Certificate holders

Subtype

Ecodan Eco Inverter 4/6H+170D

Certificate Holder
Mitsubishi Electric Air Conditioning Systems Europe LTD
Nettlehill Road, Houston Industrial Estate
EH54 5EQ Livingston
United Kingdom
Registration number
037-0087-22 / rev. 1
Certification Body
SZU - Strojirensky zkusebni ustav (Engineering Test Institute, Public Enterprise)
Subtype title
Ecodan Eco Inverter 4/6H+170D
Driving energy
Electricity
Heat Pump Type
Outdoor Air/Water
Refrigerant
R32
Mass of Refrigerant

0,800 kg

Certification Date
02.11.2022
Testing basis
HP Keymark scheme rules rev. no. 11
Generate PDF Export model CSV Download certificate
  • Number of models 11

Models

SUZ-SHWM40VAH + EHST17D-*M*D
Configure model
Model name
SUZ-SHWM40VAH + EHST17D-*M*D
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

3 kW

3.6 kW

El input

0.63 kW

1.29 kW

COP

4.77

2.79

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

56 dB(A)

56 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

172 %

124 %

Prated

5 kW

4.6 kW

SCOP

4.37

3.17

Tbiv

-10 °C

-10 °C

TOL

-25 °C

-25 °C

Pdh Tj = -7°C

4.5 kW

4.1 kW

COP Tj = -7°C

2.57

2.14

Cdh Tj = -7 °C

0.991

0.992

Pdh Tj = +2°C

3.2 kW

2.8 kW

COP Tj = +2°C

4.29

2.91

Cdh Tj = +2 °C

0.98

0.984

Pdh Tj = +7°C

3 kW

2.6 kW

COP Tj = +7°C

6.19

4.62

Cdh Tj = +7 °C

0.969

0.973

Pdh Tj = 12°C

3.4 kW

3 kW

COP Tj = 12°C

10.44

7.16

Cdh Tj = +12 °C

0.954

0.964

Pdh Tj = Tbiv

5 kW

4.6 kW

COP Tj = Tbiv

2.37

1.66

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

5 kW

4.6 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.37

1.66

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.993

0.995

WTOL

60 °C

60 °C

Poff

15 W

15 W

PTO

15 W

15 W

PSB

15 W

15 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0 kW

0 kW

Annual energy consumption Qhe

2366 kWh

2994 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

139 %

COP

3.36

Heating up time

2:48 h:min

Standby power input

30 W

Reference hot water temperature

53 °C

Mixed water at 40°C

239 l

SUZ-SHWM40VAH + ERST17D-*M*D
Configure model
Model name
SUZ-SHWM40VAH + ERST17D-*M*D
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

3 kW

3.6 kW

El input

0.63 kW

1.29 kW

COP

4.77

2.79

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

56 dB(A)

56 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

176 %

126 %

Prated

5 kW

4.6 kW

SCOP

4.47

3.23

Tbiv

-10 °C

-10 °C

TOL

-25 °C

-25 °C

Pdh Tj = -7°C

4.5 kW

4.1 kW

COP Tj = -7°C

2.57

2.14

Cdh Tj = -7 °C

0.991

0.992

Pdh Tj = +2°C

3.2 kW

2.8 kW

COP Tj = +2°C

4.29

2.91

Cdh Tj = +2 °C

0.98

0.984

Pdh Tj = +7°C

3 kW

2.6 kW

COP Tj = +7°C

6.19

4.62

Cdh Tj = +7 °C

0.969

0.973

Pdh Tj = 12°C

3.4 kW

3 kW

COP Tj = 12°C

10.44

7.16

Cdh Tj = +12 °C

0.954

0.964

Pdh Tj = Tbiv

5 kW

4.6 kW

COP Tj = Tbiv

2.37

1.66

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

5 kW

4.6 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.37

1.66

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.993

0.995

WTOL

60 °C

60 °C

Poff

15 W

15 W

PTO

15 W

15 W

PSB

15 W

15 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0 kW

0 kW

Annual energy consumption Qhe

2311 kWh

2939 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

139 %

COP

3.36

Heating up time

2:48 h:min

Standby power input

30 W

Reference hot water temperature

53 °C

Mixed water at 40°C

239 l

SUZ-SHWM40VAH + ERST17D-*M*BD
Configure model
Model name
SUZ-SHWM40VAH + ERST17D-*M*BD
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

