Certificate holders

Subtype

DAIKIN ALTHERMA 3 R ECH2O 11-16kW (500L)

Certificate Holder
DAIKIN Europe N.V.
Zandvoordestraat 300
B-8400 Oostende
Belgium
Registration number
011-1W0494
Certification Body
DIN CERTCO Gesellschaft für Konformitätsbewertung mbH
Subtype title
DAIKIN ALTHERMA 3 R ECH2O 11-16kW (500L)
Driving energy
Electricity
Heat Pump Type
Outdoor Air/Water
Refrigerant
R32
Mass of Refrigerant

3,800 kg

Certification Date
23.11.2021
Testing basis
HP KEYMARK certification scheme rules rev. 8
Generate PDF Export model CSV
  • Number of models 16

Models

ERLA11DV3 / EBSH(B)11P50D
Configure model
Model name
ERLA11DV3 / EBSH(B)11P50D
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

10.56 kW

10.64 kW

El input

2.19 kW

3.62 kW

COP

4.83

2.94

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Cooling

EN 14511-2

+7°C/+12°C

El input

3.47 kW

Cooling capacity

11.2

EER

3.22

EN 14825

+7°C/+12°C

Pdesignc

11 kW

SEER

5.92

Pdc Tj = 35°C

11 kW

EER Tj = 35°C

3.19

Pdc Tj = 30°C

8.1 kW

EER Tj = 30°C

4.94

Cdc Tj = 30 °C

0.99

Pdc Tj = 25°C

5.7 kW

EER Tj = 25°C

7.18

Cdc Tj = 25 °C

0.97

Pdc Tj = 20°C

5.9 kW

EER Tj = 20°C

8.47

Cdc Tj = 20 °C

0.97

Poff

23 W

PTO

23 W

PSB

23 W

PCK

0 W

Annual energy consumption Qce

1116 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

44.7 dB(A)

44.7 dB(A)

Sound power level outdoor

62 dB(A)

62 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

182 %

126 %

Prated

10 kW

10 kW

SCOP

4.63

3.23

Tbiv

-8 °C

-5 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

9.2 kW

7.9 kW

COP Tj = -7°C

3.03

1.89

Cdh Tj = -7 °C

n/a

1

Pdh Tj = +2°C

5.5 kW

5.4 kW

COP Tj = +2°C

4.37

3.25

Cdh Tj = +2 °C

1

1

Pdh Tj = +7°C

4.6 kW

4.4 kW

COP Tj = +7°C

6.74

4.81

Cdh Tj = +7 °C

1

1

Pdh Tj = 12°C

5.4 kW

5.3 kW

COP Tj = 12°C

8.54

6.41

Cdh Tj = +12 °C

1

1

Pdh Tj = Tbiv

9.2 kW

8.2 kW

COP Tj = Tbiv

3.01

1.96

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

8.4 kW

6.8 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.73

1.68

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1

1

WTOL

35 °C

55 °C

Poff

23 W

23 W

PTO

23 W

23 W

PSB

23 W

23 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

1.6 kW

3.2 kW

Annual energy consumption Qhe

4462 kWh

6397 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

XL

Efficiency ηDHW

126 %

COP

3.05

Heating up time

2:34 h:min

Standby power input

36.4 W

Reference hot water temperature

44.1 °C

Mixed water at 40°C

242 l

ERLA11DV3 / EBSX(B)11P50D
Configure model
Model name
ERLA11DV3 / EBSX(B)11P50D
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
+7°C/12°C
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

10.56 kW

10.64 kW

El input

2.19 kW

3.62 kW

COP

4.83

2.94

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Cooling

EN 14511-2

+7°C/+12°C

El input

3.47 kW

Cooling capacity

11.2

EER

3.22

EN 14825

+7°C/+12°C

Pdesignc

11 kW

SEER

5.92

Pdc Tj = 35°C

11 kW

EER Tj = 35°C

3.19

Pdc Tj = 30°C

8.1 kW

EER Tj = 30°C

4.94

Cdc Tj = 30 °C

0.99

Pdc Tj = 25°C

5.7 kW

EER Tj = 25°C

7.18

Cdc Tj = 25 °C

0.97

Pdc Tj = 20°C

5.9 kW

EER Tj = 20°C

8.47

Cdc Tj = 20 °C

0.97

Poff

23 W

PTO

23 W

PSB

23 W

PCK

0 W

Annual energy consumption Qce

1116 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

44.7 dB(A)

44.7 dB(A)

Sound power level outdoor

62 dB(A)

