1,350 kg
Brine/Water Heat Pump
Heating
EN 14511-4
Starting and operating test
passed
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
EN 14511-2
Low temperature
Medium temperature
Heat output
5.85 kW
5.24 kW
El input
1.35 kW
1.91 kW
COP
4.33
2.75
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
35 dB(A)
35 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
200 %
141 %
Prated
5.85 kW
5.24 kW
SCOP
5.21
3.73
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
5.85 kW
5.24 kW
COP Tj = +2°C
4.33
2.75
Cdh Tj = +2 °C
0.990
0.990
Pdh Tj = +7°C
3.98 kW
3.63 kW
COP Tj = +7°C
5.14
3.47
Cdh Tj = +7 °C
0.990
0.990
Pdh Tj = 12°C
2.12 kW
1.97 kW
COP Tj = 12°C
5.90
4.46
Cdh Tj = +12 °C
0.970
0.970
Pdh Tj = Tbiv
5.85 kW
5.24 kW
COP Tj = Tbiv
4.33
2.75
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.85 kW
5.24 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.33
2.75
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.990
0.990
WTOL
67 °C
67 °C
Poff
11 W
11 W
PTO
11 W
11 W
PSB
11 W
11 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
1500 kWh
1876 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
35 dB(A)
35 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
210 %
151 %
Prated
5.85 kW
5.24 kW
SCOP
5.44
3.99
Tbiv
-22 °C
-22 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
3.62 kW
3.29 kW
COP Tj = -7°C
5.29
3.71
Cdh Tj = -7 °C
Pdh Tj = +2°C
2.34 kW
1.94 kW
COP Tj = +2°C
5.85
4.37
Cdh Tj = +2 °C
Pdh Tj = +7°C
2.13 kW
1.98 kW
COP Tj = +7°C
5.86
4.69
Cdh Tj = +7 °C
Pdh Tj = 12°C
2.11 kW
2.00 kW
COP Tj = 12°C
5.78
4.78
Cdh Tj = +12 °C
Pdh Tj = Tbiv
5.85 kW
5.24 kW
COP Tj = Tbiv
4.33
2.75
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.85 kW
5.24 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.33
2.75
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
WTOL
67 °C
67 °C
Poff
11 W
11 W
PTO
11 W
11 W
PSB
11 W
11 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
2650 kWh
3241 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
35 dB(A)
35 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
202 %
145 %
Prated
5.85 kW
5.24 kW
SCOP
5.26
3.82
Tbiv
-10 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
5.13 kW
4.58 kW
COP Tj = -7°C
4.53
2.97
Cdh Tj = -7 °C
0.990
0.990
Pdh Tj = +2°C
3.34 kW
3.04 kW
COP Tj = +2°C
5.39
3.87
Cdh Tj = +2 °C
0.980
0.990
Pdh Tj = +7°C
2.12 kW
1.97 kW
COP Tj = +7°C
5.87
4.52
Cdh Tj = +7 °C
0.970
0.970
Pdh Tj = 12°C
2.12 kW
1.97 kW
COP Tj = 12°C
5.91
4.57
Cdh Tj = +12 °C
0.970
0.970
Pdh Tj = Tbiv
5.85 kW
5.24 kW
COP Tj = Tbiv
4.33
2.75
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.84 kW
5.24 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.33
2.75
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.990
0.990
WTOL
67 °C
67 °C
Poff
11 W
11 W
PTO
11 W
11 W
PSB
11 W
11 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
2298 kWh
2835 kWh
Domestic Hot Water (DHW)
Warmer Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
126 %
COP
3.06
Heating up time
1:35 h:min
Standby power input
30.9 W
Reference hot water temperature
47.6 °C
Mixed water at 40°C
211 l
Colder Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
126 %
COP
3.06
Heating up time
1:35 h:min
Standby power input
30.9 W
Reference hot water temperature
47.6 °C
Mixed water at 40°C
211 l
Average Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
126 %
COP
3.06
Heating up time
1:35 h:min
Standby power input
30.9 W
Reference hot water temperature
47.6 °C
Mixed water at 40°C
211 l
Water/Water Heat Pump
Heating
EN 14511-4
Starting and operating test
passed
