Certificate holders

Subtype

DC Inverter Air-Water Heat Pump 016

Certificate Holder
Foshan AIROSD Thermal Technology Co., Ltd.
Dongfeng Road, Tang Lian Industrial Zone No.2 of Five
Foshan City
China
Registration number
041-K048-02
Certification Body
BRE Global Limited
Subtype title
DC Inverter Air-Water Heat Pump 016
Driving energy
Electricity
Heat Pump Type
Outdoor Air/Water
Refrigerant
R32
Mass of Refrigerant

2,600 kg

Certification Date
20.03.2023
Testing basis
Heat Pump Keymark Scheme Rules Rev 11
Generate PDF Export model CSV Download certificate
  • Number of models 1

Models

QBKFXFC-016SRI
Configure model
Model name
QBKFXFC-016SRI
Application
Heating (medium temp)
Units
Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

16.09 kW

16.09 kW

El input

3.57 kW

5.48 kW

COP

4.50

2.94

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

67 dB(A)

67 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

175 %

132 %

Prated

15.68 kW

15.53 kW

SCOP

4.46

3.37

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

13.87 kW

13.74 kW

COP Tj = -7°C

3.18

2.33

Cdh Tj = -7 °C

0.900

0.900

Pdh Tj = +2°C

8.66 kW

8.43 kW

COP Tj = +2°C

4.56

3.16

Cdh Tj = +2 °C

0.900

0.900

Pdh Tj = +7°C

7.13 kW

6.85 kW

COP Tj = +7°C

5.28

4.52

Cdh Tj = +7 °C

0.900

0.900

Pdh Tj = 12°C

9.39 kW

9.58 kW

COP Tj = 12°C

7.38

6.82

Cdh Tj = +12 °C

0.900

0.900

Pdh Tj = Tbiv

13.87 kW

13.74 kW

COP Tj = Tbiv

3.18

2.33

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

13.36 kW

13.84 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.87

2.16

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

60 °C

60 °C

Poff

8 W

8 W

PTO

8 W

8 W

PSB

8 W

8 W

PCK

43 W

43 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

2.32 kW

1.69 kW

Annual energy consumption Qhe

7267 kWh

9509 kWh