62 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

186 %

128 %

Prated

10 kW

10 kW

SCOP

4.72

3.27

Tbiv

-8 °C

-5 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

9.2 kW

7.9 kW

COP Tj = -7°C

3.03

1.89

Cdh Tj = -7 °C

n/a

1

Pdh Tj = +2°C

5.5 kW

5.4 kW

COP Tj = +2°C

4.37

3.25

Cdh Tj = +2 °C

1

1

Pdh Tj = +7°C

4.6 kW

4.4 kW

COP Tj = +7°C

6.74

4.81

Cdh Tj = +7 °C

1

1

Pdh Tj = 12°C

5.4 kW

5.3 kW

COP Tj = 12°C

8.54

6.41

Cdh Tj = +12 °C

1

1

Pdh Tj = Tbiv

9.2 kW

8.2 kW

COP Tj = Tbiv

3.01

1.96

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

8.4 kW

6.8 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.73

1.68

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1

1

WTOL

35 °C

55 °C

Poff

23 W

23 W

PTO

23 W

23 W

PSB

23 W

23 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

1.6 kW

3.2 kW

Annual energy consumption Qhe

4378 kWh

6312 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

XL

Efficiency ηDHW

126 %

COP

3.05

Heating up time

2:34 h:min

Standby power input

36.4 W

Reference hot water temperature

44.1 °C

Mixed water at 40°C

242 l

ERLA11DW1 / EBSH(B)11P50D
Configure model
Model name
ERLA11DW1 / EBSH(B)11P50D
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

10.56 kW

10.64 kW

El input

2.19 kW

3.62 kW

COP

4.83

2.94

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Cooling

EN 14511-2

+7°C/+12°C

El input

3.47 kW

Cooling capacity

11.2

EER

3.22

EN 14825

+7°C/+12°C

Pdesignc

11 kW

SEER

5.92

Pdc Tj = 35°C

11 kW

EER Tj = 35°C

3.19

Pdc Tj = 30°C

8.1 kW

EER Tj = 30°C

4.94

Cdc Tj = 30 °C

0.99

Pdc Tj = 25°C

5.7 kW

EER Tj = 25°C

7.18

Cdc Tj = 25 °C

0.97

Pdc Tj = 20°C

5.9 kW

EER Tj = 20°C

8.47

Cdc Tj = 20 °C

0.97

Poff

23 W

PTO

23 W

PSB

23 W

PCK

0 W

Annual energy consumption Qce

1116 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

44.7 dB(A)

44.7 dB(A)

Sound power level outdoor

62 dB(A)

62 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

182 %

126 %

Prated

10 kW

10 kW

SCOP

4.63

3.23

Tbiv

-8 °C

-5 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

9.2 kW

7.9 kW

COP Tj = -7°C

3.03

1.89

Cdh Tj = -7 °C

n/a

1

Pdh Tj = +2°C

5.5 kW

5.4 kW

COP Tj = +2°C

4.37

3.25

Cdh Tj = +2 °C

1

1

Pdh Tj = +7°C

4.6 kW

4.4 kW

COP Tj = +7°C

6.74

4.81

Cdh Tj = +7 °C

1

1

Pdh Tj = 12°C

5.4 kW

5.3 kW

COP Tj = 12°C

8.54

6.41

Cdh Tj = +12 °C

1

1

Pdh Tj = Tbiv

9.2 kW

8.2 kW

COP Tj = Tbiv

3.01

1.96

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

8.4 kW

6.8 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.73

1.68

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1

1

WTOL

35 °C

55 °C

Poff

23 W

23 W

PTO

23 W

23 W

PSB

23 W

23 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

1.6 kW

3.2 kW

Annual energy consumption Qhe

4462 kWh

6397 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

XL

Efficiency ηDHW

128 %

COP

3.1

Heating up time

2:34 h:min

Standby power input

31.4 W

Reference hot water temperature

44.1 °C

Mixed water at 40°C

242 l

ERLA11DW1 / EBSX(B)11P50D
Configure model
Model name
ERLA11DW1 / EBSX(B)11P50D
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
+7°C/12°C
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

10.56 kW

10.64 kW

El input

2.19 kW

3.62 kW

COP

4.83

2.94

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Cooling

EN 14511-2

+7°C/+12°C

El input

3.47 kW

Cooling capacity

11.2

EER

3.22

EN 14825

+7°C/+12°C

Pdesignc

11 kW

SEER

5.92

Pdc Tj = 35°C

11 kW

EER Tj = 35°C

3.19

Pdc Tj = 30°C

8.1 kW

EER Tj = 30°C

4.94

Cdc Tj = 30 °C

0.99

Pdc Tj = 25°C

5.7 kW

EER Tj = 25°C

7.18

Cdc Tj = 25 °C

0.97

Pdc Tj = 20°C

5.9 kW

EER Tj = 20°C

8.47

Cdc Tj = 20 °C

0.97

Poff

23 W

PTO

23 W

PSB

23 W

PCK

0 W

Annual energy consumption Qce

1116 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

44.7 dB(A)

44.7 dB(A)

Sound power level outdoor

62 dB(A)

62 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

186 %

128 %

Prated

10 kW

10 kW

SCOP

4.72

3.27

Tbiv

-8 °C

-5 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

9.2 kW

7.9 kW

COP Tj = -7°C

3.03

1.89

Cdh Tj = -7 °C

n/a

1

Pdh Tj = +2°C

5.5 kW

5.4 kW

COP Tj = +2°C

4.37

3.25

Cdh Tj = +2 °C

1

1

Pdh Tj = +7°C

4.6 kW

4.4 kW

COP Tj = +7°C

6.74

4.81

Cdh Tj = +7 °C

1

1

Pdh Tj = 12°C

5.4 kW

5.3 kW

COP Tj = 12°C

8.54

6.41

Cdh Tj = +12 °C

1

1

Pdh Tj = Tbiv

9.2 kW

8.2 kW

COP Tj = Tbiv

3.01

1.96

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

8.4 kW

6.8 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.73

1.68

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1

1

WTOL

35 °C

55 °C

Poff

23 W

23 W

PTO

23 W

23 W

PSB

23 W

23 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

1.6 kW

3.2 kW

Annual energy consumption Qhe

4378 kWh

6312 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

XL

Efficiency ηDHW

128 %

COP

3.1

Heating up time

2:34 h:min

Standby power input

31.4 W

Reference hot water temperature

44.1 °C

Mixed water at 40°C

242 l

ERLA14DV3 / EBSH(B)16P50D
Configure model
Model name
ERLA14DV3 / EBSH(B)16P50D
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

