Certificate holders

Subtype

TTF\TTC 5.5

Certificate Holder
tecalor GmbH
Fürstenbergerstr. 77
37603 Holzminden
Germany
Registration number
012-C700168 / issue 2
Certification Body
RISE CERT
Subtype title
TTF\TTC 5.5
Driving energy
Electricity
Heat Pump Type
Brine/Water and Water/Water
Refrigerant
R452B
Mass of Refrigerant

0,575 kg

Certification Date
22.02.2023
Testing basis
EN 14511:2018, EN 14825:2018, EN 12102:2017.
Generate PDF Export model CSV Download certificate
  • Number of models 2

Models

TTC 5.5
Configure model
Model name
TTC 5.5
Application
Heating (medium temp)
Units
Indoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Brine/Water Heat Pump

Heating

EN 14511-4

Starting and operating test

passed

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

EN 14511-2

Low temperature

Medium temperature

Heat output

5.56 kW

5.00 kW

El input

1.26 kW

1.80 kW

COP

4.40

2.78

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

40 dB(A)

42 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

183 %

135 %

Prated

6.53 kW

6.00 kW

SCOP

4.78

3.58

Tbiv

4 °C

4 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

5.54 kW

5.00 kW

COP Tj = +2°C

4.39

2.77

Cdh Tj = +2 °C

0.990

1.000

Pdh Tj = +7°C

5.63 kW

5.15 kW

COP Tj = +7°C

4.72

3.34

Cdh Tj = +7 °C

0.990

1.000

Pdh Tj = 12°C

5.71 kW

5.34 kW

COP Tj = 12°C

5.09

4.04

Cdh Tj = +12 °C

0.990

0.990

Pdh Tj = Tbiv

5.60 kW

5.14 kW

COP Tj = Tbiv

4.59

3.11

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

5.54 kW

5.00 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.39

2.77

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.990

1.000

WTOL

65 °C

65 °C

Poff

4 W

4 W

PTO

7 W

7 W

PSB

7 W

7 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.99 kW

1.00 kW

Annual energy consumption Qhe

1825 kWh

2237 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

40 dB(A)

42 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

187 %

138 %

Prated

6.26 kW

6.07 kW

SCOP

4.87

3.65

Tbiv

-18 °C

-16 °C

TOL

-22 °C

-22 °C

Pdh Tj = -7°C

5.65 kW

5.19 kW

COP Tj = -7°C

4.80

3.47

Cdh Tj = -7 °C

0.990

1.000

Pdh Tj = +2°C

5.70 kW

5.29 kW

COP Tj = +2°C

5.02

3.86

Cdh Tj = +2 °C

0.990

1.000

Pdh Tj = +7°C

5.73 kW

5.37 kW

COP Tj = +7°C

5.18

4.17

Cdh Tj = +7 °C

0.990

0.990

Pdh Tj = 12°C

5.74 kW

5.43 kW

COP Tj = 12°C

5.22

4.40

Cdh Tj = +12 °C

0.990

0.990

Pdh Tj = Tbiv

5.60 kW

5.11 kW

COP Tj = Tbiv

4.60

3.21

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

5.54 kW

5.00 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.39

2.77

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.990

1.000

WTOL

65 °C

65 °C

Poff

4 W

4 W

PTO

7 W

7 W

PSB

7 W

7 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.72 kW

1.07 kW

Annual energy consumption Qhe

3170 kWh

4104 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

40 dB(A)

