2,400 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
10.08 kW
9.37 kW
El input
2.18 kW
3.2 kW
COP
4.63
2.93
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
51 dB(A)
51 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
191 %
141 %
Prated
11 kW
11 kW
SCOP
4.97
3.72
Tbiv
-7 °C
-6 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
10.1 kW
9.46 kW
COP Tj = -7°C
4.72
3.14
Cdh Tj = -7 °C
1.00
1.00
Pdh Tj = +2°C
10.17 kW
9.69 kW
COP Tj = +2°C
4.96
3.71
Cdh Tj = +2 °C
1.00
1.00
Pdh Tj = +7°C
10.24 kW
9.84 kW
COP Tj = +7°C
5.21
4.11
Cdh Tj = +7 °C
1.00
1.00
Pdh Tj = 12°C
10.31 kW
9.98 kW
COP Tj = 12°C
5.49
4.55
Cdh Tj = +12 °C
1.00
1.00
Pdh Tj = Tbiv
10.1 kW
9.5 kW
COP Tj = Tbiv
4.72
3.22
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
10.08 kW
9.37 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.63
2.93
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.00
1.00
WTOL
62 °C
62 °C
Poff
6 W
6 W
PTO
6 W
6 W
PSB
6 W
6 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.92 kW
1.63 kW
Annual energy consumption Qhe
4570 kWh
6110 kWh