Certificate holders

Subtype

NIMBUS 40 S - ARIANEXT 40 S - AEROTOP SPLIT 04X

Certificate Holder
Ariston Thermo Group
Viale Aristide Merloni 45
I-60044 Fabriano (AN)
Italy
Registration number
ICIM-PDC-000001 / 03
Certification Body
ICIM S.p.A.
Subtype title
NIMBUS 40 S - ARIANEXT 40 S - AEROTOP SPLIT 04X
Driving energy
n/a
Heat Pump Type
Outdoor Air/Water
Refrigerant
R410A
Mass of Refrigerant

2,300 kg

Certification Date
19.12.2017
Testing basis
n/a
Generate PDF Export model CSV Download certificate
  • Number of models 11

Models

AEROTOP SPLIT 04-RX
Configure model
Model name
AEROTOP SPLIT 04-RX
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-4

Operating range outdoor exchanger/indoor exchanger lower limit/lower limit

passed

Operating range outdoor exchanger/indoor exchanger upper limit/upper limit

passed

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

EN 14511-2

Low temperature

Medium temperature

Heat output

3.50 kW

2.96 kW

El input

0.69 kW

1.05 kW

COP

5.11

2.82

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

36 dB(A)

36 dB(A)

Sound power level outdoor

56 dB(A)

56 dB(A)

EN 14825

Low temperature

Medium temperature

Pdesignh

2.80 kW

2.33 kW

ηs

231 %

144 %

Prated

2.80 kW

2.33 kW

SCOP

5.86

3.67

Tbiv

2 °C

2 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

2.80 kW

2.33 kW

COP Tj = +2°C

4.12

2.30

Pdh Tj = +7°C

1.77 kW

1.56 kW

COP Tj = +7°C

5.53

2.99

Pdh Tj = 12°C

1.61 kW

1.61 kW

COP Tj = 12°C

7.73

5.65

Pdh Tj = Tbiv

2.80 kW

2.33 kW

COP Tj = Tbiv

4.12

2.30

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

2.80 kW

2.33 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.12

2.30

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.90

0.90

WTOL

60 °C

60 °C

Poff

11 W

11 W

PTO

11 W

11 W

PSB

11 W

11 W

PCK

11 W

11 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

640 kWh

848 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

36 dB(A)

36 dB(A)

Sound power level outdoor

56 dB(A)

56 dB(A)

EN 14825

Low temperature

Medium temperature

Pdesignh

7.65 kW

7.35 kW

ηs

148 %

117 %

Prated

7.65 kW

7.35 kW

SCOP

3.77

2.99

Tbiv

-7 °C

-7 °C

TOL

-20 °C

-20 °C

Pdh Tj = -7°C

4.63 kW

4.45 kW

COP Tj = -7°C

3.59

2.79

Pdh Tj = +2°C

2.85 kW

2.82 kW

COP Tj = +2°C

4.97

3.71

Pdh Tj = +7°C

1.76 kW

1.73 kW

COP Tj = +7°C

6.63

5.30

Pdh Tj = 12°C

1.62 kW

1.61 kW

COP Tj = 12°C

8.44

6.71

Pdh Tj = Tbiv

4.63 kW

4.45 kW

COP Tj = Tbiv

3.59

2.79

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

2.92 kW

2.47 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.36

1.52

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.90

0.90

WTOL

60 °C

60 °C

Poff

11 W

11 W

PTO

11 W

11 W

PSB

11 W

11 W

PCK

11 W

11 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

4.00 kW

4.00 kW

Annual energy consumption Qhe

5001 kWh

6057 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

36 dB(A)

36 dB(A)

Sound power level outdoor

56 dB(A)

56 dB(A)

EN 14825

Low temperature

Medium temperature

Pdesignh

5.20 kW

4.78 kW

ηs

191 %

135 %

Prated

5.20 kW

4.78 kW

SCOP

4.85

3.45

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

4.60 kW

4.23 kW

COP Tj = -7°C

3.34

2.35

Pdh Tj = +2°C

2.79 kW

2.76 kW

COP Tj = +2°C

4.69

3.37

Pdh Tj = +7°C

1.84 kW

1.72 kW

COP Tj = +7°C

6.28

4.26

Pdh Tj = 12°C

1.62 kW

1.58 kW

COP Tj = 12°C

8.44

6.19

Pdh Tj = Tbiv

4.60 kW

4.23 kW

COP Tj = Tbiv

3.34

2.35

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

4.15 kW

3.74 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

3.01

2.04

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.90

0.90

WTOL

60 °C

60 °C

Poff

11 W

11 W

PTO

11 W

11 W

PSB

11 W

11 W

PCK

11 W

11 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

1.05 kW

1.04 kW

Annual energy consumption Qhe

2215 kWh

2866 kWh

ARIANEXT PLUS 40 S LINK
Configure model
Model name
ARIANEXT PLUS 40 S LINK
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-4

Operating range outdoor exchanger/indoor exchanger lower limit/lower limit

passed

Operating range outdoor exchanger/indoor exchanger upper limit/upper limit

passed

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

EN 14511-2

Low temperature

Medium temperature

Heat output

3.50 kW

2.96 kW

El input

0.69 kW

1.05 kW

COP

5.11

2.82

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

36 dB(A)

36 dB(A)

Sound power level outdoor

56 dB(A)

56 dB(A)

