Certificate holders

Subtype

Ecodan Eco Inverter 6/8/10H+200D

Certificate Holder
Mitsubishi Electric Air Conditioning Systems Europe LTD
Nettlehill Road, Houston Industrial Estate
EH54 5EQ Livingston
United Kingdom
Registration number
037-0089-22 / rev. 1
Certification Body
SZU - Strojirensky zkusebni ustav (Engineering Test Institute, Public Enterprise)
Subtype title
Ecodan Eco Inverter 6/8/10H+200D
Driving energy
Electricity
Heat Pump Type
Outdoor Air/Water
Refrigerant
R32
Mass of Refrigerant

1,100 kg

Certification Date
02.11.2022
Testing basis
HP Keymark scheme rules rev. no. 11
Generate PDF Export model CSV Download certificate
  • Number of models 45

Models

SUZ-SHWM60VAH + EHST20D-M*D
Configure model
Model name
SUZ-SHWM60VAH + EHST20D-M*D
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

5 kW

5 kW

El input

1.01 kW

1.7 kW

COP

4.95

2.94

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

57 dB(A)

57 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

175 %

126 %

Prated

6.1 kW

6 kW

SCOP

4.44

3.22

Tbiv

-10 °C

-7 °C

TOL

-25 °C

-25 °C

Pdh Tj = -7°C

5.4 kW

5.31 kW

COP Tj = -7°C

2.78

1.85

Cdh Tj = -7 °C

0.992

0.995

Pdh Tj = +2°C

4.1 kW

3.7 kW

COP Tj = +2°C

4.43

3.13

Cdh Tj = +2 °C

0.984

0.987

Pdh Tj = +7°C

3.4 kW

3.1 kW

COP Tj = +7°C

6.27

4.66

Cdh Tj = +7 °C

0.972

0.977

Pdh Tj = 12°C

3.7 kW

3.9 kW

COP Tj = 12°C

7.11

6.53

Cdh Tj = +12 °C

0.971

0.975

Pdh Tj = Tbiv

6.1 kW

5.31 kW

COP Tj = Tbiv

2.26

1.85

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

6.1 kW

5.8 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.26

1.64

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.994

0.996

WTOL

60 °C

60 °C

Poff

15 W

15 W

PTO

15 W

15 W

PSB

15 W

15 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0 kW

0.2 kW

Annual energy consumption Qhe

2838 kWh

3850 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

144 %

COP

3.5

Heating up time

1:49 h:min

Standby power input

25 W

Reference hot water temperature

51.5 °C

Mixed water at 40°C

274 l

SUZ-SHWM60VAH + EHST20D-*M*D
Configure model
Model name
SUZ-SHWM60VAH + EHST20D-*M*D
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

5 kW

5 kW

El input

1.01 kW

1.7 kW

COP

4.95

2.94

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

57 dB(A)

57 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

175 %

126 %

Prated

6.1 kW

6 kW

SCOP

4.44

3.22

Tbiv

-10 °C

-7 °C

TOL

-25 °C

-25 °C

Pdh Tj = -7°C

5.4 kW

5.31 kW

COP Tj = -7°C

2.78

1.85

Cdh Tj = -7 °C

0.992

0.995

Pdh Tj = +2°C

4.1 kW

3.7 kW

COP Tj = +2°C

4.43

3.13

Cdh Tj = +2 °C

0.984

0.987

Pdh Tj = +7°C

3.4 kW

3.1 kW

COP Tj = +7°C

6.27

4.66

Cdh Tj = +7 °C

0.972

0.977

Pdh Tj = 12°C

3.7 kW

3.9 kW

COP Tj = 12°C

7.11

6.53

Cdh Tj = +12 °C

0.971

0.975

Pdh Tj = Tbiv

6.1 kW

5.31 kW

COP Tj = Tbiv

2.26

1.85

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

6.1 kW

5.8 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.26

1.64

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.994

0.996

WTOL

60 °C

60 °C

Poff

15 W

15 W

PTO

15 W

15 W

PSB

15 W

15 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0 kW

0.2 kW

Annual energy consumption Qhe

2838 kWh

3850 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

144 %

COP

3.5

Heating up time

1:49 h:min

Standby power input

25 W

Reference hot water temperature

51.5 °C

Mixed water at 40°C

274 l

SUZ-SHWM60VAH + ERST20D-*M*D
Configure model
Model name
SUZ-SHWM60VAH + ERST20D-*M*D
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

5 kW

5 kW

El input

1.01 kW

1.7 kW

COP

4.95

2.94

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

57 dB(A)

57 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

178 %

128 %

Prated

6.1 kW

6 kW

SCOP

4.53

3.27

Tbiv

-10 °C

-7 °C

TOL

-25 °C

-25 °C

Pdh Tj = -7°C

5.4 kW

5.31 kW

COP Tj = -7°C

2.78

1.85

Cdh Tj = -7 °C

0.992

0.995

Pdh Tj = +2°C

4.1 kW

3.7 kW

COP Tj = +2°C

4.43

3.13

Cdh Tj = +2 °C

0.984

0.987

Pdh Tj = +7°C

3.4 kW

3.1 kW

COP Tj = +7°C

6.27

4.66

Cdh Tj = +7 °C

0.972

0.977

Pdh Tj = 12°C

3.7 kW

3.9 kW

COP Tj = 12°C

7.11

6.53

Cdh Tj = +12 °C

0.971

0.975

Pdh Tj = Tbiv

6.1 kW

5.31 kW

COP Tj = Tbiv

2.26

1.85

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

6.1 kW

5.8 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.26

1.64

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.994

0.996

WTOL

60 °C

60 °C

Poff

15 W

15 W

PTO

15 W

15 W

PSB

15 W

15 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0 kW

0.2 kW

Annual energy consumption Qhe

2783 kWh

3794 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

144 %

COP

3.5

Heating up time

1:49 h:min

Standby power input

25 W

Reference hot water temperature

51.5 °C

Mixed water at 40°C

274 l

SUZ-SHWM60VAH + EHSD-M*D
Configure model
Model name
SUZ-SHWM60VAH + EHSD-M*D
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

5 kW

5 kW

El input

1.01 kW

1.7 kW

COP

4.95

2.94

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

57 dB(A)

57 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

175 %

126 %

Prated

6.1 kW

6 kW

SCOP

4.44

3.22

Tbiv

-10 °C

-7 °C

TOL

-25 °C

-25 °C

Pdh Tj = -7°C

5.4 kW

5.31 kW

COP Tj = -7°C

2.78

1.85

Cdh Tj = -7 °C

0.992

0.995

Pdh Tj = +2°C

4.1 kW

3.7 kW

COP Tj = +2°C

4.43

3.13

Cdh Tj = +2 °C

0.984

0.987

Pdh Tj = +7°C

3.4 kW

3.1 kW

COP Tj = +7°C

6.27

4.66

Cdh Tj = +7 °C

0.972

0.977

Pdh Tj = 12°C

3.7 kW

3.9 kW

COP Tj = 12°C

7.11

6.53

Cdh Tj = +12 °C

0.971

0.975

Pdh Tj = Tbiv

6.1 kW

5.31 kW

COP Tj = Tbiv

2.26

1.85

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

6.1 kW

5.8 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.26

1.64

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.994

0.996

WTOL

60 °C

60 °C

Poff

15 W

15 W

PTO

15 W

15 W

PSB

15 W

15 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0 kW

0.2 kW

Annual energy consumption Qhe

2838 kWh

3850 kWh

SUZ-SHWM60VAH + EHSD-*M*D
Configure model
Model name
SUZ-SHWM60VAH + EHSD-*M*D
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

5 kW

5 kW

El input

1.01 kW

1.7 kW

COP

4.95

2.94

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

57 dB(A)

57 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

175 %

126 %

Prated

6.1 kW

6 kW

SCOP

4.44

3.22

Tbiv

-10 °C

-7 °C

TOL

-25 °C

-25 °C

Pdh Tj = -7°C

5.4 kW

5.31 kW

COP Tj = -7°C

2.78

1.85

Cdh Tj = -7 °C

0.992

0.995

Pdh Tj = +2°C

4.1 kW

3.7 kW

COP Tj = +2°C

4.43

3.13

Cdh Tj = +2 °C

0.984

0.987

Pdh Tj = +7°C

3.4 kW

3.1 kW

COP Tj = +7°C

6.27

4.66

Cdh Tj = +7 °C

0.972

0.977

Pdh Tj = 12°C

3.7 kW

3.9 kW

COP Tj = 12°C

7.11

6.53

Cdh Tj = +12 °C

0.971

0.975

Pdh Tj = Tbiv

6.1 kW

5.31 kW

COP Tj = Tbiv

2.26

1.85

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

6.1 kW

5.8 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.26

1.64

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.994

0.996

WTOL

60 °C

60 °C

Poff

15 W

15 W

PTO

15 W

15 W

PSB

15 W

15 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0 kW

0.2 kW

Annual energy consumption Qhe

2838 kWh

3850 kWh

SUZ-SHWM60VAH + ERSD-M*D
Configure model
Model name
SUZ-SHWM60VAH + ERSD-M*D
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

5 kW

5 kW

El input

1.01 kW

1.7 kW

COP

4.95

2.94

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

57 dB(A)

57 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

178 %

128 %

Prated

6.1 kW

6 kW

SCOP

4.53

3.27

Tbiv

-10 °C

-7 °C

TOL

-25 °C

-25 °C

Pdh Tj = -7°C

5.4 kW

5.31 kW

COP Tj = -7°C

2.78

1.85

Cdh Tj = -7 °C

0.992

0.995

Pdh Tj = +2°C

4.1 kW

3.7 kW

COP Tj = +2°C

4.43

3.13

Cdh Tj = +2 °C

0.984

0.987

Pdh Tj = +7°C

3.4 kW

3.1 kW

COP Tj = +7°C

6.27

4.66

Cdh Tj = +7 °C

0.972

0.977

Pdh Tj = 12°C

3.7 kW

3.9 kW

COP Tj = 12°C

7.11

6.53

Cdh Tj = +12 °C

0.971

0.975

Pdh Tj = Tbiv

6.1 kW

5.31 kW

COP Tj = Tbiv

2.26

1.85

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

6.1 kW

5.8 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.26

1.64

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.994

0.996

WTOL

60 °C

60 °C

Poff

15 W

15 W

PTO

15 W

15 W

PSB

15 W

15 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0 kW

0.2 kW

Annual energy consumption Qhe

2783 kWh

3794 kWh

SUZ-SHWM60VAH + ERSD-*M*D
Configure model
Model name
SUZ-SHWM60VAH + ERSD-*M*D
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

