6,500 kg
Average Climate
EN 14511-3 at 15 °C / 60 °C (Annex A Part D)
Heat output
35.00 kW
El input
9.72 kW
COP
3.60
EN 12102-1
Sound power level outdoor
76 dB(A)
Operating test
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Starting and operating test
passed