10,000 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
37.70 kW
34.49 kW
El input
7.98 kW
11.47 kW
COP
4.72
3.01
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
60 dB(A)
60 dB(A)
Sound power level outdoor
60 dB(A)
60 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
199 %
132 %
Prated
38.00 kW
34.00 kW
SCOP
5.17
3.50
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = -7°C
0.00 kW
0.00 kW
COP Tj = -7°C
0.00
0.00
Pdh Tj = +2°C
38.00 kW
34.10 kW
COP Tj = +2°C
4.78
2.82
Pdh Tj = +7°C
38.50 kW
35.20 kW
COP Tj = +7°C
5.12
3.24
Pdh Tj = 12°C
39.10 kW
37.00 kW
COP Tj = 12°C
5.69
4.08
Pdh Tj = Tbiv
38.00 kW
34.10 kW
COP Tj = Tbiv
4.78
2.82
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
38.00 kW
34.10 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.78
2.82
Rated airflow rate
0 m³/h
0 m³/h
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.90
0.90
WTOL
60 °C
60 °C
Poff
0 W
0 W
PTO
7 W
7 W
PSB
7 W
7 W
PCK
7 W
74 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
9834 kWh
13033 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
60 dB(A)
60 dB(A)
Sound power level outdoor
60 dB(A)
60 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
208 %
139 %
Prated
47.00 kW
43.00 kW
SCOP
5.41
3.66
Tbiv
-15 °C
-15 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
38.80 kW
35.80 kW
COP Tj = -7°C
5.38
3.48
Cdh Tj = -7 °C
Pdh Tj = +2°C
39.10 kW
36.70 kW
COP Tj = +2°C
5.67
3.91
Cdh Tj = +2 °C
Pdh Tj = +7°C
39.30 kW
37.40 kW
COP Tj = +7°C
5.90
4.32
Cdh Tj = +7 °C
Pdh Tj = 12°C
39.30 kW
37.90 kW
COP Tj = 12°C
5.94
4.66
Cdh Tj = +12 °C
Pdh Tj = Tbiv
38.60 kW
35.30 kW
COP Tj = Tbiv
5.26
3.25
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
38.60 kW
34.10 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
5.26
2.82
Rated airflow rate
0 m³/h
0 m³/h
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
60 °C
60 °C
Poff
0 W
0 W
PTO
7 W
7 W
PSB
7 W
7 W
PCK
74 W
74 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
8.40 kW
9.15 kW
Annual energy consumption Qhe
21594 kWh
28986 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
60 dB(A)
60 dB(A)
Sound power level outdoor
60 dB(A)
60 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
200 %
133 %
Prated
38.00 kW
34.00 kW
SCOP
5.19
3.52
Tbiv
-10 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
38.10 kW
34.50 kW
COP Tj = -7°C
4.84
2.95
Pdh Tj = +2°C
38.60 kW
35.80 kW
COP Tj = +2°C
5.20
3.50
Pdh Tj = +7°C
39.00 kW
36.70 kW
COP Tj = +7°C
5.56
2.92
Pdh Tj = 12°C
39.30 kW
37.50 kW
COP Tj = 12°C
5.96
4.42
Pdh Tj = Tbiv
38.00 kW
34.10 kW
COP Tj = Tbiv
4.75
2.82
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
38.00 kW
34.10 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.78
2.82
Rated airflow rate
0 m³/h
0 m³/h
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.90
0.90
WTOL
60 °C
60 °C
Poff
0 W
0 W
PTO
7 W
7 W
PSB
7 W
7 W
PCK
74 W
74 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
15136 kWh
20029 kWh