5 kW

5 kW

El input

1.01 kW

1.7 kW

COP

4.95

2.94

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

57 dB(A)

57 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

178 %

128 %

Prated

6.1 kW

6 kW

SCOP

4.53

3.27

Tbiv

-10 °C

-7 °C

TOL

-25 °C

-25 °C

Pdh Tj = -7°C

5.4 kW

5.31 kW

COP Tj = -7°C

2.78

1.85

Cdh Tj = -7 °C

0.992

0.995

Pdh Tj = +2°C

4.1 kW

3.7 kW

COP Tj = +2°C

4.43

3.13

Cdh Tj = +2 °C

0.984

0.987

Pdh Tj = +7°C

3.4 kW

3.1 kW

COP Tj = +7°C

6.27

4.66

Cdh Tj = +7 °C

0.972

0.977

Pdh Tj = 12°C

3.7 kW

3.9 kW

COP Tj = 12°C

7.11

6.53

Cdh Tj = +12 °C

0.971

0.975

Pdh Tj = Tbiv

6.1 kW

5.31 kW

COP Tj = Tbiv

2.26

1.85

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

6.1 kW

5.8 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.26

1.64

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.994

0.996

WTOL

60 °C

60 °C

Poff

15 W

15 W

PTO

15 W

15 W

PSB

15 W

15 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0 kW

0.2 kW

Annual energy consumption Qhe

2783 kWh

3794 kWh

SUZ-SWM80VA2 + EHST20D-M*D
Configure model
Model name
SUZ-SWM80VA2 + EHST20D-M*D
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

6 kW

6 kW

El input

1.18 kW

2 kW

COP

5.1

3

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

59 dB(A)

59 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

183 %

133 %

Prated

6.6 kW

7 kW

SCOP

4.66

3.39

Tbiv

-10 °C

-7 °C

TOL

-25 °C

-25 °C

Pdh Tj = -7°C

5.9 kW

6.2 kW

COP Tj = -7°C

3.16

1.91

Cdh Tj = -7 °C

0.992

0.995

Pdh Tj = +2°C

4.4 kW

3.8 kW

COP Tj = +2°C

4.61

3.39

Cdh Tj = +2 °C

0.984

0.987

Pdh Tj = +7°C

3.4 kW

3.1 kW

COP Tj = +7°C

6.22

4.69

Cdh Tj = +7 °C

0.973

0.977

Pdh Tj = 12°C

3.7 kW

3.9 kW

COP Tj = 12°C

7.38

6.67

Cdh Tj = +12 °C

0.97

0.974

Pdh Tj = Tbiv

6.6 kW

6.2 kW

COP Tj = Tbiv

2.4

1.91

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

6.6 kW

5.8 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.4

1.68

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.995

0.996

WTOL

60 °C

60 °C

Poff

15 W

15 W

PTO

15 W

15 W

PSB

15 W

15 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0 kW

1.2 kW

Annual energy consumption Qhe

2929 kWh

4262 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

144 %

COP

3.5

Heating up time

1:49 h:min

Standby power input

25 W

Reference hot water temperature

51.5 °C

Mixed water at 40°C

274 l

SUZ-SWM80VA2 + EHST20D-*M*D
Configure model
Model name
SUZ-SWM80VA2 + EHST20D-*M*D
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

6 kW

6 kW

El input

1.18 kW

2 kW

COP

5.1

3

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

59 dB(A)

59 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

183 %

133 %

Prated

6.6 kW

7 kW

SCOP

4.66

3.39

Tbiv

-10 °C

-7 °C

TOL

-25 °C

-25 °C

Pdh Tj = -7°C

5.9 kW

6.2 kW

COP Tj = -7°C

3.16

1.91

Cdh Tj = -7 °C

0.992

0.995

Pdh Tj = +2°C

4.4 kW

3.8 kW

COP Tj = +2°C

4.61

3.39

Cdh Tj = +2 °C

0.984

0.987

Pdh Tj = +7°C

3.4 kW

3.1 kW

COP Tj = +7°C

6.22

4.69

Cdh Tj = +7 °C

0.973

0.977

Pdh Tj = 12°C

3.7 kW

3.9 kW

COP Tj = 12°C

7.38

6.67

Cdh Tj = +12 °C

0.97

0.974

Pdh Tj = Tbiv

6.6 kW

6.2 kW

COP Tj = Tbiv

2.4

1.91

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

6.6 kW

5.8 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.4

1.68

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.995

0.996

WTOL

60 °C

60 °C

Poff

15 W

15 W

PTO

15 W

15 W

PSB

15 W

15 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0 kW

1.2 kW

Annual energy consumption Qhe

2929 kWh

4262 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

144 %

COP

3.5

Heating up time

1:49 h:min

Standby power input

25 W

Reference hot water temperature

51.5 °C

Mixed water at 40°C

274 l

SUZ-SWM80VA2 + ERST20D-*M*D
Configure model
Model name
SUZ-SWM80VA2 + ERST20D-*M*D
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

6 kW

6 kW

El input

1.18 kW

2 kW

COP

5.1

3

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

59 dB(A)

59 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

187 %

135 %

Prated

6.6 kW

7 kW

SCOP

4.74

3.44

Tbiv

-10 °C

-7 °C

TOL

-25 °C

-25 °C

Pdh Tj = -7°C

5.9 kW

6.2 kW

COP Tj = -7°C

3.16

1.91

Cdh Tj = -7 °C

0.992

0.995

Pdh Tj = +2°C

4.4 kW

3.8 kW

COP Tj = +2°C

4.61

3.39

Cdh Tj = +2 °C

0.984

0.987

Pdh Tj = +7°C

3.4 kW

3.1 kW

COP Tj = +7°C

6.22

4.69

Cdh Tj = +7 °C

0.973

0.977

Pdh Tj = 12°C

3.7 kW

3.9 kW

COP Tj = 12°C

7.38

6.67

Cdh Tj = +12 °C

0.97

0.974

Pdh Tj = Tbiv

6.6 kW

6.2 kW

COP Tj = Tbiv

2.4

1.91

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

6.6 kW

5.8 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.4

1.68

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.995

0.996

WTOL

60 °C

60 °C

Poff

15 W

15 W

PTO

15 W

15 W

PSB

15 W

15 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0 kW

1.2 kW

Annual energy consumption Qhe

2874 kWh

4207 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

144 %

COP

3.5

Heating up time

1:49 h:min

Standby power input

25 W

Reference hot water temperature

51.5 °C

Mixed water at 40°C

274 l

SUZ-SWM80VA2 + EHSD-M*D
Configure model
Model name
SUZ-SWM80VA2 + EHSD-M*D
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

6 kW

6 kW

El input

1.18 kW

2 kW

COP

5.1

3

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

59 dB(A)

59 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

183 %

133 %

Prated

6.6 kW

7 kW

SCOP

4.66

3.39

Tbiv

-10 °C

-7 °C

TOL

-25 °C

-25 °C

Pdh Tj = -7°C

5.9 kW

6.2 kW

COP Tj = -7°C

3.16

1.91

Cdh Tj = -7 °C

0.992

0.995

Pdh Tj = +2°C

4.4 kW

3.8 kW

COP Tj = +2°C

4.61

3.39

Cdh Tj = +2 °C

0.984

0.987

Pdh Tj = +7°C

3.4 kW

3.1 kW

COP Tj = +7°C

6.22

4.69

Cdh Tj = +7 °C

0.973

0.977

Pdh Tj = 12°C

3.7 kW

3.9 kW

COP Tj = 12°C

7.38

6.67

Cdh Tj = +12 °C

0.97

0.974

Pdh Tj = Tbiv

6.6 kW

6.2 kW

COP Tj = Tbiv

2.4

1.91

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

6.6 kW

5.8 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.4

1.68

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.995

0.996

WTOL

60 °C

60 °C

Poff

15 W

15 W

PTO

15 W

15 W

PSB

15 W

15 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0 kW

1.2 kW

Annual energy consumption Qhe

2929 kWh

4262 kWh

SUZ-SWM80VA2 + EHSD-*M*D
Configure model
Model name
SUZ-SWM80VA2 + EHSD-*M*D
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

6 kW

6 kW

El input

1.18 kW

2 kW

COP

5.1

3

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

59 dB(A)

59 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

183 %

133 %

Prated

6.6 kW

7 kW

SCOP

4.66

3.39

Tbiv

-10 °C

-7 °C

TOL

-25 °C

-25 °C

Pdh Tj = -7°C

5.9 kW

6.2 kW

COP Tj = -7°C

3.16

1.91

Cdh Tj = -7 °C

0.992

0.995

Pdh Tj = +2°C

4.4 kW

3.8 kW

COP Tj = +2°C

4.61

3.39

Cdh Tj = +2 °C

0.984

0.987

Pdh Tj = +7°C

3.4 kW

3.1 kW

COP Tj = +7°C

6.22

4.69

Cdh Tj = +7 °C

0.973

0.977

Pdh Tj = 12°C

3.7 kW

3.9 kW

COP Tj = 12°C

7.38

6.67

Cdh Tj = +12 °C

0.97

0.974

Pdh Tj = Tbiv

6.6 kW

6.2 kW

COP Tj = Tbiv

2.4

1.91

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

6.6 kW

5.8 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.4

1.68

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.995

0.996

WTOL

60 °C

60 °C

Poff

15 W

15 W

PTO

15 W

15 W

PSB

15 W

15 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0 kW

1.2 kW

Annual energy consumption Qhe

2929 kWh

4262 kWh

SUZ-SWM80VA2 + ERSD-M*D
Configure model
Model name
SUZ-SWM80VA2 + ERSD-M*D
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

6 kW

6 kW

El input

1.18 kW

2 kW

COP

5.1

3

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

59 dB(A)

59 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

187 %

135 %

Prated

6.6 kW

7 kW

SCOP

4.74

3.44

Tbiv

-10 °C

-7 °C

TOL

-25 °C

-25 °C

Pdh Tj = -7°C

5.9 kW

6.2 kW

COP Tj = -7°C

3.16

1.91

Cdh Tj = -7 °C

0.992

0.995

Pdh Tj = +2°C

4.4 kW

3.8 kW

COP Tj = +2°C

4.61

3.39

Cdh Tj = +2 °C

0.984

0.987

Pdh Tj = +7°C

3.4 kW

3.1 kW

COP Tj = +7°C

6.22

4.69

Cdh Tj = +7 °C

0.973

0.977

Pdh Tj = 12°C

3.7 kW

3.9 kW

COP Tj = 12°C

7.38

6.67

Cdh Tj = +12 °C

0.97

0.974

Pdh Tj = Tbiv

6.6 kW

6.2 kW

COP Tj = Tbiv

2.4

1.91

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

6.6 kW

5.8 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.4

1.68

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.995

0.996

WTOL

60 °C

60 °C

Poff

15 W

15 W

PTO

15 W

15 W

PSB

15 W

15 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0 kW

1.2 kW

Annual energy consumption Qhe

2874 kWh

4207 kWh

SUZ-SWM80VA2 + ERSD-*M*D
Configure model
Model name
SUZ-SWM80VA2 + ERSD-*M*D
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