12 kW

11.87 kW

El input

2.46 kW

4.11 kW

COP

4.87

2.89

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Cooling

EN 14511-2

+7°C/+12°C

El input

4.34 kW

Cooling capacity

12.9

EER

2.98

EN 14825

+7°C/+12°C

Pdesignc

12.9 kW

SEER

5.86

Pdc Tj = 35°C

12.9 kW

EER Tj = 35°C

2.96

Pdc Tj = 30°C

8.8 kW

EER Tj = 30°C

4.77

Cdc Tj = 30 °C

0.99

Pdc Tj = 25°C

6.2 kW

EER Tj = 25°C

7

Cdc Tj = 25 °C

0.97

Pdc Tj = 20°C

5.9 kW

EER Tj = 20°C

8.88

Cdc Tj = 20 °C

0.96

Poff

23 W

PTO

23 W

PSB

23 W

PCK

0 W

Annual energy consumption Qce

1314 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

49 dB(A)

49 dB(A)

Sound power level outdoor

62 dB(A)

62 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

181 %

126 %

Prated

11 kW

11 kW

SCOP

4.6

3.22

Tbiv

-7 °C

-5 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

9.8 kW

8.5 kW

COP Tj = -7°C

2.99

1.8

Cdh Tj = -7 °C

n/a

1

Pdh Tj = +2°C

6.1 kW

6.2 kW

COP Tj = +2°C

4.35

3.28

Cdh Tj = +2 °C

1

1

Pdh Tj = +7°C

4.6 kW

4.4 kW

COP Tj = +7°C

6.7

4.88

Cdh Tj = +7 °C

1

1

Pdh Tj = 12°C

5.4 kW

5.3 kW

COP Tj = 12°C

8.65

6.58

Cdh Tj = +12 °C

1

1

Pdh Tj = Tbiv

9.8 kW

8.9 kW

COP Tj = Tbiv

2.99

1.87

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

9.1 kW

7 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.71

1.76

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1

1

WTOL

35 °C

55 °C

Poff

23 W

23 W

PTO

23 W

23 W

PSB

23 W

23 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

1.9 kW

4 kW

Annual energy consumption Qhe

4935 kWh

7047 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

XL

Efficiency ηDHW

126 %

COP

3.05

Heating up time

2:34 h:min

Standby power input

36.4 W

Reference hot water temperature

44.1 °C

Mixed water at 40°C

242 l

ERLA14DV3 / EBSX(B)16P50D
Configure model
Model name
ERLA14DV3 / EBSX(B)16P50D
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
+7°C/12°C
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

12 kW

11.87 kW

El input

2.46 kW

4.11 kW

COP

4.87

2.89

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Cooling

EN 14511-2

+7°C/+12°C

El input

4.34 kW

Cooling capacity

12.9

EER

2.98

EN 14825

+7°C/+12°C

Pdesignc

12.9 kW

SEER

5.86

Pdc Tj = 35°C

12.9 kW

EER Tj = 35°C

2.96

Pdc Tj = 30°C

8.8 kW

EER Tj = 30°C

4.77

Cdc Tj = 30 °C

0.99

Pdc Tj = 25°C

6.2 kW

EER Tj = 25°C

7

Cdc Tj = 25 °C

0.97

Pdc Tj = 20°C

5.9 kW

EER Tj = 20°C

8.88

Cdc Tj = 20 °C

0.96

Poff

23 W

PTO

23 W

PSB

23 W

PCK

0 W

Annual energy consumption Qce

1314 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

49 dB(A)

49 dB(A)

Sound power level outdoor

62 dB(A)

62 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

184 %

128 %

Prated

11 kW

11 kW

SCOP

4.68

3.26

Tbiv

-7 °C

-5 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

9.8 kW

8.5 kW

COP Tj = -7°C

2.99

1.8

Cdh Tj = -7 °C

n/a

1

Pdh Tj = +2°C

6.1 kW

6.2 kW

COP Tj = +2°C

4.35

3.28

Cdh Tj = +2 °C

1

1

Pdh Tj = +7°C

4.6 kW

4.4 kW

COP Tj = +7°C

6.7

4.88

Cdh Tj = +7 °C

1

1

Pdh Tj = 12°C

5.4 kW

5.3 kW

COP Tj = 12°C

8.65

6.58

Cdh Tj = +12 °C

1

1

Pdh Tj = Tbiv

9.8 kW

8.9 kW

COP Tj = Tbiv

2.99

1.87

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

9.1 kW

7 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.71

1.76

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1

1

WTOL

35 °C

55 °C

Poff

23 W

23 W

PTO

23 W

23 W

PSB

23 W

23 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

1.9 kW

4 kW

Annual energy consumption Qhe

4851 kWh

6962 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

XL

Efficiency ηDHW

126 %

COP

3.05

Heating up time

2:34 h:min

Standby power input

36.4 W

Reference hot water temperature

44.1 °C

Mixed water at 40°C

242 l

ERLA14DW1 / EBSH(B)16P50D
Configure model
Model name
ERLA14DW1 / EBSH(B)16P50D
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