EN 14825

Low temperature

Medium temperature

Pdesignh

2.80 kW

2.33 kW

ηs

231 %

144 %

Prated

2.80 kW

2.33 kW

SCOP

5.86

3.67

Tbiv

2 °C

2 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

2.80 kW

2.33 kW

COP Tj = +2°C

4.12

2.30

Pdh Tj = +7°C

1.77 kW

1.56 kW

COP Tj = +7°C

5.53

2.99

Pdh Tj = 12°C

1.61 kW

1.61 kW

COP Tj = 12°C

7.73

5.65

Pdh Tj = Tbiv

2.80 kW

2.33 kW

COP Tj = Tbiv

4.12

2.30

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

2.80 kW

2.33 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.12

2.30

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.90

0.90

WTOL

60 °C

60 °C

Poff

11 W

11 W

PTO

11 W

11 W

PSB

11 W

11 W

PCK

11 W

11 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

640 kWh

848 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

36 dB(A)

36 dB(A)

Sound power level outdoor

56 dB(A)

56 dB(A)

EN 14825

Low temperature

Medium temperature

Pdesignh

7.65 kW

7.35 kW

ηs

148 %

117 %

Prated

7.65 kW

7.35 kW

SCOP

3.77

2.99

Tbiv

-7 °C

-7 °C

TOL

-20 °C

-20 °C

Pdh Tj = -7°C

4.63 kW

4.45 kW

COP Tj = -7°C

3.59

2.79

Pdh Tj = +2°C

2.85 kW

2.82 kW

COP Tj = +2°C

4.97

3.71

Pdh Tj = +7°C

1.76 kW

1.73 kW

COP Tj = +7°C

6.63

5.30

Pdh Tj = 12°C

1.62 kW

1.61 kW

COP Tj = 12°C

8.44

6.71

Pdh Tj = Tbiv

4.63 kW

4.45 kW

COP Tj = Tbiv

3.59

2.79

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

2.92 kW

2.47 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.36

1.52

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.90

0.90

WTOL

60 °C

60 °C

Poff

11 W

11 W

PTO

11 W

11 W

PSB

11 W

11 W

PCK

11 W

11 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

4.00 kW

4.00 kW

Annual energy consumption Qhe

5001 kWh

6057 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

36 dB(A)

36 dB(A)

Sound power level outdoor

56 dB(A)

56 dB(A)

EN 14825

Low temperature

Medium temperature

Pdesignh

5.20 kW

4.78 kW

ηs

191 %

135 %

Prated

5.20 kW

4.78 kW

SCOP

4.85

3.45

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

4.60 kW

4.23 kW

COP Tj = -7°C

3.34

2.35

Pdh Tj = +2°C

2.79 kW

2.76 kW

COP Tj = +2°C

4.69

3.37

Pdh Tj = +7°C

1.84 kW

1.72 kW

COP Tj = +7°C

6.28

4.26

Pdh Tj = 12°C

1.62 kW

1.58 kW

COP Tj = 12°C

8.44

6.19

Pdh Tj = Tbiv

4.60 kW

4.23 kW

COP Tj = Tbiv

3.34

2.35

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

4.15 kW

3.74 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

3.01

2.04

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.90

0.90

WTOL

60 °C

60 °C

Poff

11 W

11 W

PTO

11 W

11 W

PSB

11 W

11 W

PCK

11 W

11 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

1.05 kW

1.04 kW

Annual energy consumption Qhe

2215 kWh

2866 kWh

ARIANEXT PLUS 40 S
Configure model
Model name
ARIANEXT PLUS 40 S
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-4

Operating range outdoor exchanger/indoor exchanger lower limit/lower limit

passed

Operating range outdoor exchanger/indoor exchanger upper limit/upper limit

passed

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

EN 14511-2

Low temperature

Medium temperature

Heat output

3.50 kW

2.96 kW

El input

0.69 kW

1.05 kW

COP

5.11

2.82

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

36 dB(A)

36 dB(A)

Sound power level outdoor

56 dB(A)

56 dB(A)

EN 14825

Low temperature

Medium temperature

Pdesignh

2.80 kW

2.33 kW

ηs

231 %

144 %

Prated

2.80 kW

2.33 kW

SCOP

5.86

3.67

Tbiv

2 °C

2 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

2.80 kW

2.33 kW

COP Tj = +2°C

4.12

2.30

Pdh Tj = +7°C

1.77 kW

1.56 kW

COP Tj = +7°C

5.53

2.99

Pdh Tj = 12°C

1.61 kW

1.61 kW

COP Tj = 12°C

7.73

5.65

Pdh Tj = Tbiv

2.80 kW

2.33 kW

COP Tj = Tbiv

4.12

2.30

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

2.80 kW

2.33 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.12

2.30

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.90

0.90

WTOL

60 °C

60 °C

Poff

11 W

11 W

PTO

11 W

11 W

PSB

11 W

11 W

PCK

11 W

11 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

640 kWh

848 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

36 dB(A)

36 dB(A)

Sound power level outdoor

56 dB(A)

56 dB(A)

EN 14825

Low temperature

Medium temperature

Pdesignh

7.65 kW

7.35 kW

ηs

148 %

117 %

Prated

7.65 kW

7.35 kW

SCOP

3.77

2.99

Tbiv

-7 °C

-7 °C

TOL

-20 °C

-20 °C

Pdh Tj = -7°C

4.63 kW

4.45 kW

COP Tj = -7°C

3.59

2.79

Pdh Tj = +2°C

2.85 kW

2.82 kW

COP Tj = +2°C

4.97

3.71

Pdh Tj = +7°C

1.76 kW

1.73 kW

COP Tj = +7°C

6.63

5.30

Pdh Tj = 12°C

1.62 kW

1.61 kW

COP Tj = 12°C

8.44

6.71

Pdh Tj = Tbiv

4.63 kW

4.45 kW

COP Tj = Tbiv

3.59

2.79

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

2.92 kW

2.47 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.36

1.52

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.90

0.90

WTOL

60 °C

60 °C

Poff

11 W

11 W

PTO

11 W

11 W

PSB

11 W

11 W

PCK

11 W

11 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

4.00 kW

4.00 kW

Annual energy consumption Qhe

5001 kWh

6057 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

36 dB(A)