6 kW

6 kW

El input

1.18 kW

2 kW

COP

5.1

3

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

59 dB(A)

59 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

187 %

135 %

Prated

6.6 kW

7 kW

SCOP

4.74

3.44

Tbiv

-10 °C

-7 °C

TOL

-25 °C

-25 °C

Pdh Tj = -7°C

5.9 kW

6.2 kW

COP Tj = -7°C

3.16

1.91

Cdh Tj = -7 °C

0.992

0.995

Pdh Tj = +2°C

4.4 kW

3.8 kW

COP Tj = +2°C

4.61

3.39

Cdh Tj = +2 °C

0.984

0.987

Pdh Tj = +7°C

3.4 kW

3.1 kW

COP Tj = +7°C

6.22

4.69

Cdh Tj = +7 °C

0.973

0.977

Pdh Tj = 12°C

3.7 kW

3.9 kW

COP Tj = 12°C

7.38

6.67

Cdh Tj = +12 °C

0.97

0.974

Pdh Tj = Tbiv

6.6 kW

6.2 kW

COP Tj = Tbiv

2.4

1.91

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

6.6 kW

5.8 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.4

1.68

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.995

0.996

WTOL

60 °C

60 °C

Poff

15 W

15 W

PTO

15 W

15 W

PSB

15 W

15 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0 kW

1.2 kW

Annual energy consumption Qhe

2874 kWh

4207 kWh

SUZ-SWM80VAH2 + EHST20D-M*D
Configure model
Model name
SUZ-SWM80VAH2 + EHST20D-M*D
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

6 kW

6 kW

El input

1.18 kW

2 kW

COP

5.1

3

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

59 dB(A)

59 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

175 %

128 %

Prated

6.6 kW

7 kW

SCOP

4.44

3.29

Tbiv

-10 °C

-7 °C

TOL

-25 °C

-25 °C

Pdh Tj = -7°C

5.9 kW

6.2 kW

COP Tj = -7°C

2.86

1.81

Cdh Tj = -7 °C

0.993

0.996

Pdh Tj = +2°C

4.4 kW

3.8 kW

COP Tj = +2°C

4.35

3.25

Cdh Tj = +2 °C

0.985

0.987

Pdh Tj = +7°C

3.4 kW

3.1 kW

COP Tj = +7°C

6.22

4.69

Cdh Tj = +7 °C

0.973

0.977

Pdh Tj = 12°C

3.7 kW

3.9 kW

COP Tj = 12°C

7.38

6.67

Cdh Tj = +12 °C

0.97

0.974

Pdh Tj = Tbiv

6.6 kW

6.2 kW

COP Tj = Tbiv

2.23

1.81

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

6.6 kW

5.8 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.23

1.58

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.995

0.996

WTOL

60 °C

60 °C

Poff

15 W

15 W

PTO

15 W

15 W

PSB

15 W

15 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0 kW

1.2 kW

Annual energy consumption Qhe

3070 kWh

4401 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

144 %

COP

3.5

Heating up time

1:49 h:min

Standby power input

25 W

Reference hot water temperature

51.5 °C

Mixed water at 40°C

274 l

SUZ-SWM80VAH2 + EHST20D-*M*D
Configure model
Model name
SUZ-SWM80VAH2 + EHST20D-*M*D
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

6 kW

6 kW

El input

1.18 kW

2 kW

COP

5.1

3

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

59 dB(A)

59 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

175 %

128 %

Prated

6.6 kW

7 kW

SCOP

4.44

3.29

Tbiv

-10 °C

-7 °C

TOL

-25 °C

-25 °C

Pdh Tj = -7°C

5.9 kW

6.2 kW

COP Tj = -7°C

2.86

1.81

Cdh Tj = -7 °C

0.993

0.996

Pdh Tj = +2°C

4.4 kW

3.8 kW

COP Tj = +2°C

4.35

3.25

Cdh Tj = +2 °C

0.985

0.987

Pdh Tj = +7°C

3.4 kW

3.1 kW

COP Tj = +7°C

6.22

4.69

Cdh Tj = +7 °C

0.973

0.977

Pdh Tj = 12°C

3.7 kW

3.9 kW

COP Tj = 12°C

7.38

6.67

Cdh Tj = +12 °C

0.97

0.974

Pdh Tj = Tbiv

6.6 kW

6.2 kW

COP Tj = Tbiv

2.23

1.81

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

6.6 kW

5.8 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.23

1.58

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.995

0.996

WTOL

60 °C

60 °C

Poff

15 W

15 W

PTO

15 W

15 W

PSB

15 W

15 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0 kW

1.2 kW

Annual energy consumption Qhe

3070 kWh

4401 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

144 %

COP

3.5

Heating up time

1:49 h:min

Standby power input

25 W

Reference hot water temperature

51.5 °C

Mixed water at 40°C

274 l

SUZ-SWM80VAH2 + ERST20D-*M*D
Configure model
Model name
SUZ-SWM80VAH2 + ERST20D-*M*D
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

6 kW

6 kW

El input

1.18 kW

2 kW

COP

5.1

3

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

59 dB(A)

59 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

178 %

130 %

Prated

6.6 kW

7 kW

SCOP

4.52

3.33

Tbiv

-10 °C

-7 °C

TOL

-25 °C

-25 °C

Pdh Tj = -7°C

5.9 kW

6.2 kW

COP Tj = -7°C

2.86

1.81

Cdh Tj = -7 °C

0.993

0.996

Pdh Tj = +2°C

4.4 kW

3.8 kW

COP Tj = +2°C

4.35

3.25

Cdh Tj = +2 °C

0.985

0.987

Pdh Tj = +7°C

3.4 kW

3.1 kW

COP Tj = +7°C

6.22

4.69

Cdh Tj = +7 °C

0.973

0.977

Pdh Tj = 12°C

3.7 kW

3.9 kW

COP Tj = 12°C

7.38

6.67

Cdh Tj = +12 °C

0.97

0.974

Pdh Tj = Tbiv

6.6 kW

6.2 kW

COP Tj = Tbiv

2.23

1.81

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

6.6 kW

5.8 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.23

1.58

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.995

0.996

WTOL

60 °C

60 °C

Poff

15 W

15 W

PTO

15 W

15 W

PSB

15 W

15 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0 kW

1.2 kW

Annual energy consumption Qhe

3015 kWh

4346 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

144 %

COP

3.5

Heating up time

1:49 h:min

Standby power input

25 W

Reference hot water temperature

51.5 °C

Mixed water at 40°C

274 l

SUZ-SWM80VAH2 + EHSD-M*D
Configure model
Model name
SUZ-SWM80VAH2 + EHSD-M*D
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

6 kW

6 kW

El input

1.18 kW

2 kW

COP

5.1

3

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

59 dB(A)

59 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

175 %

128 %

Prated

6.6 kW

7 kW

SCOP

4.44

3.29

Tbiv

-10 °C

-7 °C

TOL

-25 °C

-25 °C

Pdh Tj = -7°C

5.9 kW

6.2 kW

COP Tj = -7°C

2.86

1.81

Cdh Tj = -7 °C

0.993

0.996

Pdh Tj = +2°C

4.4 kW

3.8 kW

COP Tj = +2°C

4.35

3.25

Cdh Tj = +2 °C

0.985

0.987

Pdh Tj = +7°C

3.4 kW

3.1 kW

COP Tj = +7°C

6.22

4.69

Cdh Tj = +7 °C

0.973

0.977

Pdh Tj = 12°C

3.7 kW

3.9 kW

COP Tj = 12°C

7.38

6.67

Cdh Tj = +12 °C

0.97

0.974

Pdh Tj = Tbiv

6.6 kW

6.2 kW

COP Tj = Tbiv

2.23

1.81

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

6.6 kW

5.8 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.23

1.58

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.995

0.996

WTOL

60 °C

60 °C

Poff

15 W

15 W

PTO

15 W

15 W

PSB

15 W

15 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0 kW

1.2 kW

Annual energy consumption Qhe

3070 kWh

4401 kWh

SUZ-SWM80VAH2 + EHSD-*M*D
Configure model
Model name
SUZ-SWM80VAH2 + EHSD-*M*D
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

6 kW

6 kW

El input

1.18 kW

2 kW

COP

5.1

3

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

59 dB(A)

59 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

175 %

128 %

Prated

6.6 kW

7 kW

SCOP

4.44

3.29

Tbiv

-10 °C

-7 °C

TOL

-25 °C

-25 °C

Pdh Tj = -7°C

5.9 kW

6.2 kW

COP Tj = -7°C

2.86

1.81

Cdh Tj = -7 °C

0.993

0.996

Pdh Tj = +2°C

4.4 kW

3.8 kW

COP Tj = +2°C

4.35

3.25

Cdh Tj = +2 °C

0.985

0.987

Pdh Tj = +7°C

3.4 kW

3.1 kW

COP Tj = +7°C

6.22

4.69

Cdh Tj = +7 °C

0.973

0.977

Pdh Tj = 12°C

3.7 kW

3.9 kW

COP Tj = 12°C

7.38

6.67

Cdh Tj = +12 °C

0.97

0.974

Pdh Tj = Tbiv

6.6 kW

6.2 kW

COP Tj = Tbiv

2.23

1.81

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

6.6 kW

5.8 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.23

1.58

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.995

0.996

WTOL

60 °C

60 °C

Poff

15 W

15 W

PTO

15 W

15 W

PSB

15 W

15 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0 kW

1.2 kW

Annual energy consumption Qhe

3070 kWh

4401 kWh

SUZ-SWM80VAH2 + ERSD-M*D
Configure model
Model name
SUZ-SWM80VAH2 + ERSD-M*D
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

6 kW

6 kW

El input

1.18 kW

2 kW

COP

5.1

3

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

59 dB(A)