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
EN 14511-2
Low temperature
Medium temperature
Heat output
7.80 kW
6.89 kW
El input
1.38 kW
2.03 kW
COP
5.66
3.40
Average Climate
EN 14825
Low temperature
Medium temperature
ηs
300 %
202 %
Prated
7.80 kW
6.89 kW
SCOP
7.70
5.24
Tbiv
-10 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
6.94 kW
6.22 kW
COP Tj = -7°C
6.07
3.78
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
4.34 kW
3.64 kW
COP Tj = +2°C
7.77
5.29
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
2.80 kW
2.61 kW
COP Tj = +7°C
9.40
6.44
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
2.80 kW
2.65 kW
COP Tj = 12°C
9.35
6.74
Cdh Tj = +12 °C
0.960
0.970
Pdh Tj = Tbiv
7.80 kW
6.89 kW
COP Tj = Tbiv
5.66
3.40
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.80 kW
6.89 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
5.66
3.40
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
67 °C
67 °C
Poff
11 W
11 W
PTO
11 W
11 W
PSB
11 W
11 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
2092 kWh
2721 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
xl
Efficiency ηDHW
126 %
COP
3.06
Heating up time
1:35 h:min
Standby power input
30.9 W
Reference hot water temperature
47.6 °C
Mixed water at 40°C
211 l
Brine/Water Heat Pump
Heating
EN 14511-4
Starting and operating test
passed
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
EN 14511-2
Low temperature
Medium temperature
Heat output
5.85 kW
5.24 kW
El input
1.35 kW
1.91 kW
COP
4.33
2.75
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
36 dB(A)
36 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
200 %
141 %
Prated
5.85 kW
5.24 kW
SCOP
5.21
3.73
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
5.85 kW
5.24 kW
COP Tj = +2°C
4.33
2.75
Cdh Tj = +2 °C
0.990
0.990
Pdh Tj = +7°C
3.98 kW
3.63 kW
COP Tj = +7°C
5.14
3.47
Cdh Tj = +7 °C
0.990
0.990
Pdh Tj = 12°C
2.12 kW
1.97 kW
COP Tj = 12°C
5.90
4.46
Cdh Tj = +12 °C
0.970
0.970
Pdh Tj = Tbiv
5.85 kW
5.24 kW
COP Tj = Tbiv
4.33
2.75
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.85 kW
5.24 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.33
2.75
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.990
0.990
WTOL
67 °C
67 °C
Poff
11 W
11 W
PTO
11 W
11 W
PSB
11 W
11 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
1500 kWh
1876 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
36 dB(A)
36 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
210 %
151 %
Prated
5.85 kW
5.24 kW
SCOP
5.44
3.99
Tbiv
-22 °C
-22 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
3.62 kW
3.29 kW
COP Tj = -7°C
5.29
3.71
Cdh Tj = -7 °C
0.980
0.990
Pdh Tj = +2°C
2.34 kW
1.94 kW
COP Tj = +2°C
5.85
4.37
Cdh Tj = +2 °C
0.970
0.970
Pdh Tj = +7°C
2.13 kW
1.98 kW
COP Tj = +7°C
5.86
4.69
Cdh Tj = +7 °C
0.970
0.970
Pdh Tj = 12°C
2.11 kW
2.00 kW
COP Tj = 12°C
5.78
4.78
Cdh Tj = +12 °C
0.970
0.970
Pdh Tj = Tbiv
5.85 kW
5.24 kW
COP Tj = Tbiv
4.33
2.75
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.85 kW
5.24 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.33
2.75
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.990
0.990
WTOL
67 °C
67 °C
Poff
11 W
11 W
PTO
11 W
11 W
PSB
11 W
11 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
2650 kWh
3241 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
36 dB(A)
36 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
202 %
145 %
Prated
5.85 kW
5.24 kW
SCOP
5.26
3.82
Tbiv
-10 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
5.13 kW
4.85 kW
COP Tj = -7°C
4.53
2.97
Cdh Tj = -7 °C
0.990