36 dB(A)

Sound power level outdoor

56 dB(A)

56 dB(A)

EN 14825

Low temperature

Medium temperature

Pdesignh

5.20 kW

4.78 kW

ηs

191 %

135 %

Prated

5.20 kW

4.78 kW

SCOP

4.85

3.45

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

4.60 kW

4.23 kW

COP Tj = -7°C

3.34

2.35

Pdh Tj = +2°C

2.79 kW

2.76 kW

COP Tj = +2°C

4.69

3.37

Pdh Tj = +7°C

1.84 kW

1.72 kW

COP Tj = +7°C

6.28

4.26

Pdh Tj = 12°C

1.62 kW

1.58 kW

COP Tj = 12°C

8.44

6.19

Pdh Tj = Tbiv

4.60 kW

4.23 kW

COP Tj = Tbiv

3.34

2.35

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

4.15 kW

3.74 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

3.01

2.04

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.90

0.90

WTOL

60 °C

60 °C

Poff

11 W

11 W

PTO

11 W

11 W

PSB

11 W

11 W

PCK

11 W

11 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

1.05 kW

1.04 kW

Annual energy consumption Qhe

2215 kWh

2866 kWh

NIMBUS PLUS 40 S NET
Configure model
Model name
NIMBUS PLUS 40 S NET
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-4

Operating range outdoor exchanger/indoor exchanger lower limit/lower limit

passed

Operating range outdoor exchanger/indoor exchanger upper limit/upper limit

passed

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

EN 14511-2

Low temperature

Medium temperature

Heat output

3.50 kW

2.96 kW

El input

0.69 kW

1.05 kW

COP

5.11

2.82

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

36 dB(A)

36 dB(A)

Sound power level outdoor

56 dB(A)

56 dB(A)

EN 14825

Low temperature

Medium temperature

Pdesignh

2.80 kW

2.33 kW

ηs

231 %

144 %

Prated

2.80 kW

2.33 kW

SCOP

5.86

3.67

Tbiv

2 °C

2 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

2.80 kW

2.33 kW

COP Tj = +2°C

4.12

2.30

Pdh Tj = +7°C

1.77 kW

1.56 kW

COP Tj = +7°C

5.53

2.99

Pdh Tj = 12°C

1.61 kW

1.61 kW

COP Tj = 12°C

7.73

5.65

Pdh Tj = Tbiv

2.80 kW

2.33 kW

COP Tj = Tbiv

4.12

2.30

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

2.80 kW

2.33 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.12

2.30

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.90

0.90

WTOL

60 °C

60 °C

Poff

11 W

11 W

PTO

11 W

11 W

PSB

11 W

11 W

PCK

11 W

11 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

640 kWh

848 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

36 dB(A)

36 dB(A)

Sound power level outdoor

56 dB(A)

56 dB(A)

EN 14825

Low temperature

Medium temperature

Pdesignh

7.65 kW

7.35 kW

ηs

148 %

117 %

Prated

7.65 kW

7.35 kW

SCOP

3.77

2.99

Tbiv

-7 °C

-7 °C

TOL

-20 °C

-20 °C

Pdh Tj = -7°C

4.63 kW

4.45 kW

COP Tj = -7°C

3.59

2.79

Pdh Tj = +2°C

2.85 kW

2.82 kW

COP Tj = +2°C

4.97

3.71

Pdh Tj = +7°C

1.76 kW

1.73 kW

COP Tj = +7°C

6.63

5.30

Pdh Tj = 12°C

1.62 kW

1.61 kW

COP Tj = 12°C

8.44

6.71

Pdh Tj = Tbiv

4.63 kW

4.45 kW

COP Tj = Tbiv

3.59

2.79

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

2.92 kW

2.47 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.36

1.52

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.90

0.90

WTOL

60 °C

60 °C

Poff

11 W

11 W

PTO

11 W

11 W

PSB

11 W

11 W

PCK

11 W

11 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

4.00 kW

4.00 kW

Annual energy consumption Qhe

5001 kWh

6057 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

36 dB(A)

36 dB(A)

Sound power level outdoor

56 dB(A)

56 dB(A)

EN 14825

Low temperature

Medium temperature

Pdesignh

5.20 kW

4.78 kW

ηs

191 %

135 %

Prated

5.20 kW

4.78 kW

SCOP

4.85

3.45

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

4.60 kW

4.23 kW

COP Tj = -7°C

3.34

2.35

Pdh Tj = +2°C

2.79 kW

2.76 kW

COP Tj = +2°C

4.69

3.37

Pdh Tj = +7°C

1.84 kW

1.72 kW

COP Tj = +7°C

6.28

4.26

Pdh Tj = 12°C

1.62 kW

1.58 kW

COP Tj = 12°C

8.44

6.19

Pdh Tj = Tbiv

4.60 kW

4.23 kW

COP Tj = Tbiv

3.34

2.35

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

4.15 kW

3.74 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

3.01

2.04

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.90

0.90

WTOL

60 °C

60 °C

Poff

11 W

11 W

PTO

11 W

11 W

PSB

11 W

11 W

PCK

11 W

11 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

1.05 kW

1.04 kW

Annual energy consumption Qhe

2215 kWh

2866 kWh

AEROTOP SPLIT 04M-CRX
Configure model
Model name
AEROTOP SPLIT 04M-CRX
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-4