3 kW

3.6 kW

El input

0.63 kW

1.29 kW

COP

4.77

2.79

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

56 dB(A)

56 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

176 %

126 %

Prated

5 kW

4.6 kW

SCOP

4.47

3.23

Tbiv

-10 °C

-10 °C

TOL

-25 °C

-25 °C

Pdh Tj = -7°C

4.5 kW

4.1 kW

COP Tj = -7°C

2.57

2.14

Cdh Tj = -7 °C

0.991

0.992

Pdh Tj = +2°C

3.2 kW

2.8 kW

COP Tj = +2°C

4.29

2.91

Cdh Tj = +2 °C

0.98

0.984

Pdh Tj = +7°C

3 kW

2.6 kW

COP Tj = +7°C

6.19

4.62

Cdh Tj = +7 °C

0.969

0.973

Pdh Tj = 12°C

3.4 kW

3 kW

COP Tj = 12°C

10.44

7.16

Cdh Tj = +12 °C

0.954

0.964

Pdh Tj = Tbiv

5 kW

4.6 kW

COP Tj = Tbiv

2.37

1.66

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

5 kW

4.6 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.37

1.66

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.993

0.995

WTOL

60 °C

60 °C

Poff

15 W

15 W

PTO

15 W

15 W

PSB

15 W

15 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0 kW

0 kW

Annual energy consumption Qhe

2311 kWh

2939 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

139 %

COP

3.36

Heating up time

2:48 h:min

Standby power input

30 W

Reference hot water temperature

53 °C

Mixed water at 40°C

239 l

SUZ-SWM60VA2 + EHST17D-*M*D
Configure model
Model name
SUZ-SWM60VA2 + EHST17D-*M*D
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

5 kW

5 kW

El input

1.03 kW

1.81 kW

COP

4.85

2.77

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

56 dB(A)

56 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

185 %

134 %

Prated

6.1 kW

6 kW

SCOP

4.7

3.43

Tbiv

-10 °C

-7 °C

TOL

-25 °C

-25 °C

Pdh Tj = -7°C

5.4 kW

5.31 kW

COP Tj = -7°C

2.79

1.95

Cdh Tj = -7 °C

0.992

0.994

Pdh Tj = +2°C

3.3 kW

3.3 kW

COP Tj = +2°C

4.73

3.42

Cdh Tj = +2 °C

0.978

0.984

Pdh Tj = +7°C

3.2 kW

2.6 kW

COP Tj = +7°C

6.22

4.72

Cdh Tj = +7 °C

0.971

0.973

Pdh Tj = 12°C

3.2 kW

3.5 kW

COP Tj = 12°C

9.9

6.95

Cdh Tj = +12 °C

0.954

0.97

Pdh Tj = Tbiv

6.1 kW

5.31 kW

COP Tj = Tbiv

2.54

1.95

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

6.1 kW

5 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.54

1.91

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.994

0.994

WTOL

60 °C

60 °C

Poff

15 W

15 W

PTO

15 W

15 W

PSB

15 W

15 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0 kW

1 kW

Annual energy consumption Qhe

2681 kWh

3615 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

139 %

COP

3.36

Heating up time

2:48 h:min

Standby power input

30 W

Reference hot water temperature

53 °C

Mixed water at 40°C

239 l

SUZ-SWM60VA2 + ERST17D-*M*D
Configure model
Model name
SUZ-SWM60VA2 + ERST17D-*M*D
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

5 kW

5 kW

El input

1.03 kW

1.81 kW

COP

4.85

2.77

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

56 dB(A)