42 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

181 %

135 %

Prated

6.03 kW

6.33 kW

SCOP

4.74

3.56

Tbiv

-8 °C

-5 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

5.58 kW

5.14 kW

COP Tj = -7°C

4.51

3.07

Cdh Tj = -7 °C

0.990

1.000

Pdh Tj = +2°C

5.64 kW

5.23 kW

COP Tj = +2°C

4.74

3.60

Cdh Tj = +2 °C

0.990

1.000

Pdh Tj = +7°C

5.69 kW

5.31 kW

COP Tj = +7°C

4.99

3.94

Cdh Tj = +7 °C

0.990

0.990

Pdh Tj = 12°C

5.75 kW

5.39 kW

COP Tj = 12°C

5.25

4.27

Cdh Tj = +12 °C

0.990

0.990

Pdh Tj = Tbiv

5.57 kW

5.12 kW

COP Tj = Tbiv

4.47

3.21

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

5.54 kW

5.00 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.39

2.77

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.990

1.000

WTOL

65 °C

65 °C

Poff

4 W

4 W

PTO

7 W

7 W

PSB

7 W

7 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.49 kW

1.33 kW

Annual energy consumption Qhe

2630 kWh

3672 kWh

Water/Water Heat Pump

Heating

EN 14511-4

Starting and operating test

passed

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

EN 14511-2

Low temperature

Medium temperature

Heat output

7.21 kW

6.66 kW

El input

1.27 kW

1.86 kW

COP

5.70

3.57

Warmer Climate

EN 14825

Low temperature

Medium temperature

ηs

238 %

177 %

Prated

7.81 kW

7.94 kW

SCOP

6.16

4.62

Tbiv

3 °C

4 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

7.21 kW

6.66 kW

COP Tj = +2°C

5.70

3.57

Cdh Tj = +2 °C

0.990

1.000

Pdh Tj = +7°C

7.31 kW

6.93 kW

COP Tj = +7°C

6.07

4.25

Cdh Tj = +7 °C

0.990

1.000

Pdh Tj = 12°C

7.37 kW

7.19 kW

COP Tj = 12°C

6.53

5.31

Cdh Tj = +12 °C

0.990

0.990

Pdh Tj = Tbiv

7.25 kW

6.81 kW

COP Tj = Tbiv

5.82

3.91

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

7.21 kW

6.66 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

5.70

3.57

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.990

1.000

WTOL

65 °C

65 °C

Poff

4 W

4 W

PTO

7 W

7 W

PSB

7 W

7 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.60 kW

1.28 kW

Annual energy consumption Qhe

1694 kWh

2299 kWh

Colder Climate

EN 14825

Low temperature

Medium temperature

ηs

243 %

181 %

Prated

8.14 kW

8.16 kW

SCOP

6.27

4.72

Tbiv

-18 °C

-16 °C

TOL

-22 °C

-22 °C

Pdh Tj = -7°C

7.34 kW

6.98 kW

COP Tj = -7°C

6.22

4.45

Cdh Tj = -7 °C

0.990

0.996

Pdh Tj = +2°C

7.36 kW

7.13 kW

COP Tj = +2°C

6.46

5.02

Cdh Tj = +2 °C

0.990

0.995

Pdh Tj = +7°C

7.37 kW

7.24 kW

COP Tj = +7°C

6.64

5.52

Cdh Tj = +7 °C

0.990

0.995

Pdh Tj = 12°C

7.37 kW

7.31 kW

COP Tj = 12°C

6.68

5.94

Cdh Tj = +12 °C

0.990

0.994

Pdh Tj = Tbiv

7.29 kW

6.87 kW

COP Tj = Tbiv

5.96

4.07

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

7.21 kW

6.66 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

5.70

3.57

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.990

0.996

WTOL

65 °C

65 °C

Poff

4 W

4 W

PTO

7 W

7 W

PSB

7 W

7 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.93 kW

1.50 kW

Annual energy consumption Qhe

3199 kWh

4265 kWh

Average Climate

EN 14825

Low temperature

Medium temperature

ηs

237 %

175 %

Prated

7.85 kW

8.07 kW

SCOP

6.12

4.58

Tbiv

-8 °C

-6 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

7.26 kW

6.78 kW

COP Tj = -7°C

5.85

3.85

Cdh Tj = -7 °C

0.990

1.000

Pdh Tj = +2°C

7.32 kW

7.02 kW

COP Tj = +2°C

6.14

4.60

Cdh Tj = +2 °C

0.990

1.000

Pdh Tj = +7°C

7.36 kW

7.15 kW

COP Tj = +7°C

6.43

5.12

Cdh Tj = +7 °C

0.990

1.000

Pdh Tj = 12°C

7.37 kW

7.27 kW

COP Tj = 12°C

6.71

5.70

Cdh Tj = +12 °C

0.990

0.990

Pdh Tj = Tbiv

7.24 kW

6.83 kW

COP Tj = Tbiv

5.80

3.96

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

7.21 kW

6.66 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

5.70

3.57

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.990

1.000

WTOL

65 °C

65 °C

Poff

4 W

4 W

PTO

7 W

7 W

PSB

7 W

7 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.64 kW

1.41 kW

Annual energy consumption Qhe

2651 kWh

3641 kWh

TTF 5.5
Configure model
Model name
TTF 5.5
Application
Heating (medium temp)
Units
Indoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Brine/Water Heat Pump

