1,800 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
12 kW
7 kW
El input
2.53 kW
2.59 kW
COP
4.75
2.7
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Cooling
EN 14511-2
+7°C/+12°C
+18°C/+23°C
El input
4.81 kW
3.87 kW
Cooling capacity
12.5
14
EER
2.6
3.62
EN 14825
+7°C/+12°C
+18°C/+23°C
Pdesignc
12.5 kW
14 kW
SEER
3.6
4.88
Pdc Tj = 35°C
12.5 kW
14 kW
EER Tj = 35°C
2.6
3.62
Cdc Tj = 35 °C
0.997
0.996
Pdc Tj = 30°C
9.21 kW
10.32 kW
EER Tj = 30°C
3.47
4.93
Cdc Tj = 30 °C
0.994
0.993
Pdc Tj = 25°C
6 kW
6.63 kW
EER Tj = 25°C
4.2
5.1
Cdc Tj = 25 °C
0.99
0.988
Pdc Tj = 20°C
3.7 kW
4.7 kW
EER Tj = 20°C
3.49
5.4
Cdc Tj = 20 °C
0.986
0.983
Poff
15 W
15 W
PTO
15 W
15 W
PSB
15 W
15 W
PCK
0 W
0 W
Annual energy consumption Qce
2081 kWh
1720 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
58 dB(A)
58 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
175 %
134 %
Prated
14 kW
14 kW
SCOP
4.46
3.43
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
12.4 kW
12.4 kW
COP Tj = -7°C
2.7
1.98
Cdh Tj = -7 °C
0.997
0.998
Pdh Tj = +2°C
7.6 kW
7.5 kW
COP Tj = +2°C
4.51
3.4
Cdh Tj = +2 °C
0.991
0.993
Pdh Tj = +7°C
6.4 kW
6.3 kW
COP Tj = +7°C
5.91
4.61
Cdh Tj = +7 °C
0.986
0.989
Pdh Tj = 12°C
4.1 kW
3.9 kW
COP Tj = 12°C
7.03
6.28
Cdh Tj = +12 °C
0.974
0.976
Pdh Tj = Tbiv
12.4 kW
12.4 kW
COP Tj = Tbiv
2.7
1.98
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11 kW
11 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.4
1.75
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.997
0.998
WTOL
60 °C
60 °C
Poff
15 W
15 W
PTO
15 W
15 W
PSB
15 W
15 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
3 kW
3 kW
Annual energy consumption Qhe
6483 kWh
8438 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
114 %
COP
2.76
Heating up time
2:40 h:min
Standby power input
50 W
Reference hot water temperature
52.5 °C
Mixed water at 40°C
417 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
12 kW
7 kW
El input
2.53 kW
2.59 kW
COP
4.75
2.7
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Cooling
EN 14511-2
+7°C/+12°C
+18°C/+23°C
El input
4.81 kW
3.87 kW
Cooling capacity
12.5
14
EER
2.6
3.62
EN 14825
+7°C/+12°C
+18°C/+23°C
Pdesignc
12.5 kW
14 kW
SEER
3.58
4.84
Pdc Tj = 35°C
12.5 kW
14 kW
EER Tj = 35°C
2.6
3.62
Cdc Tj = 35 °C
0.995
0.994
Pdc Tj = 30°C
9.21 kW
10.32 kW
EER Tj = 30°C
3.47
4.93
Cdc Tj = 30 °C
0.992
0.989
Pdc Tj = 25°C
6 kW
6.63 kW
EER Tj = 25°C
4.2
5.1
Cdc Tj = 25 °C
0.985
0.983
Pdc Tj = 20°C
3.7 kW
4.7 kW
EER Tj = 20°C
3.49
5.4
Cdc Tj = 20 °C
0.979
0.975
Poff
22 W
22 W
PTO
22 W
22 W
PSB
22 W
22 W
PCK
0 W
0 W
Annual energy consumption Qce
2097 kWh
1736 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
58 dB(A)
58 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
175 %
134 %
Prated
14 kW
14 kW
SCOP
4.44
3.41
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
12.4 kW
12.4 kW
COP Tj = -7°C
2.7
1.98
Cdh Tj = -7 °C
0.995
0.996
Pdh Tj = +2°C
7.6 kW
7.5 kW
COP Tj = +2°C
4.51
3.4
Cdh Tj = +2 °C
0.987
0.99
Pdh Tj = +7°C
6.4 kW
6.3 kW
COP Tj = +7°C
5.91
4.61
Cdh Tj = +7 °C
0.98
0.984
Pdh Tj = 12°C
4.1 kW
3.9 kW
COP Tj = 12°C
7.03
6.28
Cdh Tj = +12 °C
0.962
0.965
Pdh Tj = Tbiv
12.4 kW
12.4 kW
COP Tj = Tbiv
2.7
1.98
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11 kW
11 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.4
1.75
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.995
0.997
WTOL
60 °C
60 °C
Poff
22 W
22 W
PTO
22 W
22 W
PSB
22 W
22 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
3 kW
3 kW
Annual energy consumption Qhe
6517 kWh
8473 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
114 %
COP
2.76
Heating up time
2:40 h:min
Standby power input
50 W
Reference hot water temperature
52.5 °C
Mixed water at 40°C