Operating range outdoor exchanger/indoor exchanger lower limit/lower limit

passed

Operating range outdoor exchanger/indoor exchanger upper limit/upper limit

passed

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

EN 14511-2

Low temperature

Medium temperature

Heat output

3.50 kW

2.96 kW

El input

0.69 kW

1.05 kW

COP

5.11

2.82

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

36 dB(A)

36 dB(A)

Sound power level outdoor

56 dB(A)

56 dB(A)

EN 14825

Low temperature

Medium temperature

Pdesignh

2.80 kW

2.33 kW

ηs

231 %

144 %

Prated

2.80 kW

2.33 kW

SCOP

5.86

3.67

Tbiv

2 °C

2 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

2.80 kW

2.33 kW

COP Tj = +2°C

4.12

2.30

Pdh Tj = +7°C

1.77 kW

1.56 kW

COP Tj = +7°C

5.53

2.99

Pdh Tj = 12°C

1.61 kW

1.61 kW

COP Tj = 12°C

7.73

5.65

Pdh Tj = Tbiv

2.80 kW

2.33 kW

COP Tj = Tbiv

4.12

2.30

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

2.80 kW

2.33 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.12

2.30

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.90

0.90

WTOL

60 °C

60 °C

Poff

11 W

11 W

PTO

11 W

11 W

PSB

11 W

11 W

PCK

11 W

11 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

640 kWh

848 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

36 dB(A)

36 dB(A)

Sound power level outdoor

56 dB(A)

56 dB(A)

EN 14825

Low temperature

Medium temperature

Pdesignh

7.65 kW

7.35 kW

ηs

148 %

117 %

Prated

7.65 kW

7.35 kW

SCOP

3.77

2.99

Tbiv

-7 °C

-7 °C

TOL

-20 °C

-20 °C

Pdh Tj = -7°C

4.63 kW

4.45 kW

COP Tj = -7°C

3.59

2.79

Pdh Tj = +2°C

2.85 kW

2.82 kW

COP Tj = +2°C

4.97

3.71

Pdh Tj = +7°C

1.76 kW

1.73 kW

COP Tj = +7°C

6.63

5.30

Pdh Tj = 12°C

1.62 kW

1.61 kW

COP Tj = 12°C

8.44

6.71

Pdh Tj = Tbiv

4.63 kW

4.45 kW

COP Tj = Tbiv

3.59

2.79

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

2.92 kW

2.47 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.36

1.52

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.90

0.90

WTOL

60 °C

60 °C

Poff

11 W

11 W

PTO

11 W

11 W

PSB

11 W

11 W

PCK

11 W

11 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

4.00 kW

4.00 kW

Annual energy consumption Qhe

5001 kWh

6057 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

36 dB(A)

36 dB(A)

Sound power level outdoor

56 dB(A)

56 dB(A)

EN 14825

Low temperature

Medium temperature

Pdesignh

5.20 kW

4.78 kW

ηs

191 %

135 %

Prated

5.20 kW

4.78 kW

SCOP

4.85

3.45

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

4.60 kW

4.23 kW

COP Tj = -7°C

3.34

2.35

Pdh Tj = +2°C

2.79 kW

2.76 kW

COP Tj = +2°C

4.69

3.37

Pdh Tj = +7°C

1.84 kW

1.72 kW

COP Tj = +7°C

6.28

4.26

Pdh Tj = 12°C

1.62 kW

1.58 kW

COP Tj = 12°C

8.44

6.19

Pdh Tj = Tbiv

4.60 kW

4.23 kW

COP Tj = Tbiv

3.34

2.35

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

4.15 kW

3.74 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

3.01

2.04

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.90

0.90

WTOL

60 °C

60 °C

Poff

11 W

11 W

PTO

11 W

11 W

PSB

11 W

11 W

PCK

11 W

11 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

1.05 kW

1.04 kW

Annual energy consumption Qhe

2215 kWh

2866 kWh

Domestic Hot Water (DHW)

Warmer Climate

EN 16147

Declared load profile

XL

Efficiency ηDHW

133 %

COP

3.20

Heating up time

02:46 h:min

Standby power input

39.0 W

Reference hot water temperature

52.6 °C

Mixed water at 40°C

240 l

Colder Climate

EN 16147

Declared load profile

XL

Efficiency ηDHW

95 %

COP

2.30

Heating up time

02:55 h:min

Standby power input

42.0 W

Reference hot water temperature

52.5 °C

Mixed water at 40°C

242 l

Average Climate

EN 16147

Declared load profile

XL

Efficiency ηDHW

107 %

COP

2.60

Heating up time

01:48 h:min

Standby power input

44.0 W

Reference hot water temperature

52.5 °C

Mixed water at 40°C

241 l

ARIANEXT COMPACT 40 S LINK
Configure model
Model name
ARIANEXT COMPACT 40 S LINK
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-4

Operating range outdoor exchanger/indoor exchanger lower limit/lower limit

passed

Operating range outdoor exchanger/indoor exchanger upper limit/upper limit

passed

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

EN 14511-2

Low temperature

Medium temperature

Heat output

3.50 kW

2.96 kW

El input

0.69 kW

1.05 kW

COP

5.11

2.82

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

36 dB(A)

36 dB(A)

Sound power level outdoor

56 dB(A)

56 dB(A)

