Certificate holders

Subtype

Air to Water Heat Pump 120

Certificate Holder
Guangdong New Energy Technology Development Co., Ltd.
NO.125, Chuangyou Road
511340 Guangdong
China
Registration number
041-K054-02
Certification Body
BRE Global Limited
Subtype title
Air to Water Heat Pump 120
Driving energy
Electricity
Heat Pump Type
Outdoor Air/Water
Refrigerant
R32
Mass of Refrigerant

1,400 kg

Certification Date
16.05.2023
Testing basis
Heat Pump Keymark Scheme Rules Rev 11
Generate PDF Export model CSV Download certificate
  • Number of models 1

Models

NE-F120HCR4INVM
Configure model
Model name
NE-F120HCR4INVM
Application
Heating (medium temp)
Units
Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

11.41 kW

10.96 kW

El input

2.63 kW

3.96 kW

COP

4.34

2.77

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

65 dB(A)

65 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

177 %

128 %

Prated

6.52 kW

7.34 kW

SCOP

4.49

3.27

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

5.76 kW

6.49 kW

COP Tj = -7°C

3.09

2.83

Cdh Tj = -7 °C

0.900

0.900

Pdh Tj = +2°C

3.53 kW

4.03 kW

COP Tj = +2°C

4.11

2.81

Cdh Tj = +2 °C

0.900

0.900

Pdh Tj = +7°C

3.78 kW

3.60 kW

COP Tj = +7°C

6.86

4.66

Cdh Tj = +7 °C

0.900

0.900

Pdh Tj = 12°C

4.47 kW

4.06 kW

COP Tj = 12°C

8.89

6.30

Cdh Tj = +12 °C

0.900

0.900

Pdh Tj = Tbiv

5.76 kW

6.49 kW

COP Tj = Tbiv

3.09

2.83

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

6.04 kW

4.43 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.46

1.86

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

60 °C

60 °C

Poff

6 W

6 W

PTO

14 W

14 W

PSB

6 W

6 W

PCK

29 W

29 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.48 kW

2.91 kW

Annual energy consumption Qhe

2998 kWh

4640 kWh