Certificate holders

Subtype

AQUATOP S08

Certificate Holder
ELCO GmbH
Hohenzollernstrasse 31
72379 Hechingen
Germany
Registration number
011-1W0305
Certification Body
DIN CERTCO Gesellschaft für Konformitätsbewertung mbH
Subtype title
AQUATOP S08
Driving energy
n/a
Heat Pump Type
Brine/Water and Water/Water
Refrigerant
R410A
Mass of Refrigerant

2,300 kg

Certification Date
04.05.2019
Testing basis
n/a
Generate PDF Export model CSV
  • Number of models 1

Models

AQUATOP S08
Configure model
Model name
AQUATOP S08
Application
Heating (medium temp)
Units
Indoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
3x230V 50Hz

Brine/Water Heat Pump

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

7.74 kW

6.71 kW

El input

1.44 kW

2.53 kW

COP

4.65

2.65

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

34 dB(A)

34 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

187 %

155 %

Prated

8.25 kW

7.36 kW

SCOP

4.89

4.08

Tbiv

2 °C

2 °C

TOL

-22 °C

-22 °C

Pdh Tj = +2°C

8.25 kW

7.36 kW

COP Tj = +2°C

4.46

2.77

Cdh Tj = +2 °C

 

 

Pdh Tj = +7°C

8.58 kW

8.02 kW

COP Tj = +7°C

4.99

3.60

Cdh Tj = +7 °C

 

 

Pdh Tj = 12°C

8.66 kW

8.90 kW

COP Tj = 12°C

5.12

5.09

Cdh Tj = +12 °C

 

 

Pdh Tj = Tbiv

8.25 kW

7.36 kW

COP Tj = Tbiv

4.46

2.77

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

8.25 kW

7.36 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.46

2.77

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1.000

1.000

WTOL

65 °C

65 °C

Poff

0 W

0 W

PTO

20 W

20 W

PSB

20 W

20 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

2255 kWh

2408 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

34 dB(A)

34 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

191 %

160 %

Prated

8.25 kW

7.36 kW

SCOP

4.98

4.20

Tbiv

-22 °C

-22 °C

TOL

-22 °C

-22 °C

Pdh Tj = -7°C

8.66 kW

8.09 kW

COP Tj = -7°C

5.12

3.82

Cdh Tj = -7 °C

 

 

Pdh Tj = +2°C

8.68 kW

8.68 kW

COP Tj = +2°C

5.12

4.68

Cdh Tj = +2 °C

 

 

Pdh Tj = +7°C

8.68 kW

9.05 kW

COP Tj = +7°C

5.12

5.37

Cdh Tj = +7 °C

 

 

Pdh Tj = 12°C

8.68 kW

9.20 kW

COP Tj = 12°C

5.12

5.67

Cdh Tj = +12 °C

 

 

Pdh Tj = Tbiv

8.25 kW

7.36 kW

COP Tj = Tbiv

4.46

2.77

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

8.25 kW

7.36 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.46

2.77

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1.000

1.000

WTOL

65 °C

65 °C

Poff

0 W

0 W

PTO

20 W

20 W

PSB

20 W

20 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

4086 kWh

4323 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

34 dB(A)

34 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

189 %

154 %

Prated

8.25 kW

7.36 kW

SCOP

4.92

4.06

Tbiv

-10 °C

-10 °C

TOL

-22 °C

-22 °C

Pdh Tj = -7°C

8.33 kW

7.58 kW

COP Tj = -7°C

4.59

3.01

Cdh Tj = -7 °C

 

 

Pdh Tj = +2°C

8.66 kW

8.24 kW

COP Tj = +2°C

5.12

4.07

Cdh Tj = +2 °C

 

 

Pdh Tj = +7°C

8.66 kW

8.75 kW

COP Tj = +7°C

5.12

4.81

Cdh Tj = +7 °C

 

 

Pdh Tj = 12°C

8.25 kW

9.20 kW

COP Tj = 12°C

5.12

5.67

Cdh Tj = +12 °C

 