EN 14825

Low temperature

Medium temperature

Pdesignh

2.80 kW

2.33 kW

ηs

231 %

144 %

Prated

2.80 kW

2.33 kW

SCOP

5.86

3.67

Tbiv

2 °C

2 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

2.80 kW

2.33 kW

COP Tj = +2°C

4.12

2.30

Pdh Tj = +7°C

1.77 kW

1.56 kW

COP Tj = +7°C

5.53

2.99

Pdh Tj = 12°C

1.61 kW

1.61 kW

COP Tj = 12°C

7.73

5.65

Pdh Tj = Tbiv

2.80 kW

2.33 kW

COP Tj = Tbiv

4.12

2.30

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

2.80 kW

2.33 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.12

2.30

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.90

0.90

WTOL

60 °C

60 °C

Poff

11 W

11 W

PTO

11 W

11 W

PSB

11 W

11 W

PCK

11 W

11 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

640 kWh

848 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

36 dB(A)

36 dB(A)

Sound power level outdoor

56 dB(A)

56 dB(A)

EN 14825

Low temperature

Medium temperature

Pdesignh

7.65 kW

7.35 kW

ηs

148 %

117 %

Prated

7.65 kW

7.35 kW

SCOP

3.77

2.99

Tbiv

-7 °C

-7 °C

TOL

-20 °C

-20 °C

Pdh Tj = -7°C

4.63 kW

4.45 kW

COP Tj = -7°C

3.59

2.79

Pdh Tj = +2°C

2.85 kW

2.82 kW

COP Tj = +2°C

4.97

3.71

Pdh Tj = +7°C

1.76 kW

1.73 kW

COP Tj = +7°C

6.63

5.30

Pdh Tj = 12°C

1.62 kW

1.61 kW

COP Tj = 12°C

8.44

6.71

Pdh Tj = Tbiv

4.63 kW

4.45 kW

COP Tj = Tbiv

3.59

2.79

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

2.92 kW

2.47 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.36

1.52

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.90

0.90

WTOL

60 °C

60 °C

Poff

11 W

11 W

PTO

11 W

11 W

PSB

11 W

11 W

PCK

11 W

11 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

4.00 kW

4.00 kW

Annual energy consumption Qhe

5001 kWh

6057 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

36 dB(A)

36 dB(A)

Sound power level outdoor

56 dB(A)

56 dB(A)

EN 14825

Low temperature

Medium temperature

Pdesignh

5.20 kW

4.78 kW

ηs

191 %

135 %

Prated

5.20 kW

4.78 kW

SCOP

4.85

3.45

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

4.60 kW

4.23 kW

COP Tj = -7°C

3.34

2.35

Pdh Tj = +2°C

2.79 kW

2.76 kW

COP Tj = +2°C

4.69

3.37

Pdh Tj = +7°C

1.84 kW

1.72 kW

COP Tj = +7°C

6.28

4.26

Pdh Tj = 12°C

1.62 kW

1.58 kW

COP Tj = 12°C

8.44

6.19

Pdh Tj = Tbiv

4.60 kW

4.23 kW

COP Tj = Tbiv

3.34

2.35

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

4.15 kW

3.74 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

3.01

2.04

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.90

0.90

WTOL

60 °C

60 °C

Poff

11 W

11 W

PTO

11 W

11 W

PSB

11 W

11 W

PCK

11 W

11 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

1.05 kW

1.04 kW

Annual energy consumption Qhe

2215 kWh

2866 kWh

Domestic Hot Water (DHW)

Warmer Climate

EN 16147

Declared load profile

XL

Efficiency ηDHW

133 %

COP

3.20

Heating up time

02:46 h:min

Standby power input

39.0 W

Reference hot water temperature

52.6 °C

Mixed water at 40°C

240 l

Colder Climate

EN 16147

Declared load profile

XL

Efficiency ηDHW

95 %

COP

2.30

Heating up time

02:55 h:min

Standby power input

42.0 W

Reference hot water temperature

52.5 °C

Mixed water at 40°C

242 l

Average Climate

EN 16147

Declared load profile

XL

Efficiency ηDHW

107 %

COP

2.60

Heating up time

01:48 h:min

Standby power input

44.0 W

Reference hot water temperature

52.5 °C

Mixed water at 40°C

241 l

ARIANEXT FLEX 40 S LINK
Configure model
Model name
ARIANEXT FLEX 40 S LINK
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-4

Operating range outdoor exchanger/indoor exchanger lower limit/lower limit

passed

Operating range outdoor exchanger/indoor exchanger upper limit/upper limit

passed

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

EN 14511-2

Low temperature

Medium temperature

Heat output

3.50 kW

2.96 kW

El input

0.69 kW

1.05 kW

COP

5.11

2.82

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

36 dB(A)

36 dB(A)

Sound power level outdoor

56 dB(A)

56 dB(A)

EN 14825

Low temperature

Medium temperature

Pdesignh

2.80 kW

2.33 kW

ηs

231 %

144 %

Prated

2.80 kW

2.33 kW

SCOP

5.86

3.67

Tbiv

2 °C

2 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

2.80 kW

2.33 kW

COP Tj = +2°C

4.12

2.30

Pdh Tj = +7°C

1.77 kW

1.56 kW

COP Tj = +7°C

5.53

2.99

Pdh Tj = 12°C

1.61 kW

1.61 kW

COP Tj = 12°C

7.73

5.65

Pdh Tj = Tbiv

2.80 kW

2.33 kW

COP Tj = Tbiv

4.12

2.30

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

2.80 kW

2.33 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.12

2.30

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.90

0.90

WTOL

60 °C

60 °C

Poff

11 W

11 W

PTO

11 W

11 W

PSB

11 W

11 W

PCK

11 W

11 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

640 kWh

848 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

36 dB(A)