12 kW

11.87 kW

El input

2.46 kW

4.11 kW

COP

4.87

2.89

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Cooling

EN 14511-2

+7°C/+12°C

El input

4.34 kW

Cooling capacity

12.9

EER

2.98

EN 14825

+7°C/+12°C

Pdesignc

12.9 kW

SEER

5.86

Pdc Tj = 35°C

12.9 kW

EER Tj = 35°C

2.96

Pdc Tj = 30°C

8.8 kW

EER Tj = 30°C

4.77

Cdc Tj = 30 °C

0.99

Pdc Tj = 25°C

6.2 kW

EER Tj = 25°C

7

Cdc Tj = 25 °C

0.97

Pdc Tj = 20°C

5.9 kW

EER Tj = 20°C

8.88

Cdc Tj = 20 °C

0.96

Poff

23 W

PTO

23 W

PSB

23 W

PCK

0 W

Annual energy consumption Qce

1314 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

49 dB(A)

49 dB(A)

Sound power level outdoor

62 dB(A)

62 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

181 %

126 %

Prated

11 kW

11 kW

SCOP

4.6

3.22

Tbiv

-7 °C

-5 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

9.8 kW

8.5 kW

COP Tj = -7°C

2.99

1.8

Cdh Tj = -7 °C

n/a

1

Pdh Tj = +2°C

6.1 kW

6.2 kW

COP Tj = +2°C

4.35

3.28

Cdh Tj = +2 °C

1

1

Pdh Tj = +7°C

4.6 kW

4.4 kW

COP Tj = +7°C

6.7

4.88

Cdh Tj = +7 °C

1

1

Pdh Tj = 12°C

5.4 kW

5.3 kW

COP Tj = 12°C

8.65

6.58

Cdh Tj = +12 °C

1

1

Pdh Tj = Tbiv

9.8 kW

8.9 kW

COP Tj = Tbiv

2.99

1.87

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

9.1 kW

7 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.71

1.76

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1

1

WTOL

35 °C

55 °C

Poff

23 W

23 W

PTO

23 W

23 W

PSB

23 W

23 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

1.9 kW

4 kW

Annual energy consumption Qhe

4935 kWh

7047 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

XL

Efficiency ηDHW

128 %

COP

3.1

Heating up time

2:34 h:min

Standby power input

31.4 W

Reference hot water temperature

44.1 °C

Mixed water at 40°C

242 l

ERLA14DW1 / EBSX(B)16P50D
Configure model
Model name
ERLA14DW1 / EBSX(B)16P50D
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
+7°C/12°C
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

12 kW

11.87 kW

El input

2.46 kW

4.11 kW

COP

4.87

2.89

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Cooling

EN 14511-2

+7°C/+12°C

El input

4.34 kW

Cooling capacity

12.9

EER

2.98

EN 14825

+7°C/+12°C

Pdesignc

12.9 kW

SEER

5.86

Pdc Tj = 35°C

12.9 kW

EER Tj = 35°C

2.96

Pdc Tj = 30°C

8.8 kW

EER Tj = 30°C

4.77

Cdc Tj = 30 °C

0.99

Pdc Tj = 25°C

6.2 kW

EER Tj = 25°C

7

Cdc Tj = 25 °C

0.97

Pdc Tj = 20°C

5.9 kW

EER Tj = 20°C

8.88

Cdc Tj = 20 °C

0.96

Poff

23 W

PTO

23 W

PSB

23 W

PCK

0 W

Annual energy consumption Qce

1314 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

49 dB(A)

49 dB(A)

Sound power level outdoor

62 dB(A)

62 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

184 %

128 %

Prated

11 kW

11 kW

SCOP

4.68

3.26

Tbiv

-7 °C

-5 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

9.8 kW

8.5 kW

COP Tj = -7°C

2.99

1.8

Cdh Tj = -7 °C

n/a

1

Pdh Tj = +2°C

6.1 kW

6.2 kW

COP Tj = +2°C

4.35

3.28

Cdh Tj = +2 °C

1

1

Pdh Tj = +7°C

4.6 kW

4.4 kW

COP Tj = +7°C

6.7

4.88

Cdh Tj = +7 °C

1

1

Pdh Tj = 12°C

5.4 kW

5.3 kW

COP Tj = 12°C

8.65

6.58

Cdh Tj = +12 °C

1

1

Pdh Tj = Tbiv

9.8 kW

8.9 kW

COP Tj = Tbiv

2.99

1.87

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

9.1 kW

7 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.71

1.76

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1

1

WTOL

35 °C

55 °C

Poff

23 W

23 W

PTO

23 W

23 W

PSB

23 W

23 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

1.9 kW

4 kW

Annual energy consumption Qhe

4851 kWh

6962 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

XL

Efficiency ηDHW

128 %

COP

3.1

Heating up time

2:34 h:min

Standby power input

31.4 W

Reference hot water temperature

44.1 °C

Mixed water at 40°C

242 l

ERLA16DV3 / EBSH(B)16P50D
Configure model
Model name
ERLA16DV3 / EBSH(B)16P50D
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

