5,700 kg
Brine/Water Heat Pump
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
28.70 kW
24.80 kW
El input
6.50 kW
9.20 kW
COP
4.40
2.70
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
59 dB(A)
59 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
193 %
157 %
Prated
28.70 kW
24.80 kW
SCOP
5.03
4.13
Tbiv
2 °C
2 °C
TOL
-22 °C
-22 °C
Pdh Tj = +2°C
28.70 kW
24.80 kW
COP Tj = +2°C
4.40
2.70
Cdh Tj = +2 °C
Pdh Tj = +7°C
29.56 kW
26.54 kW
COP Tj = +7°C
4.84
3.59
Cdh Tj = +7 °C
Pdh Tj = 12°C
30.42 kW
29.02 kW
COP Tj = 12°C
5.32
5.00
Cdh Tj = +12 °C
Pdh Tj = Tbiv
28.70 kW
24.80 kW
COP Tj = Tbiv
4.40
2.70
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
28.70 kW
24.80 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.40
2.70
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
60 °C
60 °C
Poff
0 W
0 W
PTO
10 W
10 W
PSB
10 W
10 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
7630 kWh
8030 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
59 dB(A)
59 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
197 %
161 %
Prated
28.70 kW
24.80 kW
SCOP
5.13
4.23
Tbiv
-22 °C
-22 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
29.85 kW
27.03 kW
COP Tj = -7°C
5.02
3.81
Cdh Tj = -7 °C
Pdh Tj = +2°C
30.42 kW
28.52 kW
COP Tj = +2°C
5.24
4.62
Cdh Tj = +2 °C
Pdh Tj = +7°C
30.71 kW
29.51 kW
COP Tj = +7°C
5.46
5.24
Cdh Tj = +7 °C
Pdh Tj = 12°C
31.00 kW
30.26 kW
COP Tj = 12°C
5.54
5.67
Cdh Tj = +12 °C
Pdh Tj = Tbiv
28.70 kW
24.80 kW
COP Tj = Tbiv
4.40
2.70
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
28.70 kW
24.80 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.40
2.70
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
60 °C
60 °C
Poff
0 W
0 W
PTO
10 W
10 W
PSB
10 W
10 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
13792 kWh
14453 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
59 dB(A)
59 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
192 %
155 %
Prated
28.70 kW
24.80 kW
SCOP
5.01
4.08
Tbiv
-10 °C
-10 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
28.99 kW
25.54 kW
COP Tj = -7°C
4.49
2.94
Cdh Tj = -7 °C
Pdh Tj = +2°C
29.85 kW
27.53 kW
COP Tj = +2°C
5.02
4.05
Cdh Tj = +2 °C
Pdh Tj = +7°C
30.42 kW
28.52 kW
COP Tj = +7°C
5.24
4.75
Cdh Tj = +7 °C
Pdh Tj = 12°C
31.00 kW
29.76 kW
COP Tj = 12°C
5.54
5.56
Cdh Tj = +12 °C
Pdh Tj = Tbiv
28.70 kW
24.80 kW
COP Tj = Tbiv
4.40
2.70
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
28.70 kW
24.80 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.40
2.70
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
60 °C
60 °C
Poff
0 W
0 W
PTO
10 W
10 W
PSB
10 W
10 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
11837 kWh
12560 kWh
Water/Water Heat Pump
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
35.50 kW
34.20 kW
El input
7.00 kW
9.70 kW
COP
5.10
3.50
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
59 dB(A)
59 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
233 %
191 %
Prated
37.20 kW
34.16 kW
SCOP
6.02
4.98
Tbiv
2 °C
2 °C
TOL
-22 °C
-22 °C
Pdh Tj = +2°C
37.20 kW
34.16 kW
COP Tj = +2°C
5.38
3.52
Cdh Tj = +2 °C
Pdh Tj = +7°C
38.06 kW
35.90 kW
COP Tj = +7°C
5.82
4.41
Cdh Tj = +7 °C
Pdh Tj = 12°C
38.92 kW
38.38 kW
COP Tj = 12°C
6.30
5.82
Cdh Tj = +12 °C
Pdh Tj = Tbiv
37.20 kW
34.16 kW
COP Tj = Tbiv
5.38
3.52
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
37.20 kW
34.16 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
5.38
3.52
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
60 °C
60 °C
Poff
0 W
0 W
PTO
10 W
10 W
PSB
10 W
10 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
8253 kWh
9170 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
59 dB(A)
59 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
236 %
192 %
Prated
37.20 kW
34.16 kW
SCOP
6.09
5.01
Tbiv
-22 °C
-22 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
38.35 kW
36.39 kW
COP Tj = -7°C
5.99
4.63
Cdh Tj = -7 °C
Pdh Tj = +2°C
38.92 kW
37.88 kW
COP Tj = +2°C
6.22
5.43
Cdh Tj = +2 °C
Pdh Tj = +7°C
39.21 kW
38.87 kW
COP Tj = +7°C
6.44
6.05
Cdh Tj = +7 °C
Pdh Tj = 12°C
39.50 kW
39.62 kW
COP Tj = 12°C
6.52
6.48
Cdh Tj = +12 °C
Pdh Tj = Tbiv
37.20 kW
34.16 kW
COP Tj = Tbiv
5.38
3.52
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
37.20 kW
34.16 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
5.38
3.52
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
60 °C
60 °C
Poff
0 W
0 W
PTO
10 W
10 W
PSB
10 W
10 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
15056 kWh
16805 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
59 dB(A)
59 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
232 %
189 %
Prated
37.20 kW
34.16 kW
SCOP
6.00
4.92
Tbiv
-10 °C
-10 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
37.49 kW
34.90 kW
COP Tj = -7°C
5.47
3.76
Cdh Tj = -7 °C
Pdh Tj = +2°C
38.35 kW
36.89 kW
COP Tj = +2°C
5.99
4.87
Cdh Tj = +2 °C
Pdh Tj = +7°C
38.92 kW
37.88 kW
COP Tj = +7°C
6.22
5.57
Cdh Tj = +7 °C
Pdh Tj = 12°C
39.50 kW
39.12 kW
COP Tj = 12°C
6.52
6.38
Cdh Tj = +12 °C
Pdh Tj = Tbiv
37.20 kW
34.16 kW
COP Tj = Tbiv
5.38
3.52
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
37.20 kW
34.16 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
5.38
3.52
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
60 °C
60 °C
Poff
0 W
0 W
PTO
10 W
10 W
PSB
10 W
10 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
12807 kWh
14330 kWh