Certificate holders

Subtype

AQUATOP S14

Certificate Holder
ELCO GmbH
Hohenzollernstrasse 31
72379 Hechingen
Germany
Registration number
011-1W0307
Certification Body
DIN CERTCO Gesellschaft für Konformitätsbewertung mbH
Subtype title
AQUATOP S14
Driving energy
n/a
Heat Pump Type
Brine/Water and Water/Water
Refrigerant
R410A
Mass of Refrigerant

3,400 kg

Certification Date
04.05.2019
Testing basis
n/a
Generate PDF Export model CSV
  • Number of models 1

Models

AQUATOP S14
Configure model
Model name
AQUATOP S14
Application
Heating (medium temp)
Units
Indoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
3x230V 50Hz

Brine/Water Heat Pump

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

13.47 kW

11.99 kW

El input

2.73 kW

4.27 kW

COP

4.94

2.80

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

42 dB(A)

42 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

198 %

158 %

Prated

13.40 kW

11.92 kW

SCOP

5.15

4.15

Tbiv

2 °C

2 °C

TOL

-22 °C

-22 °C

Pdh Tj = +2°C

13.40 kW

11.92 kW

COP Tj = +2°C

4.65

2.79

Cdh Tj = +2 °C

 

 

Pdh Tj = +7°C

13.93 kW

12.99 kW

COP Tj = +7°C

5.20

3.62

Cdh Tj = +7 °C

 

 

Pdh Tj = 12°C

14.07 kW

14.42 kW

COP Tj = 12°C

5.34

5.13

Cdh Tj = +12 °C

 

 

Pdh Tj = Tbiv

13.40 kW

11.92 kW

COP Tj = Tbiv

4.65

2.79

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

13.40 kW

11.92 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.65

2.79

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1.000

1.000

WTOL

65 °C

65 °C

Poff

0 W

0 W

PTO

20 W

20 W

PSB

20 W

20 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

3478 kWh

3834 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

42 dB(A)

42 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

201 %

162 %

Prated

13.40 kW

11.92 kW

SCOP

5.23

4.26

Tbiv

-22 °C

-22 °C

TOL

-22 °C

-22 °C

Pdh Tj = -7°C

14.07 kW

13.11 kW

COP Tj = -7°C

5.34

3.85

Cdh Tj = -7 °C

 

 

Pdh Tj = +2°C

14.07 kW

14.06 kW

COP Tj = +2°C

5.34

4.71

Cdh Tj = +2 °C

 

 

Pdh Tj = +7°C

14.07 kW

14.66 kW

COP Tj = +7°C

5.34

5.41

Cdh Tj = +7 °C

 

 

Pdh Tj = 12°C

14.07 kW

14.90 kW

COP Tj = 12°C

5.34

5.71

Cdh Tj = +12 °C

 

 

Pdh Tj = Tbiv

13.40 kW

11.92 kW

COP Tj = Tbiv

4.65

2.79

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

13.40 kW

11.92 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.65

2.79

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1.000

1.000

WTOL

65 °C

65 °C

Poff

0 W

0 W

PTO

20 W

20 W

PSB

20 W

20 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

6318 kWh

6899 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

42 dB(A)

42 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

199 %

157 %

Prated

13.40 kW

11.92 kW

SCOP

5.18

2.00

Tbiv

-10 °C

-10 °C

TOL

-22 °C

-22 °C

Pdh Tj = -7°C

13.52 kW

12.27 kW

COP Tj = -7°C

4.78

3.04

Cdh Tj = -7 °C

 

 

Pdh Tj = +2°C

14.07 kW

13.35 kW

COP Tj = +2°C

5.34

4.10

Cdh Tj = +2 °C

 

 

Pdh Tj = +7°C

14.07 kW

14.18 kW

COP Tj = +7°C

5.34

4.85

Cdh Tj = +7 °C

 

 

Pdh Tj = 12°C

14.07 kW

14.90 kW

COP Tj = 12°C

5.34

5.71

Cdh Tj = +12 °C

 