16 kW

15.63 kW

El input

3.53 kW

5.68 kW

COP

4.53

2.75

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Cooling

EN 14511-2

+7°C/+12°C

El input

4.68 kW

Cooling capacity

13.6

EER

2.91

EN 14825

+7°C/+12°C

Pdesignc

13.6 kW

SEER

5.76

Pdc Tj = 35°C

13.6 kW

EER Tj = 35°C

2.88

Pdc Tj = 30°C

9.7 kW

EER Tj = 30°C

4.58

Cdc Tj = 30 °C

0.99

Pdc Tj = 25°C

6.2 kW

EER Tj = 25°C

6.99

Cdc Tj = 25 °C

0.98

Pdc Tj = 20°C

5.9 kW

EER Tj = 20°C

8.69

Cdc Tj = 20 °C

0.97

Poff

23 W

PTO

23 W

PSB

23 W

PCK

0 W

Annual energy consumption Qce

1417 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

49 dB(A)

49 dB(A)

Sound power level outdoor

62 dB(A)

62 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

181 %

130 %

Prated

12 kW

12 kW

SCOP

4.61

3.32

Tbiv

-8 °C

-5 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

11.2 kW

9.4 kW

COP Tj = -7°C

2.87

1.95

Cdh Tj = -7 °C

n/a

1

Pdh Tj = +2°C

6.7 kW

6.9 kW

COP Tj = +2°C

4.33

3.27

Cdh Tj = +2 °C

1

1

Pdh Tj = +7°C

4.7 kW

4.4 kW

COP Tj = +7°C

6.83

4.93

Cdh Tj = +7 °C

1

1

Pdh Tj = 12°C

5.5 kW

5.3 kW

COP Tj = 12°C

8.82

6.6

Cdh Tj = +12 °C

1

1

Pdh Tj = Tbiv

11.4 kW

10.1 kW

COP Tj = Tbiv

2.72

2.13

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

10.6 kW

6 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.52

1.5

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1

1

WTOL

35 °C

55 °C

Poff

23 W

23 W

PTO

23 W

23 W

PSB

23 W

23 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

1.4 kW

6.1 kW

Annual energy consumption Qhe

5377 kWh

7477 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

XL

Efficiency ηDHW

126 %

COP

3.05

Heating up time

2:34 h:min

Standby power input

36.4 W

Reference hot water temperature

44.1 °C

Mixed water at 40°C

242 l

ERLA16DV3 / EBSX(B)16P50D
Configure model
Model name
ERLA16DV3 / EBSX(B)16P50D
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
+7°C/12°C
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

16 kW

15.63 kW

El input

3.53 kW

5.68 kW

COP

4.53

2.75

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Cooling

EN 14511-2

+7°C/+12°C

El input

4.68 kW

Cooling capacity

13.6

EER

2.91

EN 14825

+7°C/+12°C

Pdesignc

13.6 kW

SEER

5.76

Pdc Tj = 35°C

13.6 kW

EER Tj = 35°C

2.88

Pdc Tj = 30°C

9.7 kW

EER Tj = 30°C

4.58

Cdc Tj = 30 °C

0.99

Pdc Tj = 25°C

6.2 kW

EER Tj = 25°C

6.99

Cdc Tj = 25 °C

0.98

Pdc Tj = 20°C

5.9 kW

EER Tj = 20°C

8.69

Cdc Tj = 20 °C

0.97

Poff

23 W

PTO

23 W

PSB

23 W

PCK

0 W

Annual energy consumption Qce

1417 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

49 dB(A)

49 dB(A)

Sound power level outdoor

62 dB(A)

62 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

184 %

131 %

Prated

12 kW

12 kW

SCOP

4.68

3.35

Tbiv

-8 °C

-5 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

11.2 kW

9.4 kW

COP Tj = -7°C

2.87

1.95

Cdh Tj = -7 °C

n/a

1

Pdh Tj = +2°C

6.7 kW

6.9 kW

COP Tj = +2°C

4.33

3.27

Cdh Tj = +2 °C

1

1

Pdh Tj = +7°C

4.7 kW

4.4 kW

COP Tj = +7°C

6.83

4.93

Cdh Tj = +7 °C

1

1

Pdh Tj = 12°C

5.5 kW

5.3 kW

COP Tj = 12°C

8.82

6.6

Cdh Tj = +12 °C

1

1

Pdh Tj = Tbiv

11.4 kW

10.1 kW

COP Tj = Tbiv

2.72

2.13

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

10.6 kW

6 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.52

1.5

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1

1

WTOL

35 °C

55 °C

Poff

23 W

23 W

PTO

23 W

23 W

PSB

23 W

23 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

1.4 kW

6.1 kW

Annual energy consumption Qhe

5293 kWh

7392 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

XL

Efficiency ηDHW

126 %

COP

3.05

Heating up time

2:34 h:min

Standby power input

36.4 W

Reference hot water temperature

44.1 °C

Mixed water at 40°C

242 l

ERLA16DV37 / EBSH(B)16P50D
Configure model
Model name
ERLA16DV37 / EBSH(B)16P50D
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

