2,200 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
2.06 kW
2.09 kW
El input
0.44 kW
0.81 kW
COP
4.68
2.59
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
45 dB(A)
45 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
198 %
136 %
Prated
2.62 kW
2.40 kW
SCOP
5.01
3.47
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
2.62 kW
2.37 kW
COP Tj = +2°C
3.76
2.28
Cdh Tj = +2 °C
Pdh Tj = +7°C
2.07 kW
1.84 kW
COP Tj = +7°C
5.19
3.35
Cdh Tj = +7 °C
Pdh Tj = 12°C
2.00 kW
1.94 kW
COP Tj = 12°C
7.92
5.39
Cdh Tj = +12 °C
Pdh Tj = Tbiv
2.62 kW
2.37 kW
COP Tj = Tbiv
3.76
2.28
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
2.62 kW
2.37 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.76
2.28
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
60 °C
60 °C
Poff
56 W
56 W
PTO
21 W
21 W
PSB
56 W
56 W
PCK
26 W
26 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
698 kWh
923 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
45 dB(A)
45 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
150 %
116 %
Prated
6.80 kW
6.70 kW
SCOP
3.83
2.98
Tbiv
-7 °C
-7 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
4.11 kW
4.05 kW
COP Tj = -7°C
3.37
2.57
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
3.01 kW
2.60 kW
COP Tj = +2°C
5.17
3.55
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
2.09 kW
2.07 kW
COP Tj = +7°C
7.26
5.31
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
2.02 kW
1.99 kW
COP Tj = 12°C
8.96
7.11
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
4.11 kW
4.05 kW
COP Tj = Tbiv
3.37
2.57
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
2.35 kW
6.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.99
1.00
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
60 °C
60 °C
Poff
56 W
56 W
PTO
21 W
21 W
PSB
56 W
56 W
PCK
26 W
26 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
6.80 kW
6.70 kW
Annual energy consumption Qhe
4382 kWh
5547 kWh
Pdh Tj = -15°C (if TOL<-20°C)
4.11
4.05
COP Tj = -15°C (if TOL<-20°C)
3.37
2.57
Cdh Tj = -15 °C
0.900
0.900
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
45 dB(A)
45 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
175 %
128 %
Prated
4.70 kW
4.50 kW
SCOP
4.46
3.28
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
4.17 kW
3.94 kW
COP Tj = -7°C
3.09
2.22
Pdh Tj = +2°C
2.86 kW
2.54 kW
COP Tj = +2°C
4.29
3.10
Pdh Tj = +7°C
2.08 kW
2.04 kW
COP Tj = +7°C
6.24
4.53
Pdh Tj = 12°C
2.02 kW
1.97 kW
COP Tj = 12°C
8.31
6.44
Pdh Tj = Tbiv
4.17 kW
3.94 kW
COP Tj = Tbiv
3.09
2.22
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
4.06 kW
2.96 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.71
1.94
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.90
0.90
WTOL
60 °C
60 °C
Poff
56 W
56 W
PTO
21 W
21 W
PSB
56 W
56 W
PCK
26 W
26 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.64 kW
1.54 kW
Annual energy consumption Qhe
2187 kWh
2837 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
2.06 kW
2.10 kW
El input
0.44 kW
0.80 kW
COP
4.68
2.64
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
45 dB(A)
45 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
198 %
136 %
Prated
2.64 kW
2.40 kW
SCOP
5.03
3.48
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
2.64 kW
2.39 kW
COP Tj = +2°C
3.83
2.33
Cdh Tj = +2 °C
Pdh Tj = +7°C
2.07 kW
1.84 kW
COP Tj = +7°C
5.19
3.35
Cdh Tj = +7 °C
Pdh Tj = 12°C
2.00 kW
1.94 kW
COP Tj = 12°C
7.92
5.39
Cdh Tj = +12 °C
Pdh Tj = Tbiv
2.64 kW
2.39 kW
COP Tj = Tbiv
3.83
2.33
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
2.64 kW
2.39 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.83
2.33
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
60 °C
60 °C
Poff
56 W
56 W
PTO
21 W
21 W
PSB
56 W
56 W
PCK
26 W
26 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
70 kWh
921 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
45 dB(A)
45 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
155 %
119 %
Prated
6.90 kW
6.80 kW
SCOP
3.94
3.04
Tbiv
-7 °C
-7 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
4.16 kW
4.10 kW
COP Tj = -7°C
3.48
2.63
Cdh Tj = -7 °C
Pdh Tj = +2°C
3.03 kW
2.62 kW
COP Tj = +2°C
5.34
3.64
Cdh Tj = +2 °C
Pdh Tj = +7°C
2.09 kW
2.07 kW
COP Tj = +7°C
7.26
5.31
Cdh Tj = +7 °C
Pdh Tj = 12°C
2.02 kW
1.99 kW
COP Tj = 12°C
8.96
7.11
Cdh Tj = +12 °C
Pdh Tj = Tbiv
4.16 kW
4.10 kW
COP Tj = Tbiv
3.48
2.63
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.00 kW
3.16 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
1.00
2.50
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
60 °C
60 °C
Poff
56 W
56 W
PTO
21 W
21 W
PSB
56 W
56 W
PCK
26 W
26 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
6.90 kW
6.80 kW
Annual energy consumption Qhe
4321 kWh
5515 kWh
Pdh Tj = -15°C (if TOL<-20°C)
COP Tj = -15°C (if TOL<-20°C)
Cdh Tj = -15 °C
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
45 dB(A)
45 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
178 %
130 %
Prated
4.80 kW
4.50 kW
SCOP
4.53
3.32
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
4.22 kW
3.98 kW
COP Tj = -7°C
3.22
2.27
Pdh Tj = +2°C
2.88 kW
2.55 kW
COP Tj = +2°C
4.33
3.16
Pdh Tj = +7°C
2.08 kW
2.04 kW
COP Tj = +7°C
6.28
4.53
Pdh Tj = 12°C
2.02 kW
1.97 kW
COP Tj = 12°C
8.35
6.44
Pdh Tj = Tbiv
4.22 kW
3.98 kW
COP Tj = Tbiv
3.22
2.27
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
4.11 kW
3.79 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.84
1.85
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.90
0.90
WTOL
60 °C
60 °C
Poff
56 W
56 W
PTO
21 W
21 W
PSB
56 W
56 W
PCK
26 W
26 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.69 kW
0.71 kW
Annual energy consumption Qhe
2187 kWh
2804 kWh