5,990 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
21.50 kW
20.10 kW
El input
4.61 kW
7.08 kW
COP
4.66
2.84
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
59 dB(A)
59 dB(A)
Sound power level outdoor
59 dB(A)
59 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
188 %
128 %
Prated
22.00 kW
20.00 kW
SCOP
4.90
3.40
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
21.50 kW
20.10 kW
COP Tj = +2°C
4.66
2.84
Pdh Tj = +7°C
21.70 kW
20.50 kW
COP Tj = +7°C
4.99
3.24
Pdh Tj = 12°C
21.90 kW
21.10 kW
COP Tj = 12°C
5.54
4.03
Pdh Tj = Tbiv
21.50 kW
20.10 kW
COP Tj = Tbiv
4.66
2.84
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
21.50 kW
20.10 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.66
2.84
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.90
0.90
WTOL
60 °C
60 °C
Poff
0 W
0 W
PTO
7 W
7 W
PSB
7 W
7 W
PCK
74 W
74 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
5871 kWh
7884 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
59 dB(A)
59 dB(A)
Sound power level outdoor
59 dB(A)
59 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
201 %
137 %
Prated
27.00 kW
25.00 kW
SCOP
5.23
3.62
Tbiv
-15 °C
-15 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
21.80 kW
20.70 kW
COP Tj = -7°C
5.24
3.46
Cdh Tj = -7 °C
Pdh Tj = +2°C
21.90 kW
21.00 kW
COP Tj = +2°C
5.51
3.87
Cdh Tj = +2 °C
Pdh Tj = +7°C
21.90 kW
21.30 kW
COP Tj = +7°C
5.74
4.26
Cdh Tj = +7 °C
Pdh Tj = 12°C
22.00 kW
21.50 kW
COP Tj = 12°C
5.78
4.60
Cdh Tj = +12 °C
Pdh Tj = Tbiv
21.70 kW
20.50 kW
COP Tj = Tbiv
5.12
3.24
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
21.50 kW
21.10 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.66
2.84
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
60 °C
60 °C
Poff
0 W
0 W
PTO
7 W
7 W
PSB
7 W
7 W
PCK
74 W
74 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
5.11 kW
4.00 kW
Annual energy consumption Qhe
12535 kWh
17067 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
59 dB(A)
59 dB(A)
Sound power level outdoor
59 dB(A)
59 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
192 %
131 %
Prated
22.00 kW
20.00 kW
SCOP
5.00
3.48
Tbiv
-10 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
21.50 kW
20.20 kW
COP Tj = -7°C
4.72
2.96
Pdh Tj = +2°C
21.70 kW
20.70 kW
COP Tj = +2°C
5.06
3.48
Pdh Tj = +7°C
21.80 kW
21.00 kW
COP Tj = +7°C
5.41
3.88
Pdh Tj = 12°C
22.00 kW
21.30 kW
COP Tj = 12°C
5.80
4.36
Pdh Tj = Tbiv
21.50 kW
20.10 kW
COP Tj = Tbiv
4.66
2.84
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
21.50 kW
20.10 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.66
2.84
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.90
0.90
WTOL
60 °C
60 °C
Poff
0 W
0 W
PTO
7 W
7 W
PSB
7 W
7 W
PCK
74 W
74 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
8904 kWh
11988 kWh