16 kW

15.63 kW

El input

3.53 kW

5.68 kW

COP

4.53

2.75

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Cooling

EN 14511-2

+7°C/+12°C

El input

4.68 kW

Cooling capacity

13.6

EER

2.91

EN 14825

+7°C/+12°C

Pdesignc

13.6 kW

SEER

5.76

Pdc Tj = 35°C

13.6 kW

EER Tj = 35°C

2.88

Pdc Tj = 30°C

9.7 kW

EER Tj = 30°C

4.58

Cdc Tj = 30 °C

0.99

Pdc Tj = 25°C

6.2 kW

EER Tj = 25°C

6.99

Cdc Tj = 25 °C

0.98

Pdc Tj = 20°C

5.9 kW

EER Tj = 20°C

8.69

Cdc Tj = 20 °C

0.97

Poff

23 W

PTO

23 W

PSB

23 W

PCK

0 W

Annual energy consumption Qce

1417 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

49 dB(A)

49 dB(A)

Sound power level outdoor

62 dB(A)

62 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

181 %

130 %

Prated

12 kW

12 kW

SCOP

4.61

3.32

Tbiv

-8 °C

-5 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

11.2 kW

9.4 kW

COP Tj = -7°C

2.87

1.95

Cdh Tj = -7 °C

n/a

1

Pdh Tj = +2°C

6.7 kW

6.9 kW

COP Tj = +2°C

4.33

3.27

Cdh Tj = +2 °C

1

1

Pdh Tj = +7°C

4.7 kW

4.4 kW

COP Tj = +7°C

6.83

4.93

Cdh Tj = +7 °C

1

1

Pdh Tj = 12°C

5.5 kW

5.3 kW

COP Tj = 12°C

8.82

6.6

Cdh Tj = +12 °C

1

1

Pdh Tj = Tbiv

11.4 kW

10.1 kW

COP Tj = Tbiv

2.72

2.13

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

10.6 kW

6 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.52

1.5

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1

1

WTOL

35 °C

55 °C

Poff

23 W

23 W

PTO

23 W

23 W

PSB

23 W

23 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

1.4 kW

6.1 kW

Annual energy consumption Qhe

5377 kWh

7477 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

XL

Efficiency ηDHW

126 %

COP

3.05

Heating up time

2:34 h:min

Standby power input

36.4 W

Reference hot water temperature

44.1 °C

Mixed water at 40°C

242 l

ERLA16DV37 / EBSX(B)16P50D
Configure model
Model name
ERLA16DV37 / EBSX(B)16P50D
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
+7°C/12°C
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

16 kW

15.63 kW

El input

3.53 kW

5.68 kW

COP

4.53

2.75

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Cooling

EN 14511-2

+7°C/+12°C

El input

4.68 kW

Cooling capacity

13.6

EER

2.91

EN 14825

+7°C/+12°C

Pdesignc

13.6 kW

SEER

5.76

Pdc Tj = 35°C

13.6 kW

EER Tj = 35°C

2.88

Pdc Tj = 30°C

9.7 kW

EER Tj = 30°C

4.58

Cdc Tj = 30 °C

0.99

Pdc Tj = 25°C

6.2 kW

EER Tj = 25°C

6.99

Cdc Tj = 25 °C

0.98

Pdc Tj = 20°C

5.9 kW

EER Tj = 20°C

8.69

Cdc Tj = 20 °C

0.97

Poff

23 W

PTO

23 W

PSB

23 W

PCK

0 W

Annual energy consumption Qce

1417 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

49 dB(A)

49 dB(A)

Sound power level outdoor

62 dB(A)

62 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

184 %

131 %

Prated

12 kW

12 kW

SCOP

4.68

3.35

Tbiv

-8 °C

-5 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

11.2 kW

9.4 kW

COP Tj = -7°C

2.87

1.95

Cdh Tj = -7 °C

n/a

1

Pdh Tj = +2°C

6.7 kW

6.9 kW

COP Tj = +2°C

4.33

3.27

Cdh Tj = +2 °C

1

1

Pdh Tj = +7°C

4.7 kW

4.4 kW

COP Tj = +7°C

6.83

4.93

Cdh Tj = +7 °C

1

1

Pdh Tj = 12°C

5.5 kW

5.3 kW

COP Tj = 12°C

8.82

6.6

Cdh Tj = +12 °C

1

1

Pdh Tj = Tbiv

11.4 kW

10.1 kW

COP Tj = Tbiv

2.72

2.13

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

10.6 kW

6 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.52

1.5

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1

1

WTOL

35 °C

55 °C

Poff

23 W

23 W

PTO

23 W

23 W

PSB

23 W

23 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

1.4 kW

6.1 kW

Annual energy consumption Qhe

5293 kWh

7392 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

XL

Efficiency ηDHW

126 %

COP

3.05

Heating up time

2:34 h:min

Standby power input

36.4 W

Reference hot water temperature

44.1 °C

Mixed water at 40°C

242 l

ERLA16DW1 / EBSH(B)16P50D
Configure model
Model name
ERLA16DW1 / EBSH(B)16P50D
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

