2,600 kg
Heating
EN 14511-2
Heat output
9.70 kW
El input
2.22 kW
COP
4.37
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
failed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Sound power level indoor
58 dB(A)
EN 14825
ηs
190 %
Prated
10.00 kW
SCOP
4.95
Tbiv
2 °C
TOL
0 °C
Pdh Tj = +2°C
9.70 kW
COP Tj = +2°C
4.37
Cdh Tj = +2 °C
0.900
Pdh Tj = +7°C
9.80 kW
COP Tj = +7°C
4.76
Cdh Tj = +7 °C
0.900
Pdh Tj = 12°C
10.00 kW
COP Tj = 12°C
5.44
Cdh Tj = +12 °C
0.900
Pdh Tj = Tbiv
9.70 kW
COP Tj = Tbiv
4.37
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
9.70 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.37
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
WTOL
60 °C
Poff
0 W
PTO
78 W
PSB
3 W
PCK
0 W
Supplementary Heater: Type of energy input
Electricity
Supplementary Heater: PSUP
0.30 kW
Annual energy consumption Qhe
2617 kWh
Colder Climate
EN 12102-1
Sound power level indoor
58 dB(A)
EN 14825
ηs
199 %
Prated
12.00 kW
SCOP
5.17
Tbiv
-15 °C
TOL
-22 °C
Pdh Tj = -7°C
9.90 kW
COP Tj = -7°C
5.07
Cdh Tj = -7 °C
0.900
Pdh Tj = +2°C
10.00 kW
COP Tj = +2°C
5.41
Cdh Tj = +2 °C
0.900
Pdh Tj = +7°C
10.10 kW
COP Tj = +7°C
5.70
Cdh Tj = +7 °C
0.900
Pdh Tj = 12°C
10.10 kW
COP Tj = 12°C
5.75
Cdh Tj = +12 °C
0.900
Pdh Tj = Tbiv
9.90 kW
COP Tj = Tbiv
4.93
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
9.90 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.93
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
WTOL
60 °C
Poff
0 W
PTO
78 W
PSB
3 W
PCK
0 W
Supplementary Heater: Type of energy input
Electricity
Supplementary Heater: PSUP
2.10 kW
Annual energy consumption Qhe
5768 kWh
Pdh Tj = -15°C (if TOL<-20°C)
9.90
COP Tj = -15°C (if TOL<-20°C)
4.93
Cdh Tj = -15 °C
0.90
Average Climate
EN 12102-1
Sound power level indoor
58 dB(A)
EN 14825
ηs
190 %
Prated
10.00 kW
SCOP
4.94
Tbiv
-10 °C
TOL
-20 °C
Pdh Tj = -7°C
9.70 kW
COP Tj = -7°C
4.44
Cdh Tj = -7 °C
0.900
Pdh Tj = +2°C
9.80 kW
COP Tj = +2°C
4.85
Cdh Tj = +2 °C
0.900
Pdh Tj = +7°C
10.00 kW
COP Tj = +7°C
5.28
Cdh Tj = +7 °C
0.900
Pdh Tj = 12°C
10.10 kW
COP Tj = 12°C
5.78
Cdh Tj = +12 °C
0.900
Pdh Tj = Tbiv
9.70 kW
COP Tj = Tbiv
4.37
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
9.70 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.37
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
WTOL
60 °C
Poff
0 W
PTO
78 W
PSB
3 W
PCK
0 W
Supplementary Heater: Type of energy input
Electricity
Supplementary Heater: PSUP
0.30 kW
Annual energy consumption Qhe
4053 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
9.70 kW
8.57 kW
El input
2.22 kW
3.67 kW
COP
4.37
2.34
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
failed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
58 dB(A)
58 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
190 %
114 %
Prated
10.00 kW
9.00 kW
SCOP
4.94
3.06
Tbiv
-10 °C
-10 °C
TOL
-20 °C
-10 °C
Pdh Tj = -7°C
9.70 kW
8.70 kW
COP Tj = -7°C
4.44
2.46
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
9.80 kW
9.10 kW
COP Tj = +2°C
4.85
2.99
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
10.00 kW
9.30 kW
COP Tj = +7°C
5.28
3.42
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
10.10 kW
9.50 kW
COP Tj = 12°C
5.78
3.95
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
9.70 kW
8.60 kW
COP Tj = Tbiv
4.37
2.34
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
9.70 kW
8.60 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.37
2.34
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
WTOL
60 °C
60 °C
Poff
0 W
0 W
PTO
78 W
78 W
PSB
3 W
3 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.30 kW
0.00 kW
Annual energy consumption Qhe
4053 kWh
5788 kWh