417 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
12 kW
7 kW
El input
2.53 kW
2.59 kW
COP
4.75
2.7
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Cooling
EN 14511-2
+7°C/+12°C
+18°C/+23°C
El input
4.81 kW
3.87 kW
Cooling capacity
12.5
14
EER
2.6
3.62
EN 14825
+7°C/+12°C
+18°C/+23°C
Pdesignc
12.5 kW
14 kW
SEER
3.6
4.88
Pdc Tj = 35°C
12.5 kW
14 kW
EER Tj = 35°C
2.6
3.62
Cdc Tj = 35 °C
0.997
0.996
Pdc Tj = 30°C
9.21 kW
10.32 kW
EER Tj = 30°C
3.47
4.93
Cdc Tj = 30 °C
0.994
0.993
Pdc Tj = 25°C
6 kW
6.63 kW
EER Tj = 25°C
4.2
5.1
Cdc Tj = 25 °C
0.99
0.988
Pdc Tj = 20°C
3.7 kW
4.7 kW
EER Tj = 20°C
3.49
5.4
Cdc Tj = 20 °C
0.986
0.983
Poff
15 W
15 W
PTO
15 W
15 W
PSB
15 W
15 W
PCK
0 W
0 W
Annual energy consumption Qce
2081 kWh
1720 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
58 dB(A)
58 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
177 %
135 %
Prated
14 kW
14 kW
SCOP
4.5
3.45
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
12.4 kW
12.4 kW
COP Tj = -7°C
2.7
1.98
Cdh Tj = -7 °C
0.997
0.998
Pdh Tj = +2°C
7.6 kW
7.5 kW
COP Tj = +2°C
4.51
3.4
Cdh Tj = +2 °C
0.991
0.993
Pdh Tj = +7°C
6.4 kW
6.3 kW
COP Tj = +7°C
5.91
4.61
Cdh Tj = +7 °C
0.986
0.989
Pdh Tj = 12°C
4.1 kW
3.9 kW
COP Tj = 12°C
7.03
6.28
Cdh Tj = +12 °C
0.974
0.976
Pdh Tj = Tbiv
12.4 kW
12.4 kW
COP Tj = Tbiv
2.7
1.98
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11 kW
11 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.4
1.75
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.997
0.998
WTOL
60 °C
60 °C
Poff
15 W
15 W
PTO
15 W
15 W
PSB
15 W
15 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
3 kW
3 kW
Annual energy consumption Qhe
6428 kWh
8383 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
114 %
COP
2.76
Heating up time
2:40 h:min
Standby power input
50 W
Reference hot water temperature
52.5 °C
Mixed water at 40°C
417 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
12 kW
7 kW
El input
2.53 kW
2.59 kW
COP
4.75
2.7
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Cooling
EN 14511-2
+7°C/+12°C
+18°C/+23°C
El input
4.81 kW
3.87 kW
Cooling capacity
12.5
14
EER
2.6
3.62
EN 14825
+7°C/+12°C
+18°C/+23°C
Pdesignc
12.5 kW
14 kW
SEER
3.58
4.84
Pdc Tj = 35°C
12.5 kW
14 kW
EER Tj = 35°C
2.6
3.62
Cdc Tj = 35 °C
0.995
0.994
Pdc Tj = 30°C
9.21 kW
10.32 kW
EER Tj = 30°C
3.47
4.93
Cdc Tj = 30 °C
0.992
0.989
Pdc Tj = 25°C
6 kW
6.63 kW
EER Tj = 25°C
4.2
5.1
Cdc Tj = 25 °C
0.985
0.983
Pdc Tj = 20°C
3.7 kW
4.7 kW
EER Tj = 20°C
3.49
5.4
Cdc Tj = 20 °C
0.979
0.975
Poff
22 W
22 W
PTO
22 W
22 W
PSB
22 W
22 W
PCK
0 W
0 W
Annual energy consumption Qce
2097 kWh
1736 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
58 dB(A)
58 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
177 %
135 %
Prated
14 kW
14 kW
SCOP
4.49
3.45
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
12.4 kW
12.4 kW
COP Tj = -7°C
2.7
1.98
Cdh Tj = -7 °C
0.995
0.996
Pdh Tj = +2°C
7.6 kW
7.5 kW
COP Tj = +2°C
4.51
3.4
Cdh Tj = +2 °C
0.987
0.99
Pdh Tj = +7°C
6.4 kW
6.3 kW
COP Tj = +7°C
5.91
4.61
Cdh Tj = +7 °C
0.98
0.984
Pdh Tj = 12°C
4.1 kW
3.9 kW
COP Tj = 12°C
7.03
6.28
Cdh Tj = +12 °C
0.962
0.965
Pdh Tj = Tbiv
12.4 kW
12.4 kW
COP Tj = Tbiv
2.7
1.98
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11 kW
11 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.4
1.75
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.995
0.997
WTOL
60 °C
60 °C
Poff
22 W
22 W
PTO
22 W
22 W
PSB
22 W
22 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
3 kW
3 kW
Annual energy consumption Qhe
6437 kWh
8392 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
114 %
COP
2.76
Heating up time
2:40 h:min
Standby power input
50 W
Reference hot water temperature
52.5 °C
Mixed water at 40°C
417 l