16 kW

15.63 kW

El input

3.53 kW

5.68 kW

COP

4.53

2.75

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Cooling

EN 14511-2

+7°C/+12°C

El input

4.68 kW

Cooling capacity

13.6

EER

2.91

EN 14825

+7°C/+12°C

Pdesignc

13.6 kW

SEER

5.76

Pdc Tj = 35°C

13.6 kW

EER Tj = 35°C

2.88

Pdc Tj = 30°C

9.7 kW

EER Tj = 30°C

4.58

Cdc Tj = 30 °C

0.99

Pdc Tj = 25°C

6.2 kW

EER Tj = 25°C

6.99

Cdc Tj = 25 °C

0.98

Pdc Tj = 20°C

5.9 kW

EER Tj = 20°C

8.69

Cdc Tj = 20 °C

0.97

Poff

23 W

PTO

23 W

PSB

23 W

PCK

0 W

Annual energy consumption Qce

1417 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

49 dB(A)

49 dB(A)

Sound power level outdoor

62 dB(A)

62 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

181 %

130 %

Prated

12 kW

12 kW

SCOP

4.61

3.32

Tbiv

-8 °C

-5 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

11.2 kW

9.4 kW

COP Tj = -7°C

2.87

1.95

Cdh Tj = -7 °C

n/a

1

Pdh Tj = +2°C

6.7 kW

6.9 kW

COP Tj = +2°C

4.33

3.27

Cdh Tj = +2 °C

1

1

Pdh Tj = +7°C

4.7 kW

4.4 kW

COP Tj = +7°C

6.83

4.93

Cdh Tj = +7 °C

1

1

Pdh Tj = 12°C

5.5 kW

5.3 kW

COP Tj = 12°C

8.82

6.6

Cdh Tj = +12 °C

1

1

Pdh Tj = Tbiv

11.4 kW

10.1 kW

COP Tj = Tbiv

2.72

2.13

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

10.6 kW

6 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.52

1.5

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1

1

WTOL

35 °C

55 °C

Poff

23 W

23 W

PTO

23 W

23 W

PSB

23 W

23 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

1.4 kW

6.1 kW

Annual energy consumption Qhe

5377 kWh

7477 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

XL

Efficiency ηDHW

128 %

COP

3.1

Heating up time

2:34 h:min

Standby power input

31.4 W

Reference hot water temperature

44.1 °C

Mixed water at 40°C

242 l

ERLA16DW1 / EBSX(B)16P50D
Configure model
Model name
ERLA16DW1 / EBSX(B)16P50D
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
+7°C/12°C
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

16 kW

15.63 kW

El input

3.53 kW

5.68 kW

COP

4.53

2.75

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Cooling

EN 14511-2

+7°C/+12°C

El input

4.68 kW

Cooling capacity

13.6

EER

2.91

EN 14825

+7°C/+12°C

Pdesignc

13.6 kW

SEER

5.76

Pdc Tj = 35°C

13.6 kW

EER Tj = 35°C

2.88

Pdc Tj = 30°C

9.7 kW

EER Tj = 30°C

4.58

Cdc Tj = 30 °C

0.99

Pdc Tj = 25°C

6.2 kW

EER Tj = 25°C

6.99

Cdc Tj = 25 °C

0.98

Pdc Tj = 20°C

5.9 kW

EER Tj = 20°C

8.69

Cdc Tj = 20 °C

0.97

Poff

23 W

PTO

23 W

PSB

23 W

PCK

0 W

Annual energy consumption Qce

1417 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

49 dB(A)

49 dB(A)

Sound power level outdoor

62 dB(A)

62 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

184 %

131 %

Prated

12 kW

12 kW

SCOP

4.68

3.35

Tbiv

-8 °C

-5 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

11.2 kW

9.4 kW

COP Tj = -7°C

2.87

1.95

Cdh Tj = -7 °C

n/a

1

Pdh Tj = +2°C

6.7 kW

6.9 kW

COP Tj = +2°C

4.33

3.27

Cdh Tj = +2 °C

1

1

Pdh Tj = +7°C

4.7 kW

4.4 kW

COP Tj = +7°C

6.83

4.93

Cdh Tj = +7 °C

1

1

Pdh Tj = 12°C

5.5 kW

5.3 kW

COP Tj = 12°C

8.82

6.6

Cdh Tj = +12 °C

1

1

Pdh Tj = Tbiv

11.4 kW

10.1 kW

COP Tj = Tbiv

2.72

2.13

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

10.6 kW

6 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.52

1.5

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1

1

WTOL

35 °C

55 °C

Poff

23 W

23 W

PTO

23 W

23 W

PSB

23 W

23 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

1.4 kW

6.1 kW

Annual energy consumption Qhe

5293 kWh

7392 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

XL

Efficiency ηDHW

128 %

COP

3.1

Heating up time

2:34 h:min

Standby power input

31.4 W

Reference hot water temperature

44.1 °C

Mixed water at 40°C

242 l

ERLA16DW17 / EBSH(B)16P50D
Configure model
Model name
ERLA16DW17 / EBSH(B)16P50D
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