56 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

189 %

136 %

Prated

6.1 kW

6 kW

SCOP

4.8

3.48

Tbiv

-10 °C

-7 °C

TOL

-25 °C

-25 °C

Pdh Tj = -7°C

5.4 kW

5.31 kW

COP Tj = -7°C

2.79

1.95

Cdh Tj = -7 °C

0.992

0.994

Pdh Tj = +2°C

3.3 kW

3.3 kW

COP Tj = +2°C

4.73

3.42

Cdh Tj = +2 °C

0.978

0.984

Pdh Tj = +7°C

3.2 kW

2.6 kW

COP Tj = +7°C

6.22

4.72

Cdh Tj = +7 °C

0.971

0.973

Pdh Tj = 12°C

3.2 kW

3.5 kW

COP Tj = 12°C

9.9

6.95

Cdh Tj = +12 °C

0.954

0.97

Pdh Tj = Tbiv

6.1 kW

5.31 kW

COP Tj = Tbiv

2.54

1.95

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

6.1 kW

5 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.54

1.91

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.994

0.994

WTOL

60 °C

60 °C

Poff

15 W

15 W

PTO

15 W

15 W

PSB

15 W

15 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0 kW

1 kW

Annual energy consumption Qhe

2626 kWh

3560 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

139 %

COP

3.36

Heating up time

2:48 h:min

Standby power input

30 W

Reference hot water temperature

53 °C

Mixed water at 40°C

239 l

SUZ-SWM60VA2 + ERST17D-*M*BD
Configure model
Model name
SUZ-SWM60VA2 + ERST17D-*M*BD
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

5 kW

5 kW

El input

1.03 kW

1.81 kW

COP

4.85

2.77

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

56 dB(A)

56 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

189 %

136 %

Prated

6.1 kW

6 kW

SCOP

4.8

3.48

Tbiv

-10 °C

-7 °C

TOL

-25 °C

-25 °C

Pdh Tj = -7°C

5.4 kW

5.31 kW

COP Tj = -7°C

2.79

1.95

Cdh Tj = -7 °C

0.992

0.994

Pdh Tj = +2°C

3.3 kW

3.3 kW

COP Tj = +2°C

4.73

3.42

Cdh Tj = +2 °C

0.978

0.984

Pdh Tj = +7°C

3.2 kW

2.6 kW

COP Tj = +7°C

6.22

4.72

Cdh Tj = +7 °C

0.971

0.973

Pdh Tj = 12°C

3.2 kW

3.5 kW

COP Tj = 12°C

9.9

6.95

Cdh Tj = +12 °C

0.954

0.97

Pdh Tj = Tbiv

6.1 kW

5.31 kW

COP Tj = Tbiv

2.54

1.95

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

6.1 kW

5 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.54

1.91

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.994

0.994

WTOL

60 °C

60 °C

Poff

15 W

15 W

PTO

15 W

15 W

PSB

15 W

15 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0 kW

1 kW

Annual energy consumption Qhe

2626 kWh

3560 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

139 %

COP

3.36

Heating up time

2:48 h:min

Standby power input

30 W

Reference hot water temperature

53 °C

Mixed water at 40°C

239 l

SUZ-SHWM40VAH + ERST17D-*M*E
Configure model
Model name
SUZ-SHWM40VAH + ERST17D-*M*E
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
+7°C/12°C and +18°C/+23°C
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

3 kW

3.6 kW

El input

0.63 kW

1.29 kW

COP

4.77

2.79

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Cooling

EN 14511-2

+7°C/+12°C

+18°C/+23°C

El input

1.35 kW

1.19 kW

Cooling capacity

4.5

5.6

EER

3.33

4.7

EN 14825

+7°C/+12°C

+18°C/+23°C

Pdesignc

4.5 kW

5.6 kW

SEER

4.91

6.23

Pdc Tj = 35°C

4.5 kW

5.6 kW

EER Tj = 35°C

3.33

4.7

Cdc Tj = 35 °C

0.989

0.987

Pdc Tj = 30°C

3.32 kW

4.13 kW

EER Tj = 30°C

4.23

5.97

Cdc Tj = 30 °C

0.981

0.978

Pdc Tj = 25°C

2.13 kW

2.8 kW

EER Tj = 25°C

5.41

8.43

Cdc Tj = 25 °C

0.962

0.955

Pdc Tj = 20°C

2.1 kW

1.93 kW

EER Tj = 20°C

7.69

5.73

Cdc Tj = 20 °C

0.945

0.955

Poff

15 W

15 W

PTO

15 W

15 W

PSB

15 W

15 W

PCK

0 W

0 W

Annual energy consumption Qce

550 kWh

539 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

56 dB(A)