0.990
Pdh Tj = +2°C
3.34 kW
3.04 kW
COP Tj = +2°C
5.39
3.87
Cdh Tj = +2 °C
0.980
0.990
Pdh Tj = +7°C
2.12 kW
1.97 kW
COP Tj = +7°C
5.87
4.52
Cdh Tj = +7 °C
0.970
0.970
Pdh Tj = 12°C
2.12 kW
1.97 kW
COP Tj = 12°C
5.91
4.57
Cdh Tj = +12 °C
0.970
0.970
Pdh Tj = Tbiv
5.85 kW
5.24 kW
COP Tj = Tbiv
4.33
2.75
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.85 kW
5.24 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.33
2.75
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.990
0.990
WTOL
67 °C
67 °C
Poff
11 W
11 W
PTO
11 W
11 W
PSB
11 W
11 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
2298 kWh
2835 kWh
Water/Water Heat Pump
Heating
EN 14511-4
Starting and operating test
passed
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
EN 14511-2
Low temperature
Medium temperature
Heat output
7.80 kW
6.89 kW
El input
1.38 kW
2.03 kW
COP
5.66
3.40
Average Climate
EN 14825
Low temperature
Medium temperature
ηs
300 %
202 %
Prated
7.80 kW
6.89 kW
SCOP
7.70
5.24
Tbiv
-10 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
6.94 kW
6.22 kW
COP Tj = -7°C
6.07
3.78
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
4.34 kW
3.64 kW
COP Tj = +2°C
7.77
5.29
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
2.80 kW
2.61 kW
COP Tj = +7°C
9.24
6.44
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
2.80 kW
2.65 kW
COP Tj = 12°C
9.35
6.74
Cdh Tj = +12 °C
1.000
1.000
Pdh Tj = Tbiv
7.80 kW
6.89 kW
COP Tj = Tbiv
5.66
3.40
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.80 kW
6.89 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
5.66
3.40
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
67 °C
67 °C
Poff
11 W
11 W
PTO
11 W
11 W
PSB
11 W
11 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
2092 kWh
2721 kWh
Brine/Water Heat Pump
Heating
EN 14511-4
Starting and operating test
passed
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
EN 14511-2
Low temperature
Medium temperature
Heat output
7.63 kW
6.74 kW
El input
1.87 kW
2.57 kW
COP
4.08
2.62
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
36 dB(A)
36 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
202 %
144 %
Prated
7.62 kW
6.74 kW
SCOP
5.26
3.80
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
7.62 kW
6.74 kW
COP Tj = +2°C
4.08
2.62
Cdh Tj = +2 °C
0.990
1.000
Pdh Tj = +7°C
5.23 kW
4.15 kW
COP Tj = +7°C
5.07
3.58
Cdh Tj = +7 °C
0.990
0.990
Pdh Tj = 12°C
2.67 kW
2.00 kW
COP Tj = 12°C
6.02
4.89
Cdh Tj = +12 °C
0.970
0.970
Pdh Tj = Tbiv
7.62 kW
6.74 kW
COP Tj = Tbiv
4.08
2.62
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.62 kW
6.74 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.08
2.62
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.990
1.000
WTOL
67 °C
67 °C
Poff
11 W
11 W
PTO
11 W
11 W
PSB
11 W
11 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
1935 kWh
2369 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
36 dB(A)
36 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
214 %
157 %
Prated
7.62 kW
6.74 kW
SCOP
5.56
4.13
Tbiv
-22 °C
-22 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
4.59 kW
4.22 kW
COP Tj = -7°C
5.35
3.77
Cdh Tj = -7 °C
0.990
0.990
Pdh Tj = +2°C
3.01 kW
2.51 kW
COP Tj = +2°C
6.00
4.58
Cdh Tj = +2 °C
0.980
0.980
Pdh Tj = +7°C
2.14 kW
2.02 kW
COP Tj = +7°C
6.21
5.06
Cdh Tj = +7 °C
0.970
0.970
Pdh Tj = 12°C
2.11 kW
2.02 kW
COP Tj = 12°C
5.95
5.06
Cdh Tj = +12 °C
0.970
0.970
Pdh Tj = Tbiv
7.62 kW
6.74 kW
COP Tj = Tbiv
4.08
2.62
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.62 kW
6.74 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.08