Heating

EN 14511-4

Starting and operating test

passed

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

EN 14511-2

Low temperature

Medium temperature

Heat output

5.56 kW

5.00 kW

El input

1.26 kW

1.80 kW

COP

4.40

2.78

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

42 dB(A)

44 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

183 %

135 %

Prated

6.53 kW

6.00 kW

SCOP

4.78

3.58

Tbiv

4 °C

4 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

5.54 kW

5.00 kW

COP Tj = +2°C

4.39

2.77

Cdh Tj = +2 °C

0.990

1.000

Pdh Tj = +7°C

5.63 kW

5.15 kW

COP Tj = +7°C

4.72

3.34

Cdh Tj = +7 °C

0.990

1.000

Pdh Tj = 12°C

5.71 kW

5.34 kW

COP Tj = 12°C

5.09

4.04

Cdh Tj = +12 °C

0.990

0.990

Pdh Tj = Tbiv

5.60 kW

5.14 kW

COP Tj = Tbiv

4.59

3.11

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

5.54 kW

5.00 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.39

2.77

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.990

1.000

WTOL

65 °C

65 °C

Poff

4 W

4 W

PTO

7 W

7 W

PSB

7 W

7 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.99 kW

1.00 kW

Annual energy consumption Qhe

1825 kWh

2237 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

42 dB(A)

44 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

187 %

138 %

Prated

6.26 kW

6.07 kW

SCOP

4.87

3.65

Tbiv

-18 °C

-16 °C

TOL

-22 °C

-22 °C

Pdh Tj = -7°C

5.65 kW

5.19 kW

COP Tj = -7°C

4.80

3.47

Cdh Tj = -7 °C

0.990

1.000

Pdh Tj = +2°C

5.70 kW

5.29 kW

COP Tj = +2°C

5.02

3.86

Cdh Tj = +2 °C

0.990

1.000

Pdh Tj = +7°C

5.73 kW

5.37 kW

COP Tj = +7°C

5.18

4.17

Cdh Tj = +7 °C

0.990

0.990

Pdh Tj = 12°C

5.74 kW

5.43 kW

COP Tj = 12°C

5.22

4.40

Cdh Tj = +12 °C

0.990

0.990

Pdh Tj = Tbiv

5.60 kW

5.11 kW

COP Tj = Tbiv

4.60

3.21

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

5.54 kW

5.00 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.39

2.77

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.990

1.000

WTOL

65 °C

65 °C

Poff

4 W

4 W

PTO

7 W

7 W

PSB

7 W

7 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.72 kW

1.07 kW

Annual energy consumption Qhe

3170 kWh

4104 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

42 dB(A)