16 kW

15.63 kW

El input

3.53 kW

5.68 kW

COP

4.53

2.75

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Cooling

EN 14511-2

+7°C/+12°C

El input

4.68 kW

Cooling capacity

13.6

EER

2.91

EN 14825

+7°C/+12°C

Pdesignc

13.6 kW

SEER

5.76

Pdc Tj = 35°C

13.6 kW

EER Tj = 35°C

2.88

Pdc Tj = 30°C

9.7 kW

EER Tj = 30°C

4.58

Cdc Tj = 30 °C

0.99

Pdc Tj = 25°C

6.2 kW

EER Tj = 25°C

6.99

Cdc Tj = 25 °C

0.98

Pdc Tj = 20°C

5.9 kW

EER Tj = 20°C

8.69

Cdc Tj = 20 °C

0.97

Poff

23 W

PTO

23 W

PSB

23 W

PCK

0 W

Annual energy consumption Qce

1417 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

49 dB(A)

49 dB(A)

Sound power level outdoor

62 dB(A)

62 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

181 %

130 %

Prated

12 kW

12 kW

SCOP

4.61

3.32

Tbiv

-8 °C

-5 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

11.2 kW

9.4 kW

COP Tj = -7°C

2.87

1.95

Cdh Tj = -7 °C

n/a

1

Pdh Tj = +2°C

6.7 kW

6.9 kW

COP Tj = +2°C

4.33

3.27

Cdh Tj = +2 °C

1

1

Pdh Tj = +7°C

4.7 kW

4.4 kW

COP Tj = +7°C

6.83

4.93

Cdh Tj = +7 °C

1

1

Pdh Tj = 12°C

5.5 kW

5.3 kW

COP Tj = 12°C

8.82

6.6

Cdh Tj = +12 °C

1

1

Pdh Tj = Tbiv

11.4 kW

10.1 kW

COP Tj = Tbiv

2.72

2.13

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

10.6 kW

6 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.52

1.5

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1

1

WTOL

35 °C

55 °C

Poff

23 W

23 W

PTO

23 W

23 W

PSB

23 W

23 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

1.4 kW

6.1 kW

Annual energy consumption Qhe

5377 kWh

7477 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

XL

Efficiency ηDHW

128 %

COP

3.1

Heating up time

2:34 h:min

Standby power input

31.4 W

Reference hot water temperature

44.1 °C

Mixed water at 40°C

242 l

ERLA16DW17 / EBSX(B)16P50D
Configure model
Model name
ERLA16DW17 / EBSX(B)16P50D
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
+7°C/12°C
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

16 kW

15.63 kW

El input

3.53 kW

5.68 kW

COP

4.53

2.75

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Cooling

EN 14511-2

+7°C/+12°C

El input

4.68 kW

Cooling capacity

13.6

EER

2.91

EN 14825

+7°C/+12°C

Pdesignc

13.6 kW

SEER

5.76

Pdc Tj = 35°C

13.6 kW

EER Tj = 35°C

2.88

Pdc Tj = 30°C

9.7 kW

EER Tj = 30°C

4.58

Cdc Tj = 30 °C

0.99

Pdc Tj = 25°C

6.2 kW

EER Tj = 25°C

6.99

Cdc Tj = 25 °C

0.98

Pdc Tj = 20°C

5.9 kW

EER Tj = 20°C

8.69

Cdc Tj = 20 °C

0.97

Poff

23 W

PTO

23 W

PSB

23 W

PCK

0 W

Annual energy consumption Qce

1417 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

49 dB(A)

49 dB(A)

Sound power level outdoor

62 dB(A)

62 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

184 %

131 %

Prated

12 kW

12 kW

SCOP

4.68

3.35

Tbiv

-8 °C

-5 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

11.2 kW

9.4 kW

COP Tj = -7°C

2.87

1.95

Cdh Tj = -7 °C

n/a

1

Pdh Tj = +2°C

6.7 kW

6.9 kW

COP Tj = +2°C

4.33

3.27

Cdh Tj = +2 °C

1

1

Pdh Tj = +7°C

4.7 kW

4.4 kW

COP Tj = +7°C

6.83

4.93

Cdh Tj = +7 °C

1

1

Pdh Tj = 12°C

5.5 kW

5.3 kW

COP Tj = 12°C

8.82

6.6

Cdh Tj = +12 °C

1

1

Pdh Tj = Tbiv

11.4 kW

10.1 kW

COP Tj = Tbiv

2.72

2.13

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

10.6 kW

6 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.52

1.5

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1

1

WTOL

35 °C

55 °C

Poff

23 W

23 W

PTO

23 W

23 W

PSB

23 W

23 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

1.4 kW

6.1 kW

Annual energy consumption Qhe

5293 kWh

7392 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

XL

Efficiency ηDHW

128 %

COP

3.1

Heating up time

2:34 h:min

Standby power input

31.4 W

Reference hot water temperature

44.1 °C

Mixed water at 40°C

242 l