2.62
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.990
1.000
WTOL
67 °C
67 °C
Poff
11 W
11 W
PTO
11 W
11 W
PSB
11 W
11 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
3381 kWh
4024 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
36 dB(A)
36 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
203 %
150 %
Prated
7.63 kW
6.74 kW
SCOP
5.28
3.95
Tbiv
-10 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
7.06 kW
5.86 kW
COP Tj = -7°C
4.29
2.94
Cdh Tj = -7 °C
0.990
0.990
Pdh Tj = +2°C
4.24 kW
3.76 kW
COP Tj = +2°C
5.37
4.01
Cdh Tj = +2 °C
0.990
0.990
Pdh Tj = +7°C
2.67 kW
2.53 kW
COP Tj = +7°C
6.00
4.70
Cdh Tj = +7 °C
0.970
0.980
Pdh Tj = 12°C
2.11 kW
1.99 kW
COP Tj = 12°C
6.12
4.86
Cdh Tj = +12 °C
0.970
0.970
Pdh Tj = Tbiv
7.63 kW
6.74 kW
COP Tj = Tbiv
4.08
2.62
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.62 kW
6.74 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.08
2.62
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.990
1.000
WTOL
67 °C
67 °C
Poff
11 W
11 W
PTO
11 W
11 W
PSB
11 W
11 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
2984 kWh
3530 kWh
Domestic Hot Water (DHW)
Warmer Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
124 %
COP
3.01
Heating up time
1:31 h:min
Standby power input
87.0 W
Reference hot water temperature
47.6 °C
Mixed water at 40°C
211 l
Colder Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
124 %
COP
3.01
Heating up time
1:31 h:min
Standby power input
87.0 W
Reference hot water temperature
47.6 °C
Mixed water at 40°C
211 l
Average Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
124 %
COP
3.01
Heating up time
1:31 h:min
Standby power input
87.0 W
Reference hot water temperature
47.6 °C
Mixed water at 40°C
211 l
Water/Water Heat Pump
Heating
EN 14511-4
Starting and operating test
passed
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
EN 14511-2
Low temperature
Medium temperature
Heat output
10.03 kW
9.09 kW
El input
1.99 kW
2.87 kW
COP
5.04
3.17
Average Climate
EN 14825
Low temperature
Medium temperature
ηs
288 %
201 %
Prated
9.09 kW
9.09 kW
SCOP
7.40
5.23
Tbiv
-10 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
9.31 kW
7.85 kW
COP Tj = -7°C
5.37
3.60
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
5.50 kW
4.98 kW
COP Tj = +2°C
7.38
5.25
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
3.53 kW
3.36 kW
COP Tj = +7°C
9.18
6.53
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
2.80 kW
2.65 kW
COP Tj = 12°C
9.60
7.00
Cdh Tj = +12 °C
0.960
0.970
Pdh Tj = Tbiv
10.03 kW
9.09 kW
COP Tj = Tbiv
5.04
3.17
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
10.03 kW
9.09 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
5.04
3.17
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
67 °C
67 °C
Poff
11 W
11 W
PTO
11 W
11 W
PSB
11 W
11 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
2800 kWh
3591 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
148 %
COP
3.59
Heating up time
1:11 h:min
Standby power input
30.3 W
Reference hot water temperature
47.1 °C
Mixed water at 40°C
204 l
Brine/Water Heat Pump
Heating
EN 14511-4
Starting and operating test
passed
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
EN 14511-2
Low temperature
Medium temperature
Heat output
7.63 kW
6.74 kW
El input
1.87 kW
2.57 kW
COP
4.08
2.62
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
36 dB(A)
36 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
202 %
144 %
Prated
7.62 kW
6.74 kW
SCOP
5.26
3.80
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
7.62 kW
6.74 kW
COP Tj = +2°C