56 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

176 %

126 %

Prated

5 kW

4.6 kW

SCOP

4.47

3.23

Tbiv

-10 °C

-10 °C

TOL

-25 °C

-25 °C

Pdh Tj = -7°C

4.5 kW

4.1 kW

COP Tj = -7°C

2.57

2.14

Cdh Tj = -7 °C

0.991

0.992

Pdh Tj = +2°C

3.2 kW

2.8 kW

COP Tj = +2°C

4.29

2.91

Cdh Tj = +2 °C

0.98

0.984

Pdh Tj = +7°C

3 kW

2.6 kW

COP Tj = +7°C

6.19

4.62

Cdh Tj = +7 °C

0.969

0.973

Pdh Tj = 12°C

3.4 kW

3 kW

COP Tj = 12°C

10.44

7.16

Cdh Tj = +12 °C

0.954

0.964

Pdh Tj = Tbiv

5 kW

4.6 kW

COP Tj = Tbiv

2.37

1.66

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

5 kW

4.6 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.37

1.66

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.993

0.995

WTOL

60 °C

60 °C

Poff

15 W

15 W

PTO

15 W

15 W

PSB

15 W

15 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0 kW

0 kW

Annual energy consumption Qhe

2311 kWh

2939 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

135 %

COP

3.29

Heating up time

2:34 h:min

Standby power input

22.6 W

Reference hot water temperature

53 °C

Mixed water at 40°C

236 l

SUZ-SHWM40VAH + ERST17D-*M*BE
Configure model
Model name
SUZ-SHWM40VAH + ERST17D-*M*BE
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
+7°C/12°C and +18°C/+23°C
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

3 kW

3.6 kW

El input

0.63 kW

1.29 kW

COP

4.77

2.79

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Cooling

EN 14511-2

+7°C/+12°C

+18°C/+23°C

El input

1.35 kW

1.19 kW

Cooling capacity

4.5

5.6

EER

3.33

4.7

EN 14825

+7°C/+12°C

+18°C/+23°C

Pdesignc

4.5 kW

5.6 kW

SEER

4.91

6.23

Pdc Tj = 35°C

4.5 kW

5.6 kW

EER Tj = 35°C

3.33

4.7

Cdc Tj = 35 °C

0.989

0.987

Pdc Tj = 30°C

3.32 kW

4.13 kW

EER Tj = 30°C

4.23

5.97

Cdc Tj = 30 °C

0.981

0.978

Pdc Tj = 25°C

2.13 kW

2.8 kW

EER Tj = 25°C

5.41

8.43

Cdc Tj = 25 °C

0.962

0.955

Pdc Tj = 20°C

2.1 kW

1.93 kW

EER Tj = 20°C

7.69

5.73

Cdc Tj = 20 °C

0.945

0.955

Poff

15 W

15 W

PTO

15 W

15 W

PSB

15 W

15 W

PCK

0 W

0 W

Annual energy consumption Qce

550 kWh

539 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

56 dB(A)

56 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

176 %

126 %

Prated

5 kW

4.6 kW

SCOP

4.47

3.23

Tbiv

-10 °C

-10 °C

TOL

-25 °C

-25 °C

Pdh Tj = -7°C

4.5 kW

4.1 kW

COP Tj = -7°C

2.57

2.14

Cdh Tj = -7 °C

0.991

0.992

Pdh Tj = +2°C

3.2 kW

2.8 kW

COP Tj = +2°C

4.29

2.91

Cdh Tj = +2 °C

0.98

0.984

Pdh Tj = +7°C

3 kW

2.6 kW

COP Tj = +7°C

6.19

4.62

Cdh Tj = +7 °C

0.969

0.973

Pdh Tj = 12°C

3.4 kW

3 kW

COP Tj = 12°C

10.44

7.16

Cdh Tj = +12 °C

0.954

0.964

Pdh Tj = Tbiv

5 kW

4.6 kW

COP Tj = Tbiv

2.37

1.66

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

5 kW

4.6 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.37

1.66

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.993

0.995

WTOL

60 °C

60 °C

Poff

15 W

15 W

PTO

15 W

15 W

PSB

15 W

15 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0 kW

0 kW

Annual energy consumption Qhe

2311 kWh

2939 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

135 %

COP

3.29

Heating up time

2:34 h:min

Standby power input

22.6 W

Reference hot water temperature

53 °C

Mixed water at 40°C

236 l

SUZ-SWM60VA2 + EHST17D-*M*E
Configure model
Model name
SUZ-SWM60VA2 + EHST17D-*M*E
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