 

Pdh Tj = Tbiv

13.40 kW

11.92 kW

COP Tj = Tbiv

4.65

2.79

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

13.40 kW

11.92 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.65

2.79

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1.000

1.000

WTOL

65 °C

65 °C

Poff

0 W

0 W

PTO

20 W

20 W

PSB

20 W

20 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

5348 kWh

5981 kWh

Water/Water Heat Pump

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

17.06 kW

15.52 kW

El input

2.81 kW

4.22 kW

COP

6.07

3.68

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

34 dB(A)

34 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

260 %

211 %

Prated

17.06 kW

15.52 kW

SCOP

6.71

5.47

Tbiv

2 °C

2 °C

TOL

-22 °C

-22 °C

Pdh Tj = +2°C

17.06 kW

15.52 kW

COP Tj = +2°C

6.07

3.68

Cdh Tj = +2 °C

 

 

Pdh Tj = +7°C

17.73 kW

16.91 kW

COP Tj = +7°C

6.79

4.77

Cdh Tj = +7 °C

 

 

Pdh Tj = 12°C

17.91 kW

18.78 kW

COP Tj = 12°C

6.97

6.77

Cdh Tj = +12 °C

 

 

Pdh Tj = Tbiv

17.06 kW

15.52 kW

COP Tj = Tbiv

6.07

3.68

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

17.06 kW

15.52 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

6.07

3.68

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1.000

1.000

WTOL

65 °C

65 °C

Poff

0 W

0 W

PTO

20 W

20 W

PSB

20 W

20 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

3397 kWh

3788 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

34 dB(A)

34 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

265 %

217 %

Prated

17.06 kW

15.52 kW

SCOP

6.82

5.62

Tbiv

-22 °C

-22 °C

TOL

-22 °C

-22 °C

Pdh Tj = -7°C

17.91 kW

17.07 kW

COP Tj = -7°C

6.97

5.08

Cdh Tj = -7 °C

 

 

Pdh Tj = +2°C

17.91 kW

18.31 kW

COP Tj = +2°C

6.97

6.21

Cdh Tj = +2 °C

 

 

Pdh Tj = +7°C

17.91 kW

19.09 kW

COP Tj = +7°C

6.97

7.14

Cdh Tj = +7 °C

 

 

Pdh Tj = 12°C

17.91 kW

19.40 kW

COP Tj = 12°C

6.97

7.53

Cdh Tj = +12 °C

 

 

Pdh Tj = Tbiv

17.06 kW

15.52 kW

COP Tj = Tbiv

6.07

3.68

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

17.06 kW

15.52 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

6.07

3.68

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1.000

1.000

WTOL

65 °C

65 °C

Poff

0 W

0 W

PTO

20 W

20 W

PSB

20 W

20 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

6162 kWh

6804 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

34 dB(A)

34 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

262 %

209 %

Prated

17.06 kW

15.52 kW

SCOP

6.75

5.43

Tbiv

-10 °C

-10 °C

TOL

-22 °C

-22 °C

Pdh Tj = -7°C

17.21 kW

15.98 kW

COP Tj = -7°C

6.24

4.01

Cdh Tj = -7 °C

 

 

Pdh Tj = +2°C

17.91 kW

17.38 kW

COP Tj = +2°C

6.97

5.41

Cdh Tj = +2 °C

 

 

Pdh Tj = +7°C

17.91 kW

18.46 kW

COP Tj = +7°C

6.97

6.40

Cdh Tj = +7 °C

 

 

Pdh Tj = 12°C

17.91 kW

19.40 kW

COP Tj = 12°C

6.97

7.53

Cdh Tj = +12 °C

 

 

Pdh Tj = Tbiv

17.06 kW

15.52 kW

COP Tj = Tbiv

6.07

3.68

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

17.06 kW

15.52 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

6.07

3.68

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1.000

1.000

WTOL

65 °C

65 °C

Poff

0 W

0 W

PTO

20 W

20 W

PSB

20 W

20 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

5221 kWh

5901 kWh