59 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

178 %

130 %

Prated

6.6 kW

7 kW

SCOP

4.52

3.33

Tbiv

-10 °C

-7 °C

TOL

-25 °C

-25 °C

Pdh Tj = -7°C

5.9 kW

6.2 kW

COP Tj = -7°C

2.86

1.81

Cdh Tj = -7 °C

0.993

0.996

Pdh Tj = +2°C

4.4 kW

3.8 kW

COP Tj = +2°C

4.35

3.25

Cdh Tj = +2 °C

0.985

0.987

Pdh Tj = +7°C

3.4 kW

3.1 kW

COP Tj = +7°C

6.22

4.69

Cdh Tj = +7 °C

0.973

0.977

Pdh Tj = 12°C

3.7 kW

3.9 kW

COP Tj = 12°C

7.38

6.67

Cdh Tj = +12 °C

0.97

0.974

Pdh Tj = Tbiv

6.6 kW

6.2 kW

COP Tj = Tbiv

2.23

1.81

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

6.6 kW

5.8 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.23

1.58

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.995

0.996

WTOL

60 °C

60 °C

Poff

15 W

15 W

PTO

15 W

15 W

PSB

15 W

15 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0 kW

1.2 kW

Annual energy consumption Qhe

3015 kWh

4346 kWh

SUZ-SWM80VAH2 + ERSD-*M*D
Configure model
Model name
SUZ-SWM80VAH2 + ERSD-*M*D
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

6 kW

6 kW

El input

1.18 kW

2 kW

COP

5.1

3

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

59 dB(A)

59 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

178 %

130 %

Prated

6.6 kW

7 kW

SCOP

4.52

3.33

Tbiv

-10 °C

-7 °C

TOL

-25 °C

-25 °C

Pdh Tj = -7°C

5.9 kW

6.2 kW

COP Tj = -7°C

2.86

1.81

Cdh Tj = -7 °C

0.993

0.996

Pdh Tj = +2°C

4.4 kW

3.8 kW

COP Tj = +2°C

4.35

3.25

Cdh Tj = +2 °C

0.985

0.987

Pdh Tj = +7°C

3.4 kW

3.1 kW

COP Tj = +7°C

6.22

4.69

Cdh Tj = +7 °C

0.973

0.977

Pdh Tj = 12°C

3.7 kW

3.9 kW

COP Tj = 12°C

7.38

6.67

Cdh Tj = +12 °C

0.97

0.974

Pdh Tj = Tbiv

6.6 kW

6.2 kW

COP Tj = Tbiv

2.23

1.81

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

6.6 kW

5.8 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.23

1.58

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.995

0.996

WTOL

60 °C

60 °C

Poff

15 W

15 W

PTO

15 W

15 W

PSB

15 W

15 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0 kW

1.2 kW

Annual energy consumption Qhe

3015 kWh

4346 kWh

SUZ-SWM100VA + EHST20D-M*D
Configure model
Model name
SUZ-SWM100VA + EHST20D-M*D
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

7.5 kW

7.5 kW

El input

1.55 kW

2.68 kW

COP

4.85

2.8

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

60 dB(A)

60 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

179 %

133 %

Prated

7.8 kW

7.5 kW

SCOP

4.54

3.39

Tbiv

-10 °C

-7 °C

TOL

-25 °C

-25 °C

Pdh Tj = -7°C

6.9 kW

6.63 kW

COP Tj = -7°C

2.99

1.8

Cdh Tj = -7 °C

0.993

0.996

Pdh Tj = +2°C

4.5 kW

4.1 kW

COP Tj = +2°C

4.57

3.41

Cdh Tj = +2 °C

0.985

0.988

Pdh Tj = +7°C

3.4 kW

3.5 kW

COP Tj = +7°C

5.84

4.79

Cdh Tj = +7 °C

0.974

0.979

Pdh Tj = 12°C

3.7 kW

3.9 kW

COP Tj = 12°C

6.98

6.9

Cdh Tj = +12 °C

0.972

0.973

Pdh Tj = Tbiv

7.8 kW

6.63 kW

COP Tj = Tbiv

2.34

1.8

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

7.8 kW

6.1 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.34

1.69

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.995

0.996

WTOL

60 °C

60 °C

Poff

15 W

15 W

PTO

15 W

15 W

PSB

15 W

15 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0 kW

1.4 kW

Annual energy consumption Qhe

3548 kWh

4567 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

144 %

COP

3.5

Heating up time

1:49 h:min

Standby power input

25 W

Reference hot water temperature

51.5 °C

Mixed water at 40°C

274 l

SUZ-SWM100VA + EHST20D-*M*D
Configure model
Model name
SUZ-SWM100VA + EHST20D-*M*D
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

7.5 kW

7.5 kW

El input

1.55 kW

2.68 kW

COP

4.85

2.8

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

60 dB(A)

60 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

179 %

133 %

Prated

7.8 kW

7.5 kW

SCOP

4.54

3.39

Tbiv

-10 °C

-7 °C

TOL

-25 °C

-25 °C

Pdh Tj = -7°C

6.9 kW

6.63 kW

COP Tj = -7°C

2.99

1.8

Cdh Tj = -7 °C

0.993

0.996

Pdh Tj = +2°C

4.5 kW

4.1 kW

COP Tj = +2°C

4.57

3.41

Cdh Tj = +2 °C

0.985

0.988

Pdh Tj = +7°C

3.4 kW

3.5 kW

COP Tj = +7°C

5.84

4.79

Cdh Tj = +7 °C

0.974

0.979

Pdh Tj = 12°C

3.7 kW

3.9 kW

COP Tj = 12°C

6.98

6.9

Cdh Tj = +12 °C

0.972

0.973

Pdh Tj = Tbiv

7.8 kW

6.63 kW

COP Tj = Tbiv

2.34

1.8

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

7.8 kW

6.1 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.34

1.69

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.995

0.996

WTOL

60 °C

60 °C

Poff

15 W

15 W

PTO

15 W

15 W

PSB

15 W

15 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0 kW

1.4 kW

Annual energy consumption Qhe

3548 kWh

4567 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

144 %

COP

3.5

Heating up time

1:49 h:min

Standby power input

25 W

Reference hot water temperature

51.5 °C

Mixed water at 40°C

274 l

SUZ-SWM100VA + ERST20D-*M*D
Configure model
Model name
SUZ-SWM100VA + ERST20D-*M*D
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

7.5 kW

7.5 kW

El input

1.55 kW

2.68 kW

COP

4.85

2.8

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

60 dB(A)

60 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

182 %

134 %

Prated

7.8 kW

7.5 kW

SCOP

4.61

3.43

Tbiv

-10 °C

-7 °C

TOL

-25 °C

-25 °C

Pdh Tj = -7°C

6.9 kW

6.63 kW

COP Tj = -7°C

2.99

1.8

Cdh Tj = -7 °C

0.993

0.996

Pdh Tj = +2°C

4.5 kW

4.1 kW

COP Tj = +2°C

4.57

3.41

Cdh Tj = +2 °C

0.985

0.988

Pdh Tj = +7°C

3.4 kW

3.5 kW

COP Tj = +7°C

5.84

4.79

Cdh Tj = +7 °C

0.974

0.979

Pdh Tj = 12°C

3.7 kW

3.9 kW

COP Tj = 12°C

6.98

6.9

Cdh Tj = +12 °C

0.972

0.973

Pdh Tj = Tbiv

7.8 kW

6.63 kW

COP Tj = Tbiv

2.34

1.8

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

7.8 kW

6.1 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.34

1.69

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.995

0.996

WTOL

60 °C

60 °C

Poff

15 W

15 W

PTO

15 W

15 W

PSB

15 W

15 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0 kW

1.4 kW

Annual energy consumption Qhe

3492 kWh

4512 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

144 %

COP

3.5

Heating up time

1:49 h:min

Standby power input

25 W

Reference hot water temperature

51.5 °C

Mixed water at 40°C

274 l

SUZ-SWM100VA + EHSD-M*D
Configure model
Model name
SUZ-SWM100VA + EHSD-M*D
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

7.5 kW

7.5 kW

El input

1.55 kW

2.68 kW

COP

4.85

2.8

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

60 dB(A)

60 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

179 %

133 %

Prated

7.8 kW

7.5 kW

SCOP

4.54

3.39

Tbiv

-10 °C

-7 °C

TOL

-25 °C

-25 °C

Pdh Tj = -7°C

6.9 kW

6.63 kW

COP Tj = -7°C

2.99

1.8

Cdh Tj = -7 °C

0.993

0.996

Pdh Tj = +2°C

4.5 kW

4.1 kW

COP Tj = +2°C

4.57

3.41

Cdh Tj = +2 °C

0.985

0.988

Pdh Tj = +7°C

3.4 kW

3.5 kW

COP Tj = +7°C

5.84

4.79

Cdh Tj = +7 °C

0.974

0.979

Pdh Tj = 12°C

3.7 kW

3.9 kW

COP Tj = 12°C

6.98

6.9

Cdh Tj = +12 °C

0.972

0.973

Pdh Tj = Tbiv

7.8 kW

6.63 kW

COP Tj = Tbiv

2.34

1.8

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

7.8 kW

6.1 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.34

1.69

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.995

0.996

WTOL

60 °C

60 °C

Poff

15 W

15 W

PTO

15 W

15 W

PSB

15 W

15 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0 kW

1.4 kW

Annual energy consumption Qhe

3548 kWh

4567 kWh

SUZ-SWM100VA + EHSD-*M*D
Configure model
Model name
SUZ-SWM100VA + EHSD-*M*D
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

7.5 kW

7.5 kW

El input

1.55 kW

2.68 kW

COP

4.85

2.8

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

60 dB(A)

60 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

179 %

133 %

Prated

7.8 kW

7.5 kW

SCOP

4.54

3.39

Tbiv

-10 °C

-7 °C

TOL

-25 °C

-25 °C

Pdh Tj = -7°C

6.9 kW

6.63 kW

COP Tj = -7°C

2.99

1.8

Cdh Tj = -7 °C

0.993

0.996

Pdh Tj = +2°C

4.5 kW

4.1 kW

COP Tj = +2°C

4.57

3.41

Cdh Tj = +2 °C

0.985

0.988

Pdh Tj = +7°C

3.4 kW

3.5 kW

COP Tj = +7°C

5.84

4.79

Cdh Tj = +7 °C

0.974

0.979

Pdh Tj = 12°C

3.7 kW

3.9 kW

COP Tj = 12°C

6.98

6.9

Cdh Tj = +12 °C

0.972

0.973

Pdh Tj = Tbiv

7.8 kW

6.63 kW

COP Tj = Tbiv

2.34

1.8

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

7.8 kW

6.1 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.34

1.69

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.995

0.996

WTOL

60 °C

60 °C

Poff

15 W

15 W

PTO

15 W

15 W

PSB

15 W

15 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0 kW

1.4 kW

Annual energy consumption Qhe

3548 kWh

4567 kWh

SUZ-SWM100VA + ERSD-M*D
Configure model
Model name
SUZ-SWM100VA + ERSD-M*D
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