44 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

181 %

135 %

Prated

6.03 kW

6.33 kW

SCOP

4.74

3.56

Tbiv

-8 °C

-5 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

5.58 kW

5.14 kW

COP Tj = -7°C

4.51

3.07

Cdh Tj = -7 °C

0.990

1.000

Pdh Tj = +2°C

5.64 kW

5.23 kW

COP Tj = +2°C

4.74

3.60

Cdh Tj = +2 °C

0.990

1.000

Pdh Tj = +7°C

5.69 kW

5.31 kW

COP Tj = +7°C

4.99

3.94

Cdh Tj = +7 °C

0.990

0.990

Pdh Tj = 12°C

5.75 kW

5.39 kW

COP Tj = 12°C

5.25

4.27

Cdh Tj = +12 °C

0.990

0.990

Pdh Tj = Tbiv

5.57 kW

5.12 kW

COP Tj = Tbiv

4.47

3.21

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

5.54 kW

5.00 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.39

2.77

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.990

1.000

WTOL

65 °C

65 °C

Poff

4 W

4 W

PTO

7 W

7 W

PSB

7 W

7 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.49 kW

1.33 kW

Annual energy consumption Qhe

2630 kWh

3672 kWh

Water/Water Heat Pump

Heating

EN 14511-4

Starting and operating test

passed

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

EN 14511-2

Low temperature

Medium temperature

Heat output

7.21 kW

6.66 kW

El input

1.27 kW

1.86 kW

COP

5.70

3.57

Warmer Climate

EN 14825

Low temperature

Medium temperature

ηs

238 %

177 %

Prated

7.81 kW

7.94 kW

SCOP

6.16

4.62

Tbiv

3 °C

4 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

7.21 kW

6.66 kW

COP Tj = +2°C

5.70

3.57

Cdh Tj = +2 °C

0.990

1.000

Pdh Tj = +7°C

7.31 kW

6.93 kW

COP Tj = +7°C

6.07

4.25

Cdh Tj = +7 °C

0.990

1.000

Pdh Tj = 12°C

7.37 kW

7.19 kW

COP Tj = 12°C

6.53

5.31

Cdh Tj = +12 °C

0.990

0.990

Pdh Tj = Tbiv

7.25 kW

6.81 kW

COP Tj = Tbiv

5.82

3.91

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

7.21 kW

6.66 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

5.70

3.57

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.990

1.000

WTOL

65 °C

65 °C

Poff

4 W

4 W

PTO

7 W

7 W

PSB

7 W

7 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.60 kW

1.28 kW

Annual energy consumption Qhe

1694 kWh

2299 kWh

Colder Climate

EN 14825

Low temperature

Medium temperature

ηs

243 %

181 %

Prated

8.14 kW

8.16 kW

SCOP

6.27

4.72

Tbiv

-18 °C

-16 °C

TOL

-22 °C

-22 °C

Pdh Tj = -7°C

7.34 kW

6.98 kW

COP Tj = -7°C

6.22

4.45

Cdh Tj = -7 °C

0.990

0.996

Pdh Tj = +2°C

7.36 kW

7.13 kW

COP Tj = +2°C

6.46

5.02

Cdh Tj = +2 °C

0.990

0.995

Pdh Tj = +7°C

7.37 kW

7.24 kW

COP Tj = +7°C

6.64

5.52

Cdh Tj = +7 °C

0.990

0.995

Pdh Tj = 12°C

7.37 kW

7.31 kW

COP Tj = 12°C

6.68

5.94

Cdh Tj = +12 °C

0.990

0.994

Pdh Tj = Tbiv

7.29 kW

6.87 kW

COP Tj = Tbiv

5.96

4.07

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

7.21 kW

6.66 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

5.70

3.57

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.990

0.996

WTOL

65 °C

65 °C

Poff

4 W

4 W

PTO

7 W

7 W

PSB

7 W

7 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.93 kW

1.50 kW

Annual energy consumption Qhe

3199 kWh

4265 kWh

Average Climate

EN 14825

Low temperature

Medium temperature

ηs

237 %

175 %

Prated

7.85 kW

8.07 kW

SCOP

6.12

4.58

Tbiv

-8 °C

-6 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

7.26 kW

6.78 kW

COP Tj = -7°C

5.85

3.85

Cdh Tj = -7 °C

0.990

1.000

Pdh Tj = +2°C

7.32 kW

7.02 kW

COP Tj = +2°C

6.14

4.60

Cdh Tj = +2 °C

0.990

1.000

Pdh Tj = +7°C

7.36 kW

7.15 kW

COP Tj = +7°C

6.43

5.12

Cdh Tj = +7 °C

0.990

1.000

Pdh Tj = 12°C

7.37 kW

7.27 kW

COP Tj = 12°C

6.71

5.70

Cdh Tj = +12 °C

0.990

0.990

Pdh Tj = Tbiv

7.24 kW

6.83 kW

COP Tj = Tbiv

5.80

3.96

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

7.21 kW

6.66 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

5.70

3.57

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.990

1.000

WTOL

65 °C

65 °C

Poff

4 W

4 W

PTO

7 W

7 W

PSB

7 W

7 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.64 kW

1.41 kW

Annual energy consumption Qhe

2651 kWh

3641 kWh