36 dB(A)

Sound power level outdoor

56 dB(A)

56 dB(A)

EN 14825

Low temperature

Medium temperature

Pdesignh

7.65 kW

7.35 kW

ηs

148 %

117 %

Prated

7.65 kW

7.35 kW

SCOP

3.77

2.99

Tbiv

-7 °C

-7 °C

TOL

-20 °C

-20 °C

Pdh Tj = -7°C

4.63 kW

4.45 kW

COP Tj = -7°C

3.59

2.79

Pdh Tj = +2°C

2.85 kW

2.82 kW

COP Tj = +2°C

4.97

3.71

Pdh Tj = +7°C

1.76 kW

1.73 kW

COP Tj = +7°C

6.63

5.30

Pdh Tj = 12°C

1.62 kW

1.61 kW

COP Tj = 12°C

8.44

6.71

Pdh Tj = Tbiv

4.63 kW

4.45 kW

COP Tj = Tbiv

3.59

2.79

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

2.92 kW

2.47 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.36

1.52

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.90

0.90

WTOL

60 °C

60 °C

Poff

11 W

11 W

PTO

11 W

11 W

PSB

11 W

11 W

PCK

11 W

11 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

4.00 kW

4.00 kW

Annual energy consumption Qhe

5001 kWh

6057 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

36 dB(A)

36 dB(A)

Sound power level outdoor

56 dB(A)

56 dB(A)

EN 14825

Low temperature

Medium temperature

Pdesignh

5.20 kW

4.78 kW

ηs

191 %

135 %

Prated

5.20 kW

4.78 kW

SCOP

4.85

3.45

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

4.60 kW

4.23 kW

COP Tj = -7°C

3.34

2.35

Pdh Tj = +2°C

2.79 kW

2.76 kW

COP Tj = +2°C

4.69

3.37

Pdh Tj = +7°C

1.84 kW

1.72 kW

COP Tj = +7°C

6.28

4.26

Pdh Tj = 12°C

1.62 kW

1.58 kW

COP Tj = 12°C

8.44

6.19

Pdh Tj = Tbiv

4.60 kW

4.23 kW

COP Tj = Tbiv

3.34

2.35

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

4.15 kW

3.74 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

3.01

2.04

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.90

0.90

WTOL

60 °C

60 °C

Poff

11 W

11 W

PTO

11 W

11 W

PSB

11 W

11 W

PCK

11 W

11 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

1.05 kW

1.04 kW

Annual energy consumption Qhe

2215 kWh

2866 kWh

Domestic Hot Water (DHW)

Warmer Climate

EN 16147

Declared load profile

XL

Efficiency ηDHW

133 %

COP

3.20

Heating up time

02:46 h:min

Standby power input

39.0 W

Reference hot water temperature

52.6 °C

Mixed water at 40°C

240 l

Colder Climate

EN 16147

Declared load profile

XL

Efficiency ηDHW

95 %

COP

2.30

Heating up time

02:55 h:min

Standby power input

42.0 W

Reference hot water temperature

52.5 °C

Mixed water at 40°C

242 l

Average Climate

EN 16147

Declared load profile

XL

Efficiency ηDHW

107 %

COP

2.60

Heating up time

01:48 h:min

Standby power input

44.0 W

Reference hot water temperature

52.5 °C

Mixed water at 40°C

241 l

NIMBUS COMPACT 40 S NET
Configure model
Model name
NIMBUS COMPACT 40 S NET
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-4

Operating range outdoor exchanger/indoor exchanger lower limit/lower limit

passed

Operating range outdoor exchanger/indoor exchanger upper limit/upper limit

passed

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

EN 14511-2

Low temperature

Medium temperature

Heat output

3.50 kW

2.96 kW

El input

0.69 kW

1.05 kW

COP

5.11

2.82

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

36 dB(A)

36 dB(A)

Sound power level outdoor

56 dB(A)

56 dB(A)

EN 14825

Low temperature

Medium temperature

Pdesignh

2.80 kW

2.33 kW

ηs

231 %

144 %

Prated

2.80 kW

2.33 kW

SCOP

5.86

3.67

Tbiv

2 °C

2 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

2.80 kW

2.33 kW

COP Tj = +2°C

4.12

2.30

Pdh Tj = +7°C

1.77 kW

1.56 kW

COP Tj = +7°C

5.53

2.99

Pdh Tj = 12°C

1.61 kW

1.61 kW

COP Tj = 12°C

7.73

5.65

Pdh Tj = Tbiv

2.80 kW

2.33 kW

COP Tj = Tbiv

4.12

2.30

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

2.80 kW

2.33 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.12

2.30

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.90

0.90

WTOL

60 °C

60 °C

Poff

11 W

11 W

PTO

11 W

11 W

PSB

11 W

11 W

PCK

11 W

11 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

640 kWh

848 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

36 dB(A)

36 dB(A)

Sound power level outdoor

56 dB(A)

56 dB(A)