7.5 kW

7.5 kW

El input

1.55 kW

2.68 kW

COP

4.85

2.8

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

60 dB(A)

60 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

182 %

134 %

Prated

7.8 kW

7.5 kW

SCOP

4.61

3.43

Tbiv

-10 °C

-7 °C

TOL

-25 °C

-25 °C

Pdh Tj = -7°C

6.9 kW

6.63 kW

COP Tj = -7°C

2.99

1.8

Cdh Tj = -7 °C

0.993

0.996

Pdh Tj = +2°C

4.5 kW

4.1 kW

COP Tj = +2°C

4.57

3.41

Cdh Tj = +2 °C

0.985

0.988

Pdh Tj = +7°C

3.4 kW

3.5 kW

COP Tj = +7°C

5.84

4.79

Cdh Tj = +7 °C

0.974

0.979

Pdh Tj = 12°C

3.7 kW

3.9 kW

COP Tj = 12°C

6.98

6.9

Cdh Tj = +12 °C

0.972

0.973

Pdh Tj = Tbiv

7.8 kW

6.63 kW

COP Tj = Tbiv

2.34

1.8

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

7.8 kW

6.1 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.34

1.69

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.995

0.996

WTOL

60 °C

60 °C

Poff

15 W

15 W

PTO

15 W

15 W

PSB

15 W

15 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0 kW

1.4 kW

Annual energy consumption Qhe

3492 kWh

4512 kWh

SUZ-SWM100VA + ERSD-*M*D
Configure model
Model name
SUZ-SWM100VA + ERSD-*M*D
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

7.5 kW

7.5 kW

El input

1.55 kW

2.68 kW

COP

4.85

2.8

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

60 dB(A)

60 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

182 %

134 %

Prated

7.8 kW

7.5 kW

SCOP

4.61

3.43

Tbiv

-10 °C

-7 °C

TOL

-25 °C

-25 °C

Pdh Tj = -7°C

6.9 kW

6.63 kW

COP Tj = -7°C

2.99

1.8

Cdh Tj = -7 °C

0.993

0.996

Pdh Tj = +2°C

4.5 kW

4.1 kW

COP Tj = +2°C

4.57

3.41

Cdh Tj = +2 °C

0.985

0.988

Pdh Tj = +7°C

3.4 kW

3.5 kW

COP Tj = +7°C

5.84

4.79

Cdh Tj = +7 °C

0.974

0.979

Pdh Tj = 12°C

3.7 kW

3.9 kW

COP Tj = 12°C

6.98

6.9

Cdh Tj = +12 °C

0.972

0.973

Pdh Tj = Tbiv

7.8 kW

6.63 kW

COP Tj = Tbiv

2.34

1.8

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

7.8 kW

6.1 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.34

1.69

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.995

0.996

WTOL

60 °C

60 °C

Poff

15 W

15 W

PTO

15 W

15 W

PSB

15 W

15 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0 kW

1.4 kW

Annual energy consumption Qhe

3492 kWh

4512 kWh

SUZ-SWM100VAH + EHST20D-M*D
Configure model
Model name
SUZ-SWM100VAH + EHST20D-M*D
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

7.5 kW

7.5 kW

El input

1.55 kW

2.68 kW

COP

4.85

2.8

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

60 dB(A)

60 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

174 %

127 %

Prated

7.8 kW

7.5 kW

SCOP

4.43

3.26

Tbiv

-10 °C

-7 °C

TOL

-25 °C

-25 °C

Pdh Tj = -7°C

6.9 kW

6.63 kW

COP Tj = -7°C

2.79

1.68

Cdh Tj = -7 °C

0.994

0.996

Pdh Tj = +2°C

4.5 kW

4.1 kW

COP Tj = +2°C

4.43

3.23

Cdh Tj = +2 °C

0.985

0.988

Pdh Tj = +7°C

3.4 kW

3.5 kW

COP Tj = +7°C

5.89

4.8

Cdh Tj = +7 °C

0.974

0.979

Pdh Tj = 12°C

3.7 kW

3.9 kW

COP Tj = 12°C

7.04

6.78

Cdh Tj = +12 °C

0.971

0.974

Pdh Tj = Tbiv

7.8 kW

6.63 kW

COP Tj = Tbiv

2.22

1.68

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

7.8 kW

6.1 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.22

1.59

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.996

0.996

WTOL

60 °C

60 °C

Poff

15 W

15 W

PTO

15 W

15 W

PSB

15 W

15 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0 kW

1.4 kW

Annual energy consumption Qhe

3640 kWh

4758 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

144 %

COP

3.5

Heating up time

1:49 h:min

Standby power input

25 W

Reference hot water temperature

51.5 °C

Mixed water at 40°C

274 l

SUZ-SWM100VAH + EHST20D-*M*D
Configure model
Model name
SUZ-SWM100VAH + EHST20D-*M*D
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

7.5 kW

7.5 kW

El input

1.55 kW

2.68 kW

COP

4.85

2.8

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

60 dB(A)

60 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

174 %

127 %

Prated

7.8 kW

7.5 kW

SCOP

4.43

3.26

Tbiv

-10 °C

-7 °C

TOL

-25 °C

-25 °C

Pdh Tj = -7°C

6.9 kW

6.63 kW

COP Tj = -7°C

2.79

1.68

Cdh Tj = -7 °C

0.994

0.996

Pdh Tj = +2°C

4.5 kW

4.1 kW

COP Tj = +2°C

4.43

3.23

Cdh Tj = +2 °C

0.985

0.988

Pdh Tj = +7°C

3.4 kW

3.5 kW

COP Tj = +7°C

5.89

4.8

Cdh Tj = +7 °C

0.974

0.979

Pdh Tj = 12°C

3.7 kW

3.9 kW

COP Tj = 12°C

7.04

6.78

Cdh Tj = +12 °C

0.971

0.974

Pdh Tj = Tbiv

7.8 kW

6.63 kW

COP Tj = Tbiv

2.22

1.68

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

7.8 kW

6.1 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.22

1.59

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.996

0.996

WTOL

60 °C

60 °C

Poff

15 W

15 W

PTO

15 W

15 W

PSB

15 W

15 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0 kW

1.4 kW

Annual energy consumption Qhe

3640 kWh

4758 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

144 %

COP

3.5

Heating up time

1:49 h:min

Standby power input

25 W

Reference hot water temperature

51.5 °C

Mixed water at 40°C

274 l

SUZ-SWM100VAH + ERST20D-*M*D
Configure model
Model name
SUZ-SWM100VAH + ERST20D-*M*D
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

7.5 kW

7.5 kW

El input

1.55 kW

2.68 kW

COP

4.85

2.8

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

60 dB(A)

60 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

177 %

129 %

Prated

7.8 kW

7.5 kW

SCOP

4.5

3.29

Tbiv

-10 °C

-7 °C

TOL

-25 °C

-25 °C

Pdh Tj = -7°C

6.9 kW

6.63 kW

COP Tj = -7°C

2.79

1.68

Cdh Tj = -7 °C

0.994

0.996

Pdh Tj = +2°C

4.5 kW

4.1 kW

COP Tj = +2°C

4.43

3.23

Cdh Tj = +2 °C

0.985

0.988

Pdh Tj = +7°C

3.4 kW

3.5 kW

COP Tj = +7°C

5.89

4.8

Cdh Tj = +7 °C

0.974

0.979

Pdh Tj = 12°C

3.7 kW

3.9 kW

COP Tj = 12°C

7.04

6.78

Cdh Tj = +12 °C

0.971

0.974

Pdh Tj = Tbiv

7.8 kW

6.63 kW

COP Tj = Tbiv

2.22

1.68

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

7.8 kW

6.1 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.22

1.59

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.996

0.996

WTOL

60 °C

60 °C

Poff

15 W

15 W

PTO

15 W

15 W

PSB

15 W

15 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0 kW

1.4 kW

Annual energy consumption Qhe

3585 kWh

4703 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

144 %

COP

3.5

Heating up time

1:49 h:min

Standby power input

25 W

Reference hot water temperature

51.5 °C

Mixed water at 40°C

274 l

SUZ-SWM100VAH + EHSD-M*D
Configure model
Model name
SUZ-SWM100VAH + EHSD-M*D
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

7.5 kW

7.5 kW

El input

1.55 kW

2.68 kW

COP

4.85

2.8

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

60 dB(A)

60 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

174 %

127 %

Prated

7.8 kW

7.5 kW

SCOP

4.43

3.26

Tbiv

-10 °C

-7 °C

TOL

-25 °C

-25 °C

Pdh Tj = -7°C

6.9 kW

6.63 kW

COP Tj = -7°C

2.79

1.68

Cdh Tj = -7 °C

0.994

0.996

Pdh Tj = +2°C

4.5 kW

4.1 kW

COP Tj = +2°C

4.43

3.23

Cdh Tj = +2 °C

0.985

0.988

Pdh Tj = +7°C

3.4 kW

3.5 kW

COP Tj = +7°C

5.89

4.8

Cdh Tj = +7 °C

0.974

0.979

Pdh Tj = 12°C

3.7 kW

3.9 kW

COP Tj = 12°C

7.04

6.78

Cdh Tj = +12 °C

0.971

0.974

Pdh Tj = Tbiv

7.8 kW

6.63 kW

COP Tj = Tbiv

2.22

1.68

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

7.8 kW

6.1 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.22

1.59

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.996

0.996

WTOL

60 °C

60 °C

Poff

15 W

15 W

PTO

15 W

15 W

PSB

15 W

15 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0 kW

1.4 kW

Annual energy consumption Qhe

3640 kWh

4758 kWh

SUZ-SWM100VAH + EHSD-*M*D
Configure model
Model name
SUZ-SWM100VAH + EHSD-*M*D
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

7.5 kW

7.5 kW

El input

1.55 kW

2.68 kW

COP

4.85

2.8

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

60 dB(A)

