7,300 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
26.83 kW
25.59 kW
El input
6.80 kW
9.01 kW
COP
3.94
2.84
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
69 dB(A)
69 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
149 %
111 %
Prated
29.00 kW
29.00 kW
SCOP
3.79
2.86
Tbiv
-5 °C
-5 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
22.10 kW
22.70 kW
COP Tj = -7°C
3.16
2.33
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
26.70 kW
25.80 kW
COP Tj = +2°C
3.86
2.70
Cdh Tj = +2 °C
0.990
0.990
Pdh Tj = +7°C
27.40 kW
26.80 kW
COP Tj = +7°C
4.41
3.43
Cdh Tj = +7 °C
0.990
0.990
Pdh Tj = 12°C
26.80 kW
26.60 kW
COP Tj = 12°C
4.84
4.10
Cdh Tj = +12 °C
0.990
0.990
Pdh Tj = Tbiv
23.10 kW
23.20 kW
COP Tj = Tbiv
3.34
2.41
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
20.60 kW
22.10 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.94
2.26
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
WTOL
60 °C
60 °C
Poff
7 W
7 W
PTO
7 W
7 W
PSB
7 W
7 W
PCK
25 W
25 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
8.40 kW
6.90 kW
Annual energy consumption Qhe
15805 kWh
20964 kWh