EN 14825

Low temperature

Medium temperature

Pdesignh

7.65 kW

7.35 kW

ηs

148 %

117 %

Prated

7.65 kW

7.35 kW

SCOP

3.77

2.99

Tbiv

-7 °C

-7 °C

TOL

-20 °C

-20 °C

Pdh Tj = -7°C

4.63 kW

4.45 kW

COP Tj = -7°C

3.59

2.79

Pdh Tj = +2°C

2.85 kW

2.82 kW

COP Tj = +2°C

4.97

3.71

Pdh Tj = +7°C

1.76 kW

1.73 kW

COP Tj = +7°C

6.63

5.30

Pdh Tj = 12°C

1.62 kW

1.61 kW

COP Tj = 12°C

8.44

6.71

Pdh Tj = Tbiv

4.63 kW

4.45 kW

COP Tj = Tbiv

3.59

2.79

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

2.92 kW

2.47 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.36

1.52

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.90

0.90

WTOL

60 °C

60 °C

Poff

11 W

11 W

PTO

11 W

11 W

PSB

11 W

11 W

PCK

11 W

11 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

4.00 kW

4.00 kW

Annual energy consumption Qhe

5001 kWh

6057 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

36 dB(A)

36 dB(A)

Sound power level outdoor

56 dB(A)

56 dB(A)

EN 14825

Low temperature

Medium temperature

Pdesignh

5.20 kW

4.78 kW

ηs

191 %

135 %

Prated

5.20 kW

4.78 kW

SCOP

4.85

3.45

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

4.60 kW

4.23 kW

COP Tj = -7°C

3.34

2.35

Pdh Tj = +2°C

2.79 kW

2.76 kW

COP Tj = +2°C

4.69

3.37

Pdh Tj = +7°C

1.84 kW

1.72 kW

COP Tj = +7°C

6.28

4.26

Pdh Tj = 12°C

1.62 kW

1.58 kW

COP Tj = 12°C

8.44

6.19

Pdh Tj = Tbiv

4.60 kW

4.23 kW

COP Tj = Tbiv

3.34

2.35

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

4.15 kW

3.74 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

3.01

2.04

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.90

0.90

WTOL

60 °C

60 °C

Poff

11 W

11 W

PTO

11 W

11 W

PSB

11 W

11 W

PCK

11 W

11 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

1.05 kW

1.04 kW

Annual energy consumption Qhe

2215 kWh

2866 kWh

Domestic Hot Water (DHW)

Warmer Climate

EN 16147

Declared load profile

XL

Efficiency ηDHW

133 %

COP

3.20

Heating up time

02:46 h:min

Standby power input

39.0 W

Reference hot water temperature

52.6 °C

Mixed water at 40°C

240 l

Colder Climate

EN 16147

Declared load profile

XL

Efficiency ηDHW

95 %

COP

2.30

Heating up time

02:55 h:min

Standby power input

42.0 W

Reference hot water temperature

52.5 °C

Mixed water at 40°C

242 l

Average Climate

EN 16147

Declared load profile

XL

Efficiency ηDHW

107 %

COP

2.60

Heating up time

01:48 h:min

Standby power input

44.0 W

Reference hot water temperature

52.5 °C

Mixed water at 40°C

241 l

NIMBUS FLEX 40 S NET
Configure model
Model name
NIMBUS FLEX 40 S NET
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-4

Operating range outdoor exchanger/indoor exchanger lower limit/lower limit

passed

Operating range outdoor exchanger/indoor exchanger upper limit/upper limit

passed

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

EN 14511-2

Low temperature

Medium temperature

Heat output

3.50 kW

2.96 kW

El input

0.69 kW

1.05 kW

COP

5.11

2.82

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

36 dB(A)

36 dB(A)

Sound power level outdoor

56 dB(A)

56 dB(A)

EN 14825

Low temperature

Medium temperature

Pdesignh

2.80 kW

2.33 kW

ηs

231 %

144 %

Prated

2.80 kW

2.33 kW

SCOP

5.86

3.67

Tbiv

2 °C

2 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

2.80 kW

2.33 kW

COP Tj = +2°C

4.12

2.30

Pdh Tj = +7°C

1.77 kW

1.56 kW

COP Tj = +7°C

5.53

2.99

Pdh Tj = 12°C

1.61 kW

1.61 kW

COP Tj = 12°C

7.73

5.65

Pdh Tj = Tbiv

2.80 kW

2.33 kW

COP Tj = Tbiv

4.12

2.30

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

2.80 kW

2.33 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.12

2.30

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.90

0.90

WTOL

60 °C

60 °C

Poff

11 W

11 W

PTO

11 W

11 W

PSB

11 W

11 W

PCK

11 W

11 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

640 kWh

848 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

36 dB(A)

36 dB(A)

Sound power level outdoor

56 dB(A)

56 dB(A)

EN 14825

Low temperature

Medium temperature

Pdesignh

7.65 kW

7.35 kW

ηs

148 %

117 %

Prated

7.65 kW

7.35 kW

SCOP

3.77

2.99

Tbiv

-7 °C

-7 °C

TOL

-20 °C

-20 °C

Pdh Tj = -7°C

4.63 kW

4.45 kW

COP Tj = -7°C

3.59

2.79

Pdh Tj = +2°C

2.85 kW

2.82 kW

COP Tj = +2°C

4.97

3.71

Pdh Tj = +7°C

1.76 kW

1.73 kW

COP Tj = +7°C

6.63

5.30

Pdh Tj = 12°C

1.62 kW

1.61 kW

COP Tj = 12°C

8.44

6.71

Pdh Tj = Tbiv

4.63 kW

4.45 kW

COP Tj = Tbiv

3.59

2.79

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

2.92 kW

2.47 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.36

1.52

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.90

0.90

WTOL

60 °C

60 °C

Poff

11 W

11 W

PTO

11 W

11 W

PSB

11 W

11 W

PCK

11 W

11 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

4.00 kW

4.00 kW

Annual energy consumption Qhe

5001 kWh

6057 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

36 dB(A)

36 dB(A)

Sound power level outdoor

56 dB(A)

56 dB(A)