60 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

174 %

127 %

Prated

7.8 kW

7.5 kW

SCOP

4.43

3.26

Tbiv

-10 °C

-7 °C

TOL

-25 °C

-25 °C

Pdh Tj = -7°C

6.9 kW

6.63 kW

COP Tj = -7°C

2.79

1.68

Cdh Tj = -7 °C

0.994

0.996

Pdh Tj = +2°C

4.5 kW

4.1 kW

COP Tj = +2°C

4.43

3.23

Cdh Tj = +2 °C

0.985

0.988

Pdh Tj = +7°C

3.4 kW

3.5 kW

COP Tj = +7°C

5.89

4.8

Cdh Tj = +7 °C

0.974

0.979

Pdh Tj = 12°C

3.7 kW

3.9 kW

COP Tj = 12°C

7.04

6.78

Cdh Tj = +12 °C

0.971

0.974

Pdh Tj = Tbiv

7.8 kW

6.63 kW

COP Tj = Tbiv

2.22

1.68

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

7.8 kW

6.1 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.22

1.59

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.996

0.996

WTOL

60 °C

60 °C

Poff

15 W

15 W

PTO

15 W

15 W

PSB

15 W

15 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0 kW

1.4 kW

Annual energy consumption Qhe

3640 kWh

4758 kWh

SUZ-SWM100VAH + ERSD-M*D
Configure model
Model name
SUZ-SWM100VAH + ERSD-M*D
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

7.5 kW

7.5 kW

El input

1.55 kW

2.68 kW

COP

4.85

2.8

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

60 dB(A)

60 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

177 %

129 %

Prated

7.8 kW

7.5 kW

SCOP

4.5

3.29

Tbiv

-10 °C

-7 °C

TOL

-25 °C

-25 °C

Pdh Tj = -7°C

6.9 kW

6.63 kW

COP Tj = -7°C

2.79

1.68

Cdh Tj = -7 °C

0.994

0.996

Pdh Tj = +2°C

4.5 kW

4.1 kW

COP Tj = +2°C

4.43

3.23

Cdh Tj = +2 °C

0.985

0.988

Pdh Tj = +7°C

3.4 kW

3.5 kW

COP Tj = +7°C

5.89

4.8

Cdh Tj = +7 °C

0.974

0.979

Pdh Tj = 12°C

3.7 kW

3.9 kW

COP Tj = 12°C

7.04

6.78

Cdh Tj = +12 °C

0.971

0.974

Pdh Tj = Tbiv

7.8 kW

6.63 kW

COP Tj = Tbiv

2.22

1.68

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

7.8 kW

6.1 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.22

1.59

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.996

0.996

WTOL

60 °C

60 °C

Poff

15 W

15 W

PTO

15 W

15 W

PSB

15 W

15 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0 kW

1.4 kW

Annual energy consumption Qhe

3585 kWh

4703 kWh

SUZ-SWM100VAH + ERSD-*M*D
Configure model
Model name
SUZ-SWM100VAH + ERSD-*M*D
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

7.5 kW

7.5 kW

El input

1.55 kW

2.68 kW

COP

4.85

2.8

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

60 dB(A)

60 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

177 %

129 %

Prated

7.8 kW

7.5 kW

SCOP

4.5

3.29

Tbiv

-10 °C

-7 °C

TOL

-25 °C

-25 °C

Pdh Tj = -7°C

6.9 kW

6.63 kW

COP Tj = -7°C

2.79

1.68

Cdh Tj = -7 °C

0.994

0.996

Pdh Tj = +2°C

4.5 kW

4.1 kW

COP Tj = +2°C

4.43

3.23

Cdh Tj = +2 °C

0.985

0.988

Pdh Tj = +7°C

3.4 kW

3.5 kW

COP Tj = +7°C

5.89

4.8

Cdh Tj = +7 °C

0.974

0.979

Pdh Tj = 12°C

3.7 kW

3.9 kW

COP Tj = 12°C

7.04

6.78

Cdh Tj = +12 °C

0.971

0.974

Pdh Tj = Tbiv

7.8 kW

6.63 kW

COP Tj = Tbiv

2.22

1.68

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

7.8 kW

6.1 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.22

1.59

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.996

0.996

WTOL

60 °C

60 °C

Poff

15 W

15 W

PTO

15 W

15 W

PSB

15 W

15 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0 kW

1.4 kW

Annual energy consumption Qhe

3585 kWh

4703 kWh

SUZ-SHWM60VAH + ERST20D-*M*E
Configure model
Model name
SUZ-SHWM60VAH + ERST20D-*M*E
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
+7°C/12°C and +18°C/+23°C
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

5 kW

5 kW

El input

1.01 kW

1.7 kW

COP

4.95

2.94

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Cooling

EN 14511-2

+7°C/+12°C

+18°C/+23°C

El input

1.83 kW

1.15 kW

Cooling capacity

6

6

EER

3.28

5.21

EN 14825

+7°C/+12°C

+18°C/+23°C

Pdesignc

6 kW

6 kW

SEER

5.19

7.02

Pdc Tj = 35°C

6 kW

6 kW

EER Tj = 35°C

3.28

5.21

Cdc Tj = 35 °C

0.992

0.987

Pdc Tj = 30°C

4.42 kW

4.42 kW

EER Tj = 30°C

4.45

6.5

Cdc Tj = 30 °C

0.985

0.978

Pdc Tj = 25°C

2.84 kW

3.4 kW

EER Tj = 25°C

5.93

8.66

Cdc Tj = 25 °C

0.969

0.962

Pdc Tj = 20°C

2.8 kW

3.8 kW

EER Tj = 20°C

7.41

8.28

Cdc Tj = 20 °C

0.96

0.967

Poff

15 W

15 W

PTO

15 W

15 W

PSB

15 W

15 W

PCK

0 W

0 W

Annual energy consumption Qce

694 kWh

513 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

57 dB(A)

57 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

178 %

128 %

Prated

6.1 kW

6 kW

SCOP

4.53

3.27

Tbiv

-10 °C

-7 °C

TOL

-25 °C

-25 °C

Pdh Tj = -7°C

5.4 kW

5.31 kW

COP Tj = -7°C

2.78

1.85

Cdh Tj = -7 °C

0.992

0.995

Pdh Tj = +2°C

4.1 kW

3.7 kW

COP Tj = +2°C

4.43

3.13

Cdh Tj = +2 °C

0.984

0.987

Pdh Tj = +7°C

3.4 kW

3.1 kW

COP Tj = +7°C

6.27

4.66

Cdh Tj = +7 °C

0.972

0.977

Pdh Tj = 12°C

3.7 kW

3.9 kW

COP Tj = 12°C

7.11

6.53

Cdh Tj = +12 °C

0.971

0.975

Pdh Tj = Tbiv

6.1 kW

5.31 kW

COP Tj = Tbiv

2.26

1.85

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

6.1 kW

5.8 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.26

1.64

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.994

0.996

WTOL

60 °C

60 °C

Poff

15 W

15 W

PTO

15 W

15 W

PSB

15 W

15 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0 kW

0.2 kW

Annual energy consumption Qhe

2783 kWh

3794 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

148 %

COP

3.58

Heating up time

2:11 h:min

Standby power input

25.4 W

Reference hot water temperature

51.5 °C

Mixed water at 40°C

274 l

SUZ-SHWM60VAH + ERSD-*M*E
Configure model
Model name
SUZ-SHWM60VAH + ERSD-*M*E
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
+7°C/12°C and +18°C/+23°C
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

5 kW

5 kW

El input

1.01 kW

1.7 kW

COP

4.95

2.94

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Cooling

EN 14511-2

+7°C/+12°C

+18°C/+23°C

El input

1.83 kW

1.15 kW

Cooling capacity

6

6

EER

3.28

5.21

EN 14825

+7°C/+12°C

+18°C/+23°C

Pdesignc

6 kW

6 kW

SEER

5.19

7.02

Pdc Tj = 35°C

6 kW

6 kW

EER Tj = 35°C

3.28

5.21

Cdc Tj = 35 °C

0.992

0.987

Pdc Tj = 30°C

4.42 kW

4.42 kW

EER Tj = 30°C

4.45

6.5

Cdc Tj = 30 °C

0.985

0.978

Pdc Tj = 25°C

2.84 kW

3.4 kW

EER Tj = 25°C

5.93

8.66

Cdc Tj = 25 °C

0.969

0.962

Pdc Tj = 20°C

2.8 kW

3.8 kW

EER Tj = 20°C

7.41

8.28

Cdc Tj = 20 °C

0.96

0.967

Poff

15 W

15 W

PTO

15 W

15 W

PSB

15 W

15 W

PCK

0 W

0 W

Annual energy consumption Qce

694 kWh

513 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

57 dB(A)

57 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

178 %

128 %

Prated

6.1 kW

6 kW

SCOP

4.53

3.27

Tbiv

-10 °C

-7 °C

TOL

-25 °C

-25 °C

Pdh Tj = -7°C

5.4 kW

5.31 kW

COP Tj = -7°C

2.78

1.85

Cdh Tj = -7 °C

0.992

0.995

Pdh Tj = +2°C

4.1 kW

3.7 kW

COP Tj = +2°C

4.43

3.13

Cdh Tj = +2 °C

0.984

0.987

Pdh Tj = +7°C

3.4 kW

3.1 kW

COP Tj = +7°C

6.27

4.66

Cdh Tj = +7 °C

0.972

0.977

Pdh Tj = 12°C

3.7 kW

3.9 kW

COP Tj = 12°C

7.11

6.53

Cdh Tj = +12 °C

0.971

0.975

Pdh Tj = Tbiv

6.1 kW

5.31 kW

COP Tj = Tbiv

2.26

1.85

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

6.1 kW

5.8 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.26

1.64

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.994

0.996

WTOL

60 °C

60 °C

Poff

15 W

15 W

PTO

15 W

15 W

PSB

15 W

15 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0 kW

0.2 kW

Annual energy consumption Qhe

2783 kWh

3794 kWh

SUZ-SWM80VA2 + EHST20D-*M*E
Configure model
Model name
SUZ-SWM80VA2 + EHST20D-*M*E
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

6 kW

6 kW

El input

1.18 kW

2 kW

COP

5.1

3

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Cooling

EN 14511-2

+7°C/+12°C

+18°C/+23°C

El input

2.09 kW

1.32 kW

Cooling capacity

6.7

6.7

EER

3.2

5.06

EN 14825

+7°C/+12°C

+18°C/+23°C

Pdesignc

6.7 kW

6.7 kW

SEER

5.16

6.97

Pdc Tj = 35°C

6.7 kW

6.7 kW

EER Tj = 35°C

3.2

5.06

Cdc Tj = 35 °C

0.993

0.989

Pdc Tj = 30°C

4.94 kW

4.94 kW

EER Tj = 30°C

4.35

6.38

Cdc Tj = 30 °C

0.987

0.981

Pdc Tj = 25°C

3.17 kW

3.6 kW

EER Tj = 25°C

5.96

8.53

Cdc Tj = 25 °C

0.972

0.964

Pdc Tj = 20°C

2.8 kW

3.8 kW

EER Tj = 20°C

7.2

8.12

Cdc Tj = 20 °C

0.961

0.968

Poff

15 W

15 W

PTO

15 W

15 W

PSB

15 W

15 W

PCK

0 W

0 W

Annual energy consumption Qce

779 kWh

577 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

59 dB(A)