5 kW

5 kW

El input

1.03 kW

1.81 kW

COP

4.85

2.77

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Cooling

EN 14511-2

+7°C/+12°C

+18°C/+23°C

El input

1.57 kW

1.29 kW

Cooling capacity

5

6

EER

3.18

4.65

EN 14825

+7°C/+12°C

+18°C/+23°C

Pdesignc

5 kW

6 kW

SEER

4.93

6.17

Pdc Tj = 35°C

5 kW

6 kW

EER Tj = 35°C

3.18

4.65

Cdc Tj = 35 °C

0.99

0.988

Pdc Tj = 30°C

3.68 kW

4.42 kW

EER Tj = 30°C

4.2

5.94

Cdc Tj = 30 °C

0.983

0.98

Pdc Tj = 25°C

2.37 kW

2.84 kW

EER Tj = 25°C

5.53

8.28

Cdc Tj = 25 °C

0.965

0.956

Pdc Tj = 20°C

2.1 kW

1.93 kW

EER Tj = 20°C

7.5

5.6

Cdc Tj = 20 °C

0.946

0.956

Poff

15 W

15 W

PTO

15 W

15 W

PSB

15 W

15 W

PCK

0 W

0 W

Annual energy consumption Qce

609 kWh

583 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

56 dB(A)

56 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

185 %

134 %

Prated

6.1 kW

6 kW

SCOP

4.7

3.43

Tbiv

-10 °C

-7 °C

TOL

-25 °C

-25 °C

Pdh Tj = -7°C

5.4 kW

5.31 kW

COP Tj = -7°C

2.79

1.95

Cdh Tj = -7 °C

0.992

0.994

Pdh Tj = +2°C

3.3 kW

3.3 kW

COP Tj = +2°C

4.73

3.42

Cdh Tj = +2 °C

0.978

0.984

Pdh Tj = +7°C

3.2 kW

2.6 kW

COP Tj = +7°C

6.22

4.72

Cdh Tj = +7 °C

0.971

0.973

Pdh Tj = 12°C

3.2 kW

3.5 kW

COP Tj = 12°C

9.9

6.95

Cdh Tj = +12 °C

0.954

0.97

Pdh Tj = Tbiv

6.1 kW

5.31 kW

COP Tj = Tbiv

2.54

1.95

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

6.1 kW

5 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.54

1.91

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.994

0.994

WTOL

60 °C

60 °C

Poff

15 W

15 W

PTO

15 W

15 W

PSB

15 W

15 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0 kW

1 kW

Annual energy consumption Qhe

2681 kWh

3615 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

135 %

COP

3.29

Heating up time

2:34 h:min

Standby power input

22.6 W

Reference hot water temperature

53 °C

Mixed water at 40°C

236 l

SUZ-SWM60VA2 + ERST17D-*M*E
Configure model
Model name
SUZ-SWM60VA2 + ERST17D-*M*E
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
+7°C/12°C and +18°C/+23°C
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

5 kW

5 kW

El input

1.03 kW

1.81 kW

COP

4.85

2.77

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Cooling

EN 14511-2

+7°C/+12°C

+18°C/+23°C

El input

1.57 kW

1.29 kW

Cooling capacity

5

6

EER

3.18

4.65

EN 14825

+7°C/+12°C

+18°C/+23°C

Pdesignc

5 kW

6 kW

SEER

4.93

6.17

Pdc Tj = 35°C

5 kW

6 kW

EER Tj = 35°C

3.18

4.65

Cdc Tj = 35 °C

0.99

0.988

Pdc Tj = 30°C

3.68 kW

4.42 kW

EER Tj = 30°C

4.2

5.94

Cdc Tj = 30 °C

0.983

0.98

Pdc Tj = 25°C

2.37 kW

2.84 kW

EER Tj = 25°C

5.53

8.28

Cdc Tj = 25 °C

0.965

0.956

Pdc Tj = 20°C

2.1 kW

1.93 kW

EER Tj = 20°C

7.5

5.6

Cdc Tj = 20 °C

0.946

0.956

Poff

15 W

15 W

PTO

15 W

15 W

PSB

15 W

15 W

PCK

0 W

0 W

Annual energy consumption Qce

609 kWh

583 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

56 dB(A)