EN 14825

Low temperature

Medium temperature

Pdesignh

5.20 kW

4.78 kW

ηs

191 %

135 %

Prated

5.20 kW

4.78 kW

SCOP

4.85

3.45

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

4.60 kW

4.23 kW

COP Tj = -7°C

3.34

2.35

Pdh Tj = +2°C

2.79 kW

2.76 kW

COP Tj = +2°C

4.69

3.37

Pdh Tj = +7°C

1.84 kW

1.72 kW

COP Tj = +7°C

6.28

4.26

Pdh Tj = 12°C

1.62 kW

1.58 kW

COP Tj = 12°C

8.44

6.19

Pdh Tj = Tbiv

4.60 kW

4.23 kW

COP Tj = Tbiv

3.34

2.35

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

4.15 kW

3.74 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

3.01

2.04

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.90

0.90

WTOL

60 °C

60 °C

Poff

11 W

11 W

PTO

11 W

11 W

PSB

11 W

11 W

PCK

11 W

11 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

1.05 kW

1.04 kW

Annual energy consumption Qhe

2215 kWh

2866 kWh

Domestic Hot Water (DHW)

Warmer Climate

EN 16147

Declared load profile

XL

Efficiency ηDHW

133 %

COP

3.20

Heating up time

02:46 h:min

Standby power input

39.0 W

Reference hot water temperature

52.6 °C

Mixed water at 40°C

240 l

Colder Climate

EN 16147

Declared load profile

XL

Efficiency ηDHW

95 %

COP

2.30

Heating up time

02:55 h:min

Standby power input

42.0 W

Reference hot water temperature

52.5 °C

Mixed water at 40°C

242 l

Average Climate

EN 16147

Declared load profile

XL

Efficiency ηDHW

107 %

COP

2.60

Heating up time

01:48 h:min

Standby power input

44.0 W

Reference hot water temperature

52.5 °C

Mixed water at 40°C

241 l

ARIANEXT COMPACT 40 S
Configure model
Model name
ARIANEXT COMPACT 40 S
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-4

Operating range outdoor exchanger/indoor exchanger lower limit/lower limit

passed

Operating range outdoor exchanger/indoor exchanger upper limit/upper limit

passed

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

EN 14511-2

Low temperature

Medium temperature

Heat output

3.50 kW

2.96 kW

El input

0.69 kW

1.05 kW

COP

5.11

2.82

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

36 dB(A)

36 dB(A)

Sound power level outdoor

56 dB(A)

56 dB(A)

EN 14825

Low temperature

Medium temperature

Pdesignh

5.20 kW

4.78 kW

ηs

191 %

135 %

Prated

5.20 kW

4.78 kW

SCOP

4.85

3.45

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

4.60 kW

4.23 kW

COP Tj = -7°C

3.34

2.35

Pdh Tj = +2°C

2.79 kW

2.76 kW

COP Tj = +2°C

4.69

3.37

Pdh Tj = +7°C

1.84 kW

1.72 kW

COP Tj = +7°C

6.28

4.26

Pdh Tj = 12°C

1.62 kW

1.58 kW

COP Tj = 12°C

8.44

6.19

Pdh Tj = Tbiv

4.60 kW

4.23 kW

COP Tj = Tbiv

3.34

2.35

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

4.15 kW

3.74 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

3.01

2.04

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.90

0.90

WTOL

60 °C

60 °C

Poff

11 W

11 W

PTO

11 W

11 W

PSB

11 W

11 W

PCK

11 W

11 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

1.05 kW

1.04 kW

Annual energy consumption Qhe

2215 kWh

2866 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

131 %

COP

3.10

Heating up time

01:34 h:min

Standby power input

38.0 W

Reference hot water temperature

53.0 °C

Mixed water at 40°C

250 l

ARIANEXT FLEX 40 S
Configure model
Model name
ARIANEXT FLEX 40 S
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-4

Operating range outdoor exchanger/indoor exchanger lower limit/lower limit

passed

Operating range outdoor exchanger/indoor exchanger upper limit/upper limit

passed

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

EN 14511-2

Low temperature

Medium temperature

Heat output

3.50 kW

2.96 kW

El input

0.69 kW

1.05 kW

COP

5.11

2.82

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

36 dB(A)

36 dB(A)

Sound power level outdoor

56 dB(A)

56 dB(A)

EN 14825

Low temperature

Medium temperature

Pdesignh

5.20 kW

4.78 kW

ηs

191 %

135 %

Prated

5.20 kW

4.78 kW

SCOP

4.85

3.45

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

4.60 kW

4.23 kW

COP Tj = -7°C

3.34

2.35

Pdh Tj = +2°C

2.79 kW

2.76 kW

COP Tj = +2°C

4.69

3.37

Pdh Tj = +7°C

1.84 kW

1.72 kW

COP Tj = +7°C

6.28

4.26

Pdh Tj = 12°C

1.62 kW

1.58 kW

COP Tj = 12°C

8.44

6.19

Pdh Tj = Tbiv

4.60 kW

4.23 kW

COP Tj = Tbiv

3.34

2.35

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

4.15 kW

3.74 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

3.01

2.04

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.90

0.90

WTOL

60 °C

60 °C

Poff

11 W

11 W

PTO

11 W

11 W

PSB

11 W

11 W

PCK

11 W

11 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

1.05 kW

1.04 kW

Annual energy consumption Qhe

2215 kWh

2866 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

131 %

COP

3.10

Heating up time

01:34 h:min

Standby power input

38.0 W

Reference hot water temperature

53.0 °C

Mixed water at 40°C

250 l