59 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

183 %

133 %

Prated

6.6 kW

7 kW

SCOP

4.66

3.39

Tbiv

-10 °C

-7 °C

TOL

-25 °C

-25 °C

Pdh Tj = -7°C

5.9 kW

6.2 kW

COP Tj = -7°C

3.16

1.91

Cdh Tj = -7 °C

0.992

0.995

Pdh Tj = +2°C

4.4 kW

3.8 kW

COP Tj = +2°C

4.61

3.39

Cdh Tj = +2 °C

0.984

0.987

Pdh Tj = +7°C

3.4 kW

3.1 kW

COP Tj = +7°C

6.22

4.69

Cdh Tj = +7 °C

0.973

0.977

Pdh Tj = 12°C

3.7 kW

3.9 kW

COP Tj = 12°C

7.38

6.67

Cdh Tj = +12 °C

0.97

0.974

Pdh Tj = Tbiv

6.6 kW

6.2 kW

COP Tj = Tbiv

2.4

1.91

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

6.6 kW

5.8 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.4

1.68

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.995

0.996

WTOL

60 °C

60 °C

Poff

15 W

15 W

PTO

15 W

15 W

PSB

15 W

15 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0 kW

1.2 kW

Annual energy consumption Qhe

2929 kWh

4262 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

148 %

COP

3.58

Heating up time

2:11 h:min

Standby power input

25.4 W

Reference hot water temperature

51.5 °C

Mixed water at 40°C

274 l

SUZ-SWM80VA2 + ERST20D-*M*E
Configure model
Model name
SUZ-SWM80VA2 + ERST20D-*M*E
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
+7°C/12°C and +18°C/+23°C
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

6 kW

6 kW

El input

1.18 kW

2 kW

COP

5.1

3

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Cooling

EN 14511-2

+7°C/+12°C

+18°C/+23°C

El input

2.09 kW

1.32 kW

Cooling capacity

6.7

6.7

EER

3.2

5.06

EN 14825

+7°C/+12°C

+18°C/+23°C

Pdesignc

6.7 kW

6.7 kW

SEER

5.16

6.97

Pdc Tj = 35°C

6.7 kW

6.7 kW

EER Tj = 35°C

3.2

5.06

Cdc Tj = 35 °C

0.993

0.989

Pdc Tj = 30°C

4.94 kW

4.94 kW

EER Tj = 30°C

4.35

6.38

Cdc Tj = 30 °C

0.987

0.981

Pdc Tj = 25°C

3.17 kW

3.6 kW

EER Tj = 25°C

5.96

8.53

Cdc Tj = 25 °C

0.972

0.964

Pdc Tj = 20°C

2.8 kW

3.8 kW

EER Tj = 20°C

7.2

8.12

Cdc Tj = 20 °C

0.961

0.968

Poff

15 W

15 W

PTO

15 W

15 W

PSB

15 W

15 W

PCK

0 W

0 W

Annual energy consumption Qce

779 kWh

577 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

59 dB(A)

59 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

187 %

135 %

Prated

6.6 kW

7 kW

SCOP

4.74

3.44

Tbiv

-10 °C

-7 °C

TOL

-25 °C

-25 °C

Pdh Tj = -7°C

5.9 kW

6.2 kW

COP Tj = -7°C

3.16

1.91

Cdh Tj = -7 °C

0.992

0.995

Pdh Tj = +2°C

4.4 kW

3.8 kW

COP Tj = +2°C

4.61

3.39

Cdh Tj = +2 °C

0.984

0.987

Pdh Tj = +7°C

3.4 kW

3.1 kW

COP Tj = +7°C

6.22

4.69

Cdh Tj = +7 °C

0.973

0.977

Pdh Tj = 12°C

3.7 kW

3.9 kW

COP Tj = 12°C

7.38

6.67

Cdh Tj = +12 °C

0.97

0.974

Pdh Tj = Tbiv

6.6 kW

6.2 kW

COP Tj = Tbiv

2.4

1.91

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

6.6 kW

5.8 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.4

1.68

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.995

0.996

WTOL

60 °C

60 °C

Poff

15 W

15 W

PTO

15 W

15 W

PSB

15 W

15 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0 kW

1.2 kW

Annual energy consumption Qhe

2874 kWh

4207 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

148 %

COP

3.58

Heating up time

2:11 h:min

Standby power input

25.4 W

Reference hot water temperature

51.5 °C

Mixed water at 40°C

274 l

SUZ-SWM80VA2 + EHSD-*M*E
Configure model
Model name
SUZ-SWM80VA2 + EHSD-*M*E
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

6 kW

6 kW

El input

1.18 kW

2 kW

COP

5.1

3

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Cooling

EN 14511-2

+7°C/+12°C

+18°C/+23°C

El input

2.09 kW

1.32 kW

Cooling capacity

6.7

6.7

EER

3.2

5.06

EN 14825

+7°C/+12°C

+18°C/+23°C

Pdesignc

6.7 kW

6.7 kW

SEER

5.16

6.97

Pdc Tj = 35°C

6.7 kW

6.7 kW

EER Tj = 35°C

3.2

5.06

Cdc Tj = 35 °C

0.993

0.989

Pdc Tj = 30°C

4.94 kW

4.94 kW

EER Tj = 30°C

4.35

6.38

Cdc Tj = 30 °C

0.987

0.981

Pdc Tj = 25°C

3.17 kW

3.6 kW

EER Tj = 25°C

5.96

8.53

Cdc Tj = 25 °C

0.972

0.964

Pdc Tj = 20°C

2.8 kW

3.8 kW

EER Tj = 20°C

7.2

8.12

Cdc Tj = 20 °C

0.961

0.968

Poff

15 W

15 W

PTO

15 W

15 W

PSB

15 W

15 W

PCK

0 W

0 W

Annual energy consumption Qce

779 kWh

577 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

59 dB(A)

59 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

183 %

133 %

Prated

6.6 kW

7 kW

SCOP

4.66

3.39

Tbiv

-10 °C

-7 °C

TOL

-25 °C

-25 °C

Pdh Tj = -7°C

5.9 kW

6.2 kW

COP Tj = -7°C

3.16

1.91

Cdh Tj = -7 °C

0.992

0.995

Pdh Tj = +2°C

4.4 kW

3.8 kW

COP Tj = +2°C

4.61

3.39

Cdh Tj = +2 °C

0.984

0.987

Pdh Tj = +7°C

3.4 kW

3.1 kW

COP Tj = +7°C

6.22

4.69

Cdh Tj = +7 °C

0.973

0.977

Pdh Tj = 12°C

3.7 kW

3.9 kW

COP Tj = 12°C

7.38

6.67

Cdh Tj = +12 °C

0.97

0.974

Pdh Tj = Tbiv

6.6 kW

6.2 kW

COP Tj = Tbiv

2.4

1.91

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

6.6 kW

5.8 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.4

1.68

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.995

0.996

WTOL

60 °C

60 °C

Poff

15 W

15 W

PTO

15 W

15 W

PSB

15 W

15 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0 kW

1.2 kW

Annual energy consumption Qhe

2929 kWh

4262 kWh

SUZ-SWM80VA2 + ERSD-*M*E
Configure model
Model name
SUZ-SWM80VA2 + ERSD-*M*E
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
+7°C/12°C and +18°C/+23°C
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

6 kW

6 kW

El input

1.18 kW

2 kW

COP

5.1

3

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Cooling

EN 14511-2

+7°C/+12°C

+18°C/+23°C

El input

2.09 kW

1.32 kW

Cooling capacity

6.7

6.7

EER

3.2

5.06

EN 14825

+7°C/+12°C

+18°C/+23°C

Pdesignc

6.7 kW

6.7 kW

SEER

5.16

6.97

Pdc Tj = 35°C

6.7 kW

6.7 kW

EER Tj = 35°C

3.2

5.06

Cdc Tj = 35 °C

0.993

0.989

Pdc Tj = 30°C

4.94 kW

4.94 kW

EER Tj = 30°C

4.35

6.38

Cdc Tj = 30 °C

0.987

0.981

Pdc Tj = 25°C

3.17 kW

3.6 kW

EER Tj = 25°C

5.96

8.53

Cdc Tj = 25 °C

0.972

0.964

Pdc Tj = 20°C

2.8 kW

3.8 kW

EER Tj = 20°C

7.2

8.12

Cdc Tj = 20 °C

0.961

0.968

Poff

15 W

15 W

PTO

15 W

15 W

PSB

15 W

15 W

PCK

0 W

0 W

Annual energy consumption Qce

779 kWh

577 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

59 dB(A)

59 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

187 %

135 %

Prated

6.6 kW

7 kW

SCOP

4.74

3.44

Tbiv

-10 °C

-7 °C

TOL

-25 °C

-25 °C

Pdh Tj = -7°C

5.9 kW

6.2 kW

COP Tj = -7°C

3.16

1.91

Cdh Tj = -7 °C

0.992

0.995

Pdh Tj = +2°C

4.4 kW

3.8 kW

COP Tj = +2°C

4.61

3.39

Cdh Tj = +2 °C

0.984

0.987

Pdh Tj = +7°C

3.4 kW

3.1 kW

COP Tj = +7°C

6.22

4.69

Cdh Tj = +7 °C

0.973

0.977

Pdh Tj = 12°C

3.7 kW

3.9 kW

COP Tj = 12°C

7.38

6.67

Cdh Tj = +12 °C

0.97

0.974

Pdh Tj = Tbiv

6.6 kW

6.2 kW

COP Tj = Tbiv

2.4

1.91

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

6.6 kW

5.8 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.4

1.68

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.995

0.996

WTOL

60 °C

60 °C

Poff

15 W

15 W

PTO

15 W

15 W

PSB

15 W

15 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0 kW

1.2 kW

Annual energy consumption Qhe

2874 kWh

4207 kWh

SUZ-SWM100VA + EHST20D-*M*E
Configure model
Model name
SUZ-SWM100VA + EHST20D-*M*E
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