56 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

189 %

136 %

Prated

6.1 kW

6 kW

SCOP

4.8

3.48

Tbiv

-10 °C

-7 °C

TOL

-25 °C

-25 °C

Pdh Tj = -7°C

5.4 kW

5.31 kW

COP Tj = -7°C

2.79

1.95

Cdh Tj = -7 °C

0.992

0.994

Pdh Tj = +2°C

3.3 kW

3.3 kW

COP Tj = +2°C

4.73

3.42

Cdh Tj = +2 °C

0.978

0.984

Pdh Tj = +7°C

3.2 kW

2.6 kW

COP Tj = +7°C

6.22

4.72

Cdh Tj = +7 °C

0.971

0.973

Pdh Tj = 12°C

3.2 kW

3.5 kW

COP Tj = 12°C

9.9

6.95

Cdh Tj = +12 °C

0.954

0.97

Pdh Tj = Tbiv

6.1 kW

5.31 kW

COP Tj = Tbiv

2.54

1.95

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

6.1 kW

5 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.54

1.91

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.994

0.994

WTOL

60 °C

60 °C

Poff

15 W

15 W

PTO

15 W

15 W

PSB

15 W

15 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0 kW

1 kW

Annual energy consumption Qhe

2626 kWh

3560 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

135 %

COP

3.29

Heating up time

2:34 h:min

Standby power input

22.6 W

Reference hot water temperature

53 °C

Mixed water at 40°C

236 l

SUZ-SWM60VA2 + ERST17D-*M*BE
Configure model
Model name
SUZ-SWM60VA2 + ERST17D-*M*BE
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
+7°C/12°C and +18°C/+23°C
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

5 kW

5 kW

El input

1.03 kW

1.81 kW

COP

4.85

2.77

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Cooling

EN 14511-2

+7°C/+12°C

+18°C/+23°C

El input

1.57 kW

1.29 kW

Cooling capacity

5

6

EER

3.18

4.65

EN 14825

+7°C/+12°C

+18°C/+23°C

Pdesignc

5 kW

6 kW

SEER

4.93

6.17

Pdc Tj = 35°C

5 kW

6 kW

EER Tj = 35°C

3.18

4.65

Cdc Tj = 35 °C

0.99

0.988

Pdc Tj = 30°C

3.68 kW

4.42 kW

EER Tj = 30°C

4.2

5.94

Cdc Tj = 30 °C

0.983

0.98

Pdc Tj = 25°C

2.37 kW

2.84 kW

EER Tj = 25°C

5.53

8.28

Cdc Tj = 25 °C

0.965

0.956

Pdc Tj = 20°C

2.1 kW

1.93 kW

EER Tj = 20°C

7.5

5.6

Cdc Tj = 20 °C

0.946

0.956

Poff

15 W

15 W

PTO

15 W

15 W

PSB

15 W

15 W

PCK

0 W

0 W

Annual energy consumption Qce

609 kWh

583 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

56 dB(A)

56 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

189 %

136 %

Prated

6.1 kW

6 kW

SCOP

4.8

3.48

Tbiv

-10 °C

-7 °C

TOL

-25 °C

-25 °C

Pdh Tj = -7°C

5.4 kW

5.31 kW

COP Tj = -7°C

2.79

1.95

Cdh Tj = -7 °C

0.992

0.994

Pdh Tj = +2°C

3.3 kW

3.3 kW

COP Tj = +2°C

4.73

3.42

Cdh Tj = +2 °C

0.978

0.984

Pdh Tj = +7°C

3.2 kW

2.6 kW

COP Tj = +7°C

6.22

4.72

Cdh Tj = +7 °C

0.971

0.973

Pdh Tj = 12°C

3.2 kW

3.5 kW

COP Tj = 12°C

9.9

6.95

Cdh Tj = +12 °C

0.954

0.97

Pdh Tj = Tbiv

6.1 kW

5.31 kW

COP Tj = Tbiv

2.54

1.95

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

6.1 kW

5 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.54

1.91

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.994

0.994

WTOL

60 °C

60 °C

Poff

15 W

15 W

PTO

15 W

15 W

PSB

15 W

15 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0 kW

1 kW

Annual energy consumption Qhe

2626 kWh

3560 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

135 %

COP

3.29

Heating up time

2:34 h:min

Standby power input

22.6 W

Reference hot water temperature

53 °C

Mixed water at 40°C

236 l