2 kW
COP Tj = +2°C
3.34
2.31
Cdh Tj = +2 °C
0.9
0.9
Pdh Tj = +7°C
8.5 kW
9 kW
COP Tj = +7°C
5.2
3.69
Cdh Tj = +7 °C
0.9
0.9
Pdh Tj = 12°C
4.8 kW
4.1 kW
COP Tj = 12°C
7.95
5.8
Cdh Tj = +12 °C
0.9
0.9
Pdh Tj = Tbiv
8.5 kW
9 kW
COP Tj = Tbiv
5.2
3.69
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
13 kW
13.2 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.34
2.31
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.9
0.9
WTOL
65 °C
65 °C
Poff
14 W
14 W
PTO
24 W
24 W
PSB
14 W
14 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0 kW
0.8 kW
Annual energy consumption Qhe
2936 kWh
4331 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
44 dB(A)
44 dB(A)
Sound power level outdoor
68 dB(A)
68 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
155 %
121 %
Prated
14 kW
12 kW
SCOP
3.95
3.1
Tbiv
-15 °C
-15 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
9.1 kW
7.7 kW
COP Tj = -7°C
3.3
2.61
Cdh Tj = -7 °C
0.9
0.9
Pdh Tj = +2°C
5 kW
4.5 kW
COP Tj = +2°C
4.88
3.79
Cdh Tj = +2 °C
0.9
0.9
Pdh Tj = +7°C
3.2 kW
3.1 kW
COP Tj = +7°C
5.75
4.87
Cdh Tj = +7 °C
0.9
0.9
Pdh Tj = 12°C
3.7 kW
3.6 kW
COP Tj = 12°C
7.59
6.38
Cdh Tj = +12 °C
0.9
0.9
Pdh Tj = Tbiv
11.3 kW
9.6 kW
COP Tj = Tbiv
2.28
1.84
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
9.8 kW
5.1 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
1.89
1.05
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.9
0.9
WTOL
65 °C
65 °C
Poff
14 W
14 W
PTO
24 W
24 W
PSB
14 W
14 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
4.2 kW
6.9 kW
Annual energy consumption Qhe
8667 kWh
9388 kWh
Pdh Tj = -15°C (if TOL<-20°C)
11.3
9.6
COP Tj = -15°C (if TOL<-20°C)
2.28
1.84
Cdh Tj = -15 °C
0.9
0.9
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
44 dB(A)
44 dB(A)
Sound power level outdoor
68 dB(A)
68 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
179 %
134 %
Prated
15 kW
13 kW
SCOP
4.55
3.43
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
13.5 kW
11.4 kW
COP Tj = -7°C
2.7
2.05
Cdh Tj = -7 °C
0.9
0.9
Pdh Tj = +2°C
8 kW
7.1 kW
COP Tj = +2°C
4.39
3.33
Cdh Tj = +2 °C
0.9
0.9
Pdh Tj = +7°C
5.4 kW
4.5 kW
COP Tj = +7°C
6.33
4.62
Cdh Tj = +7 °C
0.9
0.9
Pdh Tj = 12°C
4.5 kW
3.4 kW
COP Tj = 12°C
8.57
6.12
Cdh Tj = +12 °C
0.9
0.9
Pdh Tj = Tbiv
13.5 kW
11.4 kW
COP Tj = Tbiv
2.7
2.05
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
13.2 kW
11.2 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.37
1.77
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.9
0.9
WTOL
65 °C
65 °C
Poff
14 W
14 W
PTO
24 W
24 W
PSB
14 W
14 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.8 kW
1.8 kW
Annual energy consumption Qhe
6915 kWh
7765 kWh