7.5 kW

7.5 kW

El input

1.55 kW

2.68 kW

COP

4.85

2.8

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Cooling

EN 14511-2

+7°C/+12°C

+18°C/+23°C

El input

2.43 kW

1.82 kW

Cooling capacity

7.3

8.1

EER

3

4.44

EN 14825

+7°C/+12°C

+18°C/+23°C

Pdesignc

7.3 kW

8.1 kW

SEER

5.08

6.74

Pdc Tj = 35°C

7.3 kW

8.1 kW

EER Tj = 35°C

3

4.44

Cdc Tj = 35 °C

0.994

0.992

Pdc Tj = 30°C

5.38 kW

5.97 kW

EER Tj = 30°C

4.24

6.05

Cdc Tj = 30 °C

0.988

0.985

Pdc Tj = 25°C

3.46 kW

4.2 kW

EER Tj = 25°C

5.94

8.29

Cdc Tj = 25 °C

0.974

0.97

Pdc Tj = 20°C

2.8 kW

3.9 kW

EER Tj = 20°C

7

7.72

Cdc Tj = 20 °C

0.963

0.97

Poff

15 W

15 W

PTO

15 W

15 W

PSB

15 W

15 W

PCK

0 W

0 W

Annual energy consumption Qce

863 kWh

722 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

60 dB(A)

60 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

179 %

133 %

Prated

7.8 kW

7.5 kW

SCOP

4.54

3.39

Tbiv

-10 °C

-7 °C

TOL

-25 °C

-25 °C

Pdh Tj = -7°C

6.9 kW

6.63 kW

COP Tj = -7°C

2.99

1.8

Cdh Tj = -7 °C

0.993

0.996

Pdh Tj = +2°C

4.5 kW

4.1 kW

COP Tj = +2°C

4.57

3.41

Cdh Tj = +2 °C

0.985

0.988

Pdh Tj = +7°C

3.4 kW

3.5 kW

COP Tj = +7°C

5.84

4.79

Cdh Tj = +7 °C

0.974

0.979

Pdh Tj = 12°C

3.7 kW

3.9 kW

COP Tj = 12°C

6.98

6.9

Cdh Tj = +12 °C

0.972

0.973

Pdh Tj = Tbiv

7.8 kW

6.63 kW

COP Tj = Tbiv

2.34

1.8

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

7.8 kW

6.1 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.34

1.69

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.995

0.996

WTOL

60 °C

60 °C

Poff

15 W

15 W

PTO

15 W

15 W

PSB

15 W

15 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0 kW

1.4 kW

Annual energy consumption Qhe

3548 kWh

4567 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

148 %

COP

3.58

Heating up time

2:11 h:min

Standby power input

25.4 W

Reference hot water temperature

51.5 °C

Mixed water at 40°C

274 l

SUZ-SWM100VA + ERST20D-*M*E
Configure model
Model name
SUZ-SWM100VA + ERST20D-*M*E
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
+7°C/12°C and +18°C/+23°C
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

7.5 kW

7.5 kW

El input

1.55 kW

2.68 kW

COP

4.85

2.8

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Cooling

EN 14511-2

+7°C/+12°C

+18°C/+23°C

El input

2.43 kW

1.82 kW

Cooling capacity

7.3

8.1

EER

3

4.44

EN 14825

+7°C/+12°C

+18°C/+23°C

Pdesignc

7.3 kW

8.1 kW

SEER

5.08

6.74

Pdc Tj = 35°C

7.3 kW

8.1 kW

EER Tj = 35°C

3

4.44

Cdc Tj = 35 °C

0.994

0.992

Pdc Tj = 30°C

5.38 kW

5.97 kW

EER Tj = 30°C

4.24

6.05

Cdc Tj = 30 °C

0.988

0.985

Pdc Tj = 25°C

3.46 kW

4.2 kW

EER Tj = 25°C

5.94

8.29

Cdc Tj = 25 °C

0.974

0.97

Pdc Tj = 20°C

2.8 kW

3.9 kW

EER Tj = 20°C

7

7.72

Cdc Tj = 20 °C

0.963

0.97

Poff

15 W

15 W

PTO

15 W

15 W

PSB

15 W

15 W

PCK

0 W

0 W

Annual energy consumption Qce

863 kWh

722 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

60 dB(A)

60 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

182 %

134 %

Prated

7.8 kW

7.5 kW

SCOP

4.61

3.43

Tbiv

-10 °C

-7 °C

TOL

-25 °C

-25 °C

Pdh Tj = -7°C

6.9 kW

6.63 kW

COP Tj = -7°C

2.99

1.8

Cdh Tj = -7 °C

0.993

0.996

Pdh Tj = +2°C

4.5 kW

4.1 kW

COP Tj = +2°C

4.57

3.41

Cdh Tj = +2 °C

0.985

0.988

Pdh Tj = +7°C

3.4 kW

3.5 kW

COP Tj = +7°C

5.84

4.79

Cdh Tj = +7 °C

0.974

0.979

Pdh Tj = 12°C

3.7 kW

3.9 kW

COP Tj = 12°C

6.98

6.9

Cdh Tj = +12 °C

0.972

0.973

Pdh Tj = Tbiv

7.8 kW

6.63 kW

COP Tj = Tbiv

2.34

1.8

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

7.8 kW

6.1 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.34

1.69

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.995

0.996

WTOL

60 °C

60 °C

Poff

15 W

15 W

PTO

15 W

15 W

PSB

15 W

15 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0 kW

1.4 kW

Annual energy consumption Qhe

3492 kWh

4512 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

148 %

COP

3.58

Heating up time

2:11 h:min

Standby power input

25.4 W

Reference hot water temperature

51.5 °C

Mixed water at 40°C

274 l

SUZ-SWM100VA + EHSD-*M*E
Configure model
Model name
SUZ-SWM100VA + EHSD-*M*E
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

7.5 kW

7.5 kW

El input

1.55 kW

2.68 kW

COP

4.85

2.8

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Cooling

EN 14511-2

+7°C/+12°C

+18°C/+23°C

El input

2.43 kW

1.82 kW

Cooling capacity

7.3

8.1

EER

3

4.44

EN 14825

+7°C/+12°C

+18°C/+23°C

Pdesignc

7.3 kW

8.1 kW

SEER

5.08

6.74

Pdc Tj = 35°C

7.3 kW

8.1 kW

EER Tj = 35°C

3

4.44

Cdc Tj = 35 °C

0.994

0.992

Pdc Tj = 30°C

5.38 kW

5.97 kW

EER Tj = 30°C

4.24

6.05

Cdc Tj = 30 °C

0.988

0.985

Pdc Tj = 25°C

3.46 kW

4.2 kW

EER Tj = 25°C

5.94

8.29

Cdc Tj = 25 °C

0.974

0.97

Pdc Tj = 20°C

2.8 kW

3.9 kW

EER Tj = 20°C

7

7.72

Cdc Tj = 20 °C

0.963

0.97

Poff

15 W

15 W

PTO

15 W

15 W

PSB

15 W

15 W

PCK

0 W

0 W

Annual energy consumption Qce

863 kWh

722 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

60 dB(A)

60 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

179 %

133 %

Prated

7.8 kW

7.5 kW

SCOP

4.54

3.39

Tbiv

-10 °C

-7 °C

TOL

-25 °C

-25 °C

Pdh Tj = -7°C

6.9 kW

6.63 kW

COP Tj = -7°C

2.99

1.8

Cdh Tj = -7 °C

0.993

0.996

Pdh Tj = +2°C

4.5 kW

4.1 kW

COP Tj = +2°C

4.57

3.41

Cdh Tj = +2 °C

0.985

0.988

Pdh Tj = +7°C

3.4 kW

3.5 kW

COP Tj = +7°C

5.84

4.79

Cdh Tj = +7 °C

0.974

0.979

Pdh Tj = 12°C

3.7 kW

3.9 kW

COP Tj = 12°C

6.98

6.9

Cdh Tj = +12 °C

0.972

0.973

Pdh Tj = Tbiv

7.8 kW

6.63 kW

COP Tj = Tbiv

2.34

1.8

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

7.8 kW

6.1 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.34

1.69

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.995

0.996

WTOL

60 °C

60 °C

Poff

15 W

15 W

PTO

15 W

15 W

PSB

15 W

15 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0 kW

1.4 kW

Annual energy consumption Qhe

3548 kWh

4567 kWh

SUZ-SWM100VA + ERSD-*M*E
Configure model
Model name
SUZ-SWM100VA + ERSD-*M*E
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
+7°C/12°C and +18°C/+23°C
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

7.5 kW

7.5 kW

El input

1.55 kW

2.68 kW

COP

4.85

2.8

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Cooling

EN 14511-2

+7°C/+12°C

+18°C/+23°C

El input

2.43 kW

1.82 kW

Cooling capacity

7.3

8.1

EER

3

4.44

EN 14825

+7°C/+12°C

+18°C/+23°C

Pdesignc

7.3 kW

8.1 kW

SEER

5.08

6.74

Pdc Tj = 35°C

7.3 kW

8.1 kW

EER Tj = 35°C

3

4.44

Cdc Tj = 35 °C

0.994

0.992

Pdc Tj = 30°C

5.38 kW

5.97 kW

EER Tj = 30°C

4.24

6.05

Cdc Tj = 30 °C

0.988

0.985

Pdc Tj = 25°C

3.46 kW

4.2 kW

EER Tj = 25°C

5.94

8.29

Cdc Tj = 25 °C

0.974

0.97

Pdc Tj = 20°C

2.8 kW

3.9 kW

EER Tj = 20°C

7

7.72

Cdc Tj = 20 °C

0.963

0.97

Poff

15 W

15 W

PTO

15 W

15 W

PSB

15 W

15 W

PCK

0 W

0 W

Annual energy consumption Qce

863 kWh

722 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

60 dB(A)

60 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

182 %

134 %

Prated

7.8 kW

7.5 kW

SCOP

4.61

3.43

Tbiv

-10 °C

-7 °C

TOL

-25 °C

-25 °C

Pdh Tj = -7°C

6.9 kW

6.63 kW

COP Tj = -7°C

2.99

1.8

Cdh Tj = -7 °C

0.993

0.996

Pdh Tj = +2°C

4.5 kW

4.1 kW

COP Tj = +2°C

4.57

3.41

Cdh Tj = +2 °C

0.985

0.988

Pdh Tj = +7°C

3.4 kW

3.5 kW

COP Tj = +7°C

5.84

4.79

Cdh Tj = +7 °C

0.974

0.979

Pdh Tj = 12°C

3.7 kW

3.9 kW

COP Tj = 12°C

6.98

6.9

Cdh Tj = +12 °C

0.972

0.973

Pdh Tj = Tbiv

7.8 kW

6.63 kW

COP Tj = Tbiv

2.34

1.8

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

7.8 kW

6.1 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.34

1.69

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.995

0.996

WTOL

60 °C

60 °C

Poff

15 W

15 W

PTO

15 W

15 W

PSB

15 W

15 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0 kW

1.4 kW

Annual energy consumption Qhe

3492 kWh

4512 kWh