 

Pdh Tj = Tbiv

8.25 kW

7.36 kW

COP Tj = Tbiv

4.46

2.77

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

8.25 kW

7.36 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.46

2.77

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1.000

1.000

WTOL

65 °C

65 °C

Poff

0 W

0 W

PTO

20 W

20 W

PSB

20 W

20 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

3461 kWh

3749 kWh

Water/Water Heat Pump

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

9.84 kW

8.95 kW

El input

1.73 kW

2.60 kW

COP

5.69

3.44

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

34 dB(A)

34 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

241 %

195 %

Prated

9.84 kW

8.95 kW

SCOP

6.23

5.07

Tbiv

2 °C

2 °C

TOL

-22 °C

-22 °C

Pdh Tj = +2°C

9.84 kW

8.95 kW

COP Tj = +2°C

5.69

3.44

Cdh Tj = +2 °C

 

 

Pdh Tj = +7°C

10.23 kW

9.75 kW

COP Tj = +7°C

6.37

4.47

Cdh Tj = +7 °C

 

 

Pdh Tj = 12°C

10.33 kW

10.82 kW

COP Tj = 12°C

6.53

6.32

Cdh Tj = +12 °C

 

 

Pdh Tj = Tbiv

9.84 kW

8.95 kW

COP Tj = Tbiv

5.69

3.44

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

9.84 kW

8.95 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

5.69

3.44

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1.000

1.000

WTOL

65 °C

65 °C

Poff

0 W

0 W

PTO

20 W

20 W

PSB

20 W

20 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

2112 kWh

2360 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

34 dB(A)

34 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

246 %

200 %

Prated

9.84 kW

8.95 kW

SCOP

6.34

5.21

Tbiv

-22 °C

-22 °C

TOL

-22 °C

-22 °C

Pdh Tj = -7°C

10.33 kW

9.84 kW

COP Tj = -7°C

3.44

4.74

Cdh Tj = -7 °C

 

 

Pdh Tj = +2°C

10.33 kW

10.56 kW

COP Tj = +2°C

6.53

5.81

Cdh Tj = +2 °C

 

 

Pdh Tj = +7°C

10.33 kW

11.01 kW

COP Tj = +7°C

6.53

6.67

Cdh Tj = +7 °C

 

 

Pdh Tj = 12°C

10.33 kW

11.19 kW

COP Tj = 12°C

6.53

7.04

Cdh Tj = +12 °C

 

 

Pdh Tj = Tbiv

9.84 kW

8.95 kW

COP Tj = Tbiv

5.69

3.44

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

9.84 kW

8.95 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

5.69

3.44

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1.000

1.000

WTOL

65 °C

65 °C

Poff

0 W

0 W

PTO

20 W

20 W

PSB

20 W

20 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

3826 kWh

4235 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

34 dB(A)

34 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

243 %

193 %

Prated

9.84 kW

8.95 kW

SCOP

6.28

5.04

Tbiv

-10 °C

-10 °C

TOL

-22 °C

-22 °C

Pdh Tj = -7°C

9.94 kW

9.22 kW

COP Tj = -7°C

5.86

3.74

Cdh Tj = -7 °C

 

 

Pdh Tj = +2°C

10.33 kW

10.02 kW

COP Tj = +2°C

6.53

5.05

Cdh Tj = +2 °C

 

 

Pdh Tj = +7°C

10.33 kW

10.64 kW

COP Tj = +7°C

6.53

5.97

Cdh Tj = +7 °C

 

 

Pdh Tj = 12°C

10.33 kW

11.19 kW

COP Tj = 12°C

6.53

7.04

Cdh Tj = +12 °C

 

 

Pdh Tj = Tbiv

9.84 kW

8.95 kW

COP Tj = Tbiv

5.69

3.44

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

9.84 kW

8.95 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

5.69

3.44

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1.000

1.000

WTOL

65 °C

65 °C

Poff

0 W

0 W

PTO

20 W

20 W

PSB

20 W

20 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

3238 kWh

3671 kWh