4.08
2.62
Cdh Tj = +2 °C
0.990
1.000
Pdh Tj = +7°C
5.23 kW
4.15 kW
COP Tj = +7°C
5.07
3.58
Cdh Tj = +7 °C
0.990
0.990
Pdh Tj = 12°C
2.67 kW
2.00 kW
COP Tj = 12°C
6.02
4.89
Cdh Tj = +12 °C
0.970
0.970
Pdh Tj = Tbiv
7.62 kW
6.74 kW
COP Tj = Tbiv
4.08
2.62
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.62 kW
6.74 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.08
2.62
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.990
1.000
WTOL
67 °C
67 °C
Poff
11 W
11 W
PTO
11 W
11 W
PSB
11 W
11 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
1935 kWh
2369 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
36 dB(A)
36 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
214 %
157 %
Prated
7.62 kW
6.74 kW
SCOP
5.56
4.13
Tbiv
-22 °C
-22 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
4.59 kW
4.22 kW
COP Tj = -7°C
5.35
3.77
Cdh Tj = -7 °C
0.990
0.990
Pdh Tj = +2°C
3.01 kW
2.51 kW
COP Tj = +2°C
6.00
4.58
Cdh Tj = +2 °C
0.980
0.980
Pdh Tj = +7°C
2.14 kW
2.02 kW
COP Tj = +7°C
6.21
5.06
Cdh Tj = +7 °C
0.970
0.970
Pdh Tj = 12°C
2.11 kW
2.02 kW
COP Tj = 12°C
5.95
5.06
Cdh Tj = +12 °C
0.970
0.970
Pdh Tj = Tbiv
7.62 kW
6.74 kW
COP Tj = Tbiv
4.08
2.62
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.62 kW
6.74 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.08
2.62
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.990
1.000
WTOL
67 °C
67 °C
Poff
11 W
11 W
PTO
11 W
11 W
PSB
11 W
11 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
3381 kWh
4024 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
36 dB(A)
36 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
203 %
150 %
Prated
7.63 kW
6.74 kW
SCOP
5.28
3.95
Tbiv
-10 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
7.06 kW
5.86 kW
COP Tj = -7°C
4.29
2.94
Cdh Tj = -7 °C
0.990
0.990
Pdh Tj = +2°C
4.24 kW
3.76 kW
COP Tj = +2°C
5.37
4.01
Cdh Tj = +2 °C
0.990
0.990
Pdh Tj = +7°C
2.67 kW
2.53 kW
COP Tj = +7°C
6.00
4.70
Cdh Tj = +7 °C
0.970
0.980
Pdh Tj = 12°C
2.11 kW
1.99 kW
COP Tj = 12°C
6.12
4.86
Cdh Tj = +12 °C
0.970
0.970
Pdh Tj = Tbiv
7.63 kW
6.74 kW
COP Tj = Tbiv
4.08
2.62
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.62 kW
6.74 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.08
2.62
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.990
1.000
WTOL
67 °C
67 °C
Poff
11 W
11 W
PTO
11 W
11 W
PSB
11 W
11 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
2984 kWh
3530 kWh
Water/Water Heat Pump
Heating
EN 14511-4
Starting and operating test
passed
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
EN 14511-2
Low temperature
Medium temperature
Heat output
10.03 kW
9.09 kW
El input
1.99 kW
2.87 kW
COP
5.04
3.17
Average Climate
EN 14825
Low temperature
Medium temperature
ηs
288 %
201 %
Prated
9.09 kW
9.09 kW
SCOP
7.40
5.23
Tbiv
-10 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
9.31 kW
7.85 kW
COP Tj = -7°C
5.37
3.60
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
5.50 kW
4.98 kW
COP Tj = +2°C
7.38
5.25
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
3.53 kW
3.36 kW
COP Tj = +7°C
9.18
6.53
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
2.80 kW
2.65 kW
COP Tj = 12°C
9.60
7.00
Cdh Tj = +12 °C
0.960
0.970
Pdh Tj = Tbiv
10.03 kW
9.09 kW
COP Tj = Tbiv
5.04
3.17
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
10.03 kW
9.09 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
5.04
3.17
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
67 °C
67 °C
Poff
11 W
11 W
PTO
11 W
11 W
PSB
11 W
11 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
2800 kWh
3591 kWh