1,400 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
18.36 kW
18.16 kW
El input
4.09 kW
6.01 kW
COP
4.49
3.02
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
70 dB(A)
72 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
189 %
146 %
Prated
16.27 kW
16.44 kW
SCOP
4.81
3.72
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
14.39 kW
14.54 kW
COP Tj = -7°C
3.01
2.48
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
8.89 kW
8.91 kW
COP Tj = +2°C
4.70
3.52
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
5.64 kW
5.73 kW
COP Tj = +7°C
6.21
4.84
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
5.88 kW
5.52 kW
COP Tj = 12°C
8.74
6.85
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
14.39 kW
14.54 kW
COP Tj = Tbiv
3.01
2.48
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
15.98 kW
15.34 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.59
2.01
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
64 °C
64 °C
Poff
14 W
14 W
PTO
29 W
29 W
PSB
14 W
14 W
PCK
42 W
42 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.29 kW
1.11 kW
Annual energy consumption Qhe
6987 kWh
9142 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
18.42 kW
18.30 kW
El input
4.01 kW
5.94 kW
COP
4.60
3.08
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
70 dB(A)
72 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
189 %
145 %
Prated
16.34 kW
16.40 kW
SCOP
4.79
3.71
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
14.46 kW
14.51 kW
COP Tj = -7°C
3.10
2.48
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
9.08 kW
9.01 kW
COP Tj = +2°C
4.71
3.50
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
5.69 kW
5.74 kW
COP Tj = +7°C
6.04
4.82
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
5.70 kW
5.47 kW
COP Tj = 12°C
7.91
6.91
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
14.46 kW
14.51 kW
COP Tj = Tbiv
3.10
2.48
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
16.34 kW
15.20 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.78
2.16
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
65 °C
65 °C
Poff
14 W
14 W
PTO
29 W
29 W
PSB
14 W
14 W
PCK
43 W
43 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
1.20 kW
Annual energy consumption Qhe
